LXM32M | 5 Commissioning |
|
|
5.3Setting the transmission rate
The parameter EthRateSet lets you set the transmission rate.
▶Set the desired transmission rate with the parameter EthRateSet.
Parameter name | Description | Unit | Data type | Parameter address | |
HMI menu |
|
| Minimum value | R/W | via fieldbus |
HMI name |
|
| Factory setting | Persistent |
|
|
|
| Maximum value | Expert |
|
|
|
|
|
| |
EthRateSet | Transmission rate setting | - | UINT16 | CANopen 3044:2h | |
| 0 | / Autodetect: Autodetect | 0 | UINT16 | Modbus 17412 |
| 0 | UINT16 | Profibus 17412 | ||
| 1 | / 10 Mbps Full: 10 Mbps full duplex | |||
| 4 | UINT16 | CIP 168.1.2 | ||
| 2 | / 10 Mbps Half: 10 Mbps half duplex | |||
|
| R/W |
| ||
| 3 | / 100 Mbps Full: 100 Mbps full duplex |
|
| |
|
| per. |
| ||
| 4 | / 100 Mbps Half: 100 Mbps half duplex |
|
| |
|
| - |
| ||
|
|
|
|
| |
| Changed settings become active immedi- |
|
|
| |
| ately. |
|
|
| |
|
|
|
|
|
|
5.4Setting the protocol
The protocol is set by means of the parameter EthMode.
▶Set the parameter EthMode to "Modbus TCP".
Parameter name | Description | Unit | Data type | Parameter address | |
HMI menu |
| Minimum value | R/W | via fieldbus | |
HMI name |
| Factory setting | Persistent |
| |
|
| Maximum value | Expert |
| |
|
|
|
|
| |
EthMode | Protocol | - | UINT16 | CANopen 3044:1h | |
ConF → CoM- | 0 / Modbus TCP / MtCP : Modbus TCP I/O | 0 | UINT16 | Modbus 17410 | |
1 | UINT16 | Profibus 17410 | |||
EtMd | scanning is enabled | 1 | UINT16 | CIP 168.1.1 | |
1 / EtherNet/IP / EtiP : EtherNet/IP commu- | |||||
|
| R/W |
| ||
| nication is enabled |
| per. |
| |
| NOTE: Modbus TCP parameter access is |
| - |
| |
| possible irrespective of the selected setting. |
|
|
| |
| Changed settings become active the next |
|
|
| |
| time the product is switched on. |
|
|
| |
|
|
|
|
|
0198441113843, V1.01, 01.2012