Pelco C3463M-B manual Activate AUX, Current Reading, Reset Alert, None default Not activated

Page 49

ACTIVATE AUX

This setting activates an auxiliary when an alert condition exists. Settings include the following options:

NONE (default): Not activated.

1:An alert condition will close AUX 1.

2:An alert condition will close AUX 2.

CURRENT READING

The Current Reading menu displays the existing status of temperature, pressure, and dew point inside the dome system. An arrow displayed to the left of a menu item denotes that an alert condition exists.

CURRENT READING

TEMPERATURE

DEWPOINT

PRESSURE

REFRESH

BACK

EXIT

An up arrow indicates the reading is over the threshold. A down arrow indicates the reading is below the threshold.

The high temperature alert occurs if the temperature is above 140°F (60°C).

The low temperature alert occurs if the temperature is below –40°F (–40°C).

The high pressure alert occurs if the pressure is above 13 PSIG.

The low pressure alert occurs if the pressure is below 1 PSIG.

The dew point (high humidity) alert occurs if the difference between the temperature and the dew point is less than or equal to 3°C.

NOTE: The normal operating temperature inside the unit will be greater than the temperature outside the back box due to the heat emitted by the system’s electronics.

RESET ALERT

Reset alert clears the alert condition and removes the alert label from the monitor. The system automatically checks internal conditions 60 seconds after reset. If conditions are still unacceptable, the alert label reappears on the screen indicating further corrective action is required.

C3463M-B (2/11)

49

Image 49
Contents Spectra IV SL and Spectra IV SE Series Page Contents Field Align Page Description Switch Settings InstallationSW2 Switches 6 to 8 Baud Settings SW2 Switches 4 and 5 Serial Port SettingsAddress Dome DriveOperation Quick Configuration GuideQuick Operation Guide Extended Coaxitron or RS-485 Mode Preset 95 Accessing Main MenuDigital Sentry System Software Endura WorkstationDigital Sentry DS Controlpoint 23X LowLight Day/Night Menu Tree Line Sync Presets Dome SettingsAlarms Password Edit the Password27X LowLight Day/Night Menu Tree Alert Current Reading Clear PasswordLabel Position Patterns ZonesEvent Edit Event Power UP Line Sync Presets Motion Detection35X LowLight Day/Night Menu Tree Azimuth Elevation Zoom Custom Camera Settings Language Reset Camera Cycle Camera Power Reboot System ExitSpectra Language System Information DIP Switch InformationExit Display Setup Preset Label Display SetupRestore Factory Defaults Back Exit Label Positions Title Text Save and Exit Cancel HelpEvent Alert MessageCamera Dome SettingsType of Lighting Auto FocusZoom Speed Zoom LimitLOW Light Limit PT Focus LockAuto IR Level IR CUT FilterLow Light Focus Shutter Speed Advanced Camera SettingsAGC Limit Auto IrisAuto White Balance Auto SharpnessBacklight Compensation Electronic Image StabilizationLOW LUX Noise Reduction OFF Low lux noise reduction is disabledVideo Level Field AlignLOW Light Sharpness Motion SettingsMinimum Focus Distance Auto FlipPark Time Preset Freeze FrameScan Speed Limit StopsAuto Tracking Power UP Start Time Line Sync Zoom Presets Lost ActionAzimuth Zero Auto TrackingSensitivity Display SetupStart Time ZoomPower UP Action Power UPBack Exit Power UP Power UP Action Table C. Stored Presets by Back Box Model PresetsBack Exit Line Sync Line Sync Phase Back Exit Presets Preset NumberPreset 92 to 93 Scan limit stops Preset 94 Reserved Preset 83 to 87 ReservedPreset 95 Select main configuration menu Preset 96 Stop a scanAbcdefghij Cancel Klmnopqrst Uvwxyz Label for Preset Preset NumberSpace Motion Detection Enable Motion DetectionEdit Detection Areas Edit Schedule Activate Aux CommandAux Time Back Exit Patterns PatternsBack Exit Back Exit Zones Zone Number ZonesEdit Zone Label Clear Zone Back ExitWindow Blanking Enable Window Reverse Clear Window Back ExitTo set a window blanking area Reverse DisabledClear Window Blank All Above Blank All Below Blank ALL ABOVE/BLANK ALL belowBlanked Area Alarms C3463M-B 2/11 AUX Back Exit AUX AUX 1 Mode Toggle Dwell Time Secs AUX 2 ModeDwell Time Secs Edit Schedule Back Exit Back Exit Title Text Title TextEdit Title Text Repeat AlertACK Action System Condition Alert MessageNone default Not activated Reset AlertActivate AUX Current ReadingBack Exit Password PasswordEnable Password Edit Password Back Abcdefghij Cancel Klmnopqrst Exit UvwxyzClock Follow the instructions in for Fixed DATE, adding Week Event Type EventBack Exit Event Event Type Event Label HolidayEdit Event Label Event LabelEdit Event List Event Clear EventHoliday Edit HolidayList Holidays Clear HolidayEdit Holiday Occurrence Month January DAY Back ExitScheduled Events Example Preset Weekend 1100 AM Sat-SunUse this page to record scheduled events Reset Camera Reset, Cycle Power, RebootCycle Camera Power Reboot SystemSoftware/Language File Upload Maintenance Signal Format Specifications23X Models Zoom Speed 4.2/5.8 seconds Horizontal Angle of ViewDD427 27X ModelsDD4CBW35 35X ModelsAppendix Table F. Switch Settings for SW1 Pelco P-Type ControlSpectra Switch Setting Address Table G. Switch Settings for SW1 Pelco D-Type Control 1Table G. Switch Settings for SW1 Pelco D-Type Control 2 Table G. Switch Settings for SW1 Pelco D-Type Control 3 Table G. Switch Settings for SW1 Pelco D-Type Control 4 Table G. Switch Settings for SW1 Pelco D-Type Control 5 Table G. Switch Settings for SW1 Pelco D-Type Control 6 Product Warranty and Return Information