EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Table C1. Input/Output Points (Left Continued).

 

 

 

 

Digital

 

 

 

 

 

State

 

 

 

 

 

or

 

 

 

 

Engineering Units:

Value

 

 

 

 

English (Metric) or

of

 

User Address

NvName

Field Name

States plus Range

State

Default

 

 

 

 

 

 

DI3Sel1Type

ncirioIoSelect

DigitalIn2S1

See DI1Sel1Type Eng. Units/States

 

Unused_DigInput

 

 

 

column for selections.

 

 

 

 

 

 

 

 

DI4Sel1Type

ncirioIoSelect

DigitalIn3S1

See DI1Sel1Type Eng. Units/States

 

Unused_DigInput

 

 

 

column for selections.

 

 

 

 

 

 

 

 

DI1Sel2Type

ncirioIoSelect

DigitalIn0S2

Momentary

0

Maintained

 

 

 

Maintained

1

 

 

 

 

Unused_DigInput

255

 

 

 

 

 

 

 

DI2Sel2Type

ncirioIoSelect

DigitalIn1S2

See DI1Sel2Type Eng. Units/States

 

Maintained

 

 

 

column for selections.

 

 

 

 

 

 

 

 

DI3Sel2Type

ncirioIoSelect

DigitalIn2S2

See DI1Sel2Type Eng. Units/States

 

Maintained

 

 

 

column for selections.

 

 

 

 

 

 

 

 

DI4Sel2Type

ncirioIoSelect

DigitalIn3S2

See DI1Sel2Type Eng. Units/States

 

Maintained

 

 

 

column for selections.

 

 

 

 

 

 

 

 

DO1Type

ncirioIoSelect

DigitalOut0

Discrete1

0

Unused_DigOutput

 

 

 

Discrete2

1

 

 

 

 

Discrete3

2

 

 

 

 

Discrete4

3

 

 

 

 

Discrete5

4

 

 

 

 

Discrete6

5

 

 

 

 

Discrete7

6

 

 

 

 

Discrete8

7

 

 

 

 

Modulate1

8

 

 

 

 

Modulate2

9

 

 

 

 

Modulate3

10

 

 

 

 

Modulate4

11

 

 

 

 

Modulate5

12

 

 

 

 

Modulate6

13

 

 

 

 

Modulate7

14

 

 

 

 

Modulate8

15

 

 

 

 

Float1_Open

16

 

 

 

 

Float2_Open

17

 

 

 

 

Float3_Open

18

 

 

 

 

Float4_Open

19

 

 

 

 

Float5_Open

20

 

 

 

 

Float6_Open

21

 

 

 

 

Float7_Open

22

 

 

 

 

Float8_Open

23

 

 

 

 

Float1_Close

24

 

 

 

 

Float2_Close

25

 

 

 

 

Float3_Close

26

 

 

 

 

Float4_Close

27

 

 

 

 

Float5_Close

28

 

 

 

 

Float6_Close

29

 

 

 

 

Float7_Close

30

 

 

 

 

Float8_Close

31

 

 

 

 

Unused_DigOutput

255

 

 

 

 

 

 

 

49

74-2699

Image 49
Contents Excel 10 W7761A Remote Input/Output Device Appendices List of TablesTypical system overview Description of DevicesControl Provided Control ApplicationProducts Covered Organization of ManualProduct Names Abbreviations and Definitions Agency ListingsExcel 10 W7761A INPUT/OUTPUT Device Controllers ConstructionExcel 10 W7761A Remote I/O Device W7761A construction in in. mm List Of Available Points W7761A Performance Specifications PowerEnvironmental Operating Temperature Specified Space Temperature Sensing RangeShipping Temperature Memory CapacityOutdoor Air Temperature Discharge Air TemperatureReturn Air Temperature Mixed Air Temperature5585 Wall ModulesT7780 construction, subbase dimensions in in. mm ConfigurationsOccupancy Sensor Mixed-Output-Type ControlWindow Open/Closed Digital Input Wall Module OptionsPlan The System OverviewApplication Steps Step No Description Determine Other Bus Devices Required Lay Out Communications and Power WiringBus Layout 750,1$ Power Budget Calculation Example Power WiringLine Loss VA Ratings For Transformer Sizing Device DescriptionNema class 2 transformer voltage output limits VA RatingLine VOLTAGE` GREATER` Than 150 VAC General Considerations Prepare Wiring DiagramsW7761A Devices Terminal Number Description W7761A I/O DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Typical Pneumatic transducer Series 60 Floating to W7761A Bus Termination ModuleSee for E-Bus termination wiring options +$672 Excel 10 W7750 Controllers Order EquipmentT7770 Wall Modules SensorsEchelon Based Components and Parts AccessoriesCabling Temperature Degrees Excel 10 Alarms Broadcasting the Service MessageW7761A Device Status LED LED States T7780 Ddwm Bypass PushbuttonAdding Analog Inputs Enthalpy 4 to 20 mA Appendix A. Using E-Vision to Commission a W7761 DeviceAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Appendix B. Sequences of Operation Room Temperature Sensor RmTempCommon Operations Dirty Filter Monitor Window Sensor StatusWndwSeries 60 Modulating Control Pulse Width Modulating PWM ControlRelative Temperature Relative HumidityAir Flow CO 2 ConcentrationTable C1. Input/Output Points Left DefaultTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left SH MA DA EV HW MN TS Table C2. Control Parameters RightTable C3. Status Points Left NoalarmTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Right Table C5. Direct Access And Special Points LeftFig. D-1. Point capacity estimate for Zone Manager Approximate Memory Size Estimating ProcedureResistance Sensors Appendix E. Sensor Data for CalibrationSensor Type Sensor Use1956.79 Table E-4. Sensor Voltage Versus Humidity Voltage/Current SensorsHumidity Percentage Sensor Voltage C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts CO 2 Concentration PPM Sensor Voltage Table E-9. Sensor Voltage Versus CO 2 ConcentrationTable E-10. Sensor Voltage Versus Input Voltage To A/D Table E-11. Sensor Voltage Vdc Versus Pressure Inw Voltage to A/D Sensor VoltagePressure Inw kPa Sensor Voltage Vdc 3ODD