6 Operation | LXM32M |
|
|
6.3Extended settings
6.3.1Web server
Functions The product features an integrated web server.
The web server offers the following features:
•Display status information
•Display and change parameters
•Display and change network settings
•Display and change Modbus TCP settings
•Display and change EtherNet/IP settings
•Display and change settings for the FDR service
•Display network statistics
•
6.3.1.1 Setting the web server
The web server is activated or deactivated by means of the parameter
EthWebserver.
▶If you do not want to use the web server, set the parameter
EthWebserver to "Off".
Parameter name | Description | Unit | Data type | Parameter address |
HMI menu |
| Minimum value | R/W | via fieldbus |
HMI name |
| Factory setting | Persistent |
|
|
| Maximum value | Expert |
|
|
|
|
|
|
EthWebserver | Ethernet webserver | - | UINT16 | CANopen 3044:6h |
| 0 / Off: Ethernet webserver off | 0 | UINT16 | Modbus 17420 |
| 1 | UINT16 | Profibus 17420 | |
| 1 / On: Ethernet webserver on | |||
| 1 | UINT16 | CIP 168.1.6 | |
|
| |||
| Changed settings become active the next |
| R/W |
|
| time the product is switched on. |
| per. |
|
|
|
| - |
|
|
|
|
|
|
6.3.1.2 Accessing the web server
The web server of the product can be accessed via a Web browser.
■The product must have a valid IP address. ▶ Start an Internet browser.
▶ Enter the IP address of the product in the address bar.
▶ Enter "USER" as the username and the password (uppercase).
0198441113843, V1.01, 01.2012
64 |