Mitsubishi Electronics FR-V500 Level regeneration 813 Torque restriction, Acceleration torque

Page 71

PARAMETERS

Function list (Extended function parameters)

 

 

 

 

 

 

At-a-glance Guide to Func-

 

 

 

 

 

 

 

tions

 

 

 

 

 

 

 

": Usable function

Function

Parameter

 

 

 

Cus-

×: Unusable function

 

 

 

 

 

* : Functions that can be used

 

 

Name

Outline

Factory

tomer

 

 

for param eter-set position con-

 

 

Setting

Set-

 

 

 

 

 

trol

 

 

 

 

 

 

ting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vector Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed

Torque

Position

 

 

 

 

 

 

control

control

control

 

 

 

 

 

 

 

 

 

 

812

Torque restriction

0 to 400%, 9999

9999

 

"

×

"

 

 

level (regeneration)

 

 

 

 

 

 

 

813

Torque restriction

0 to 400%, 9999

9999

 

"

×

"

 

 

level (3 quadrant)

 

 

 

 

 

 

 

814

Torque restriction

0 to 400%, 9999

9999

 

"

×

"

 

 

level (4 quadrant)

 

 

 

 

 

 

 

815

Torque restriction

Second function of the torque restriction level. Made valid when the RT terminal is on.

9999

 

"

×

"

 

 

level 2

0 to 400%, 9999

 

 

 

 

 

 

816

Acceleration torque

Set the torque restriction value during acceleration.

9999

 

"

×

"

 

 

restriction

0 to 400%, 9999

 

 

 

 

 

 

817

Deceleration torque

Set the torque restriction value during deceleration.

9999

 

"

×

"

 

 

restriction

0 to 400%, 9999

 

 

 

 

 

functions

818

Easy gain tuning

1 to 15

2

 

"

×

"

 

response level setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

819

Easy gain tuning

0,1,2

0

 

"

×

"

system

selection

 

 

 

 

 

 

 

 

 

820

Speed control P gain

in response to a speed command change and reduces speed variation with

60%

 

"

×

"

Control

 

 

Set the proportional gain for speed control. (Increasing the value improves trackability

 

 

 

 

 

 

1

disturbance.)

 

 

 

 

 

 

 

 

0 to 1000%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

821

Speed control

Set the integral time during speed control. (Decrease the value to shorten the time

 

 

"

×

"

 

taken for returning to the original speed if speed variation with disturbance occurs.)

0.333s

 

 

 

integral time 1

0 to 20s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

822

Speed setting filter 1

Set the primary delay filter for the analog voltage-based speed setting.

0s

 

"

"

×

 

0 to 5s

 

 

 

 

 

 

 

 

 

 

823

Speed detection filter

Set the primary delay filter for the speed feedback.

0.001s

 

"

"

"

 

 

1

0 to 5s

 

 

 

 

 

 

 

Torque control P gain

Set the proportional gain for the current control of the q and d axes. (Increasing the

 

 

 

 

 

 

824

value improves trackability in response to a current command change and reduces

100%

 

"

"

"

 

 

1

current variation with disturbance.)

 

 

 

 

 

 

 

 

0 to 200%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Torque control

Set the integral time for the current control of the q and d axes. (Decreasing the value

 

 

 

 

 

 

825

shortens the time taken to return to the original torque if current variation with

5ms

 

"

"

"

 

 

integral time 1

disturbance occurs.)

 

 

 

 

 

 

 

 

0 to 500ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the primary delay filter for the analog voltage (No. 3 terminal)-based torque

 

 

 

 

 

functions

826

Torque setting filter 1

command value. (Also valid for the torque restriction from the No. 3 terminal during

0s

 

"

"

"

 

 

speed control.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 to 5s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system

827

Torque detection filter

Set the primary delay filter for the current feedback.

0s

 

"

"

"

 

1

0 to 5s

 

 

 

 

 

 

 

 

 

 

 

 

Control

828

Model speed control

0 to 1000%

60%

 

"

×

"

 

Speed control P gain

Second function of Pr. 820 (valid when RT terminal is on)

 

 

 

 

 

 

 

gain

 

 

 

 

 

 

 

830

2

0 to 1000%, 9999

9999

 

"

×

"

 

 

 

 

 

 

 

 

 

 

831

Speed control

Second function of Pr. 821 (valid when RT terminal is on)

9999

 

"

×

"

 

 

integral time 2

0 to 20s, 9999

 

 

 

 

 

 

832

Speed setting filter 2

Second function of Pr. 822 (valid when RT terminal is on)

9999

 

"

"

×

functions

0 to 5s, 9999

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

833

Speed detection filter

Second function of Pr. 823 (valid when RT terminal is on)

9999

 

"

"

"

 

 

2

0 to 5s, 9999

 

 

 

 

 

system

834

Torque control P gain

Second function of Pr. 824 (valid when RT terminal is on)

9999

 

"

"

"

 

2

0 to 200%, 9999

 

 

 

 

 

 

 

 

 

 

 

 

Control

835

Torque control

Second function of Pr. 825 (valid when RT terminal is on)

9999

 

"

"

"

836

Torque setting filter 2

Second function of Pr. 826 (valid when RT terminal is on)

9999

 

"

"

"

 

 

integral time 2

0 to 500ms, 9999

 

 

 

 

 

 

 

 

0 to 5s, 9999

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

837

Torque detection

Second function of Pr. 827 (valid when RT terminal is on)

9999

 

"

"

"

 

 

filter 2

0 to 5s, 9999

 

 

 

 

 

67

Image 71
Contents 102 Biases and gains of speed setting terminalsThank you for choosing this Mitsubishi Vector Inverter 101Electric Shock Prevention Operation Transportation and installationWiring Trial runGeneral instructions Maintenance, inspection and parts replacementEmergency stop Disposing of the inverterFront view AbbreviationsHarmonic Suppression Guideline Product check and name of partsBasic configuration Basic configuration and connection of peripheral devicesBasic configuration and connection of peripheral devices 400V class Select the NFB type according to the power supply capacitySelection of peripheral devices 200V classStructure Removal and reinstallation of the front coverReinstallation StructureReinstallation Structure Removal and reinstallation of the operation panelReinstallation using the connection cable Install the inverter under the following conditions Installation of the inverterInstallation of the inverter Connection diagram Connection diagram, PLG cable, PU connectorConnection diagram, PLG cable, PU connector Terminal Symbol Terminal Name Description Connection diagram, PLG cable, PU connector Main circuitSpecification of main circuit terminal Screw size M8 Terminal arrangement of the main circuit terminalScrew size M6 400V classCable gause for the control circuit power Cables and wiring length200V class When input power supply is 400V class When input power supply isType Length L m Setting the PLGPLG output circuit jumper connector Pr Setting Relationship between the motor and PLG Parameter Name Factory Setting Setting Range RemarksType Terminal Terminal Name Description Symbol Connection diagram, PLG cable, PU connector Control circuitSpecifications of control circuit terminals Control circuit terminal layout Wiring instructionsNot output during inverter reset Changing the control logic When using an external power supply for transistor output For computer link communication Dedicated motor SF-V5R 1500r/min series Setting the m otorSetting the motor Parameter Name Factory Setting Setting RangeWhen using other manufacturers’ motors At-a-glance guide to motor settingMotor Rated Voltage Precautions for use of the vector inverterPrecautions for use of the vector inverter Checks prior to test run Basic operation Speed setting, run, speed meter adjustmentSetting the speed and running the motor Checks prior to test runOperation status indication FWD or REV flickers Basic operation Speed setting, run, speed meter adjustmentTurn on the start switch STF or STR PU jog operationExternal jog operation To stop the inverter Changing exampleDisplay the present operation speed by pressing SET to It may take some time until the pointer movesUnit indication, operation status indication Names and functions of the operation panelNames and functions of the opera- tion panel Key indicationMonitoring Speed settingUsed to set the running speed in the PU operation mode Alarm *1 absentOnce, press SET , and restart the setting from the beginning Operation modeAlarm history clear Clears all alarm history Names and functions of the opera- tion panel Help modeAlarm history All clear Parameter clearParameter setting mode Names and functions of the opera- tion panel Copy modeSpeed control Setting procedureSpeed control operation Speed control operationTorque restriction Speed control operation Operation command settingForward and reverse rotation commands terminals STF, STR Speed commandSecond torque restriction level Torque restriction levelPr deceleration torque Gain adjustmentPreset speed-speed Torque restrictions during acceleration and decelerationTorque control When 0 is set in Pr or Pr acceleration/deceleration timeTorque control operation Torque control operationOperation example Pr =0 O signalsFollowing table indicates the operations of the signals Signal Terminal Name RemarksPerform secure wiring. Refer to Set the PLG. Refer to Torque control operation Setting procedureTorque command right selection Torque command settingSpeed restriction 10E +10V When Pr =Used to give a speed restriction command Position control operation Position command from parameter settingPosition command from PLC Position control operationAssumes that the Pr value is the factory setting Control mode switchover timingControl mode switchover timing 〈 Example Speed Position, when Pr = 4〉Start signal Easy gain tuningEasy gain tuning Easy gain tuning execution procedureLoad inertia estimation restriction conditions Easy gain tuning Precautions for easy gain tuningAutomatically set parameters by easy gain tuning Checking the Pr control system selection valuePage 3 Pr = 2 normal tuning/adaptive magnetic flux observer Online auto tuningOnline auto tuning 2 Pr =1 start-time tuning10V SettingOutput speed Torque %Read Pr to display the currently set gain speed Setting change 1.5 sValue is 100% Current analog voltage adjustment valueExample When the analog Simple mode parameter list Function list Simple mode parametersFunction list Simple mode parameters Pr maximum speed, Pr minimum speed Setting Carrier FrequencyYou can change the motor sound Refer to page 62 for Pr soft PW M controlRefer to page 46 for details Pr control system selection Setting Drive System Control Method RemarksRefer to page 43 for details Pr extended function display selectionFunction list Extended function parameters Function list Extended function parametersSpeed jump 1B Deceleration patternRegenerative Speed jump 1ADA1 terminal function Remote settingIntelligent mode Alarm occurrencePWM frequency Selection Speed setting signalApplied motor Online auto tuning Selection Auto tuning setting Reset selectionParameter write Disable selection Reverse rotation Operation mode117 Station number 123 Waiting time setting144 Speed setting SwitchoverStall prevention 156 Operation selection 157 OL signal outputTimer Power failureMeter clear DI1 terminal function Maker setting parameters. Do not make setting 169168 171 Actual operation hour236 Multi-speed setting 232 Multi-speed settingMulti-speed setting 233 234 Multi-speed setting286 Droop gain Command selectionSwitchover speed Command 357 In-position zone427 Excessive level error Position commandCommand pulse 420 Scaling factor Numerator Command filterAmount lower 4 digits Digital position464 Control sudden stop 465 First position feedValue RAM Torque command Selection 801 Torque characteristicCharacteristic 805 Torque command832 Speed setting filter 818 Easy gain tuning Response level setting 819822 Speed setting filter 826 Torque setting filter842 Torque bias Adjustment840 Torque bias selection 841 Torque biasSetting time 892 Maintenance output 874 OLT level settingFault definition 890 Maintenance outputMajor faults Errors AlarmsErrors Alarms Inv. Overload OV During AccOV During Dec Motor OverloadUnder Voltage Br. Cct. FaultGround Fault Inst. Pwr. LossStll Prev STP OL shown during stall OH FaultOption Fault Option slot alarm 1 toPU Leave Out Fault 1 to FaultCPU Fault Corrupt MemryOperation Panel P12 FaultIndication Fault Name Operation Panel P24Overspeed occurrence No encoder signalExcessive position error No encoder a signalStall prevention Minor faultFan Failure Operation Panel Err Indication Reset from operation panel Errors Alarms How to recover from PU stop error PSCorrespondences between digital and actual characters Resetting the inverterCorrespondences between digital and actual characters Memo Vector control TroubleshootingTroubleshooting Motor generates abnormal noiseVector control Troubleshooting Motor does not rotateParameter Command beenIs the torque For speed restriction?F control Troubleshooting Motor generates heat abnormally Being made? Troubleshooting Motor huntsSpeed control Troubleshooting Machine operates unstably Does the inverters speed command match the motor speed? Troubleshooting Speed command does not match motor speedHave you set the motor type? Is the PLG setting correct? Troubleshooting Motor rotates but speed does not change Pr , Pr Is an external Troubleshooting Torque control is not exercised normallyIs the wiring length short? Torque controlFilter Pr Is the torque command unvaried?Reduce noise Frequency low?Check items Precautions for maintenance and inspectionPrecautions for maintenance and inspection Insulation resistance test using meggerDo not conduct a pressure test. Deterioration may occur Precautions for maintenance and inspection Pressure testDaily and periodic inspection Area Inspection Description Replacement of partsPart Name Standard Replacement Interval Description IntervalRelays Cooling fanSmoothing capacitors Examples of Measuring Points and Instruments Measurement of main circuit voltages, currents and powersPf2 = Measuring Points and Instruments100% Pf1 = 100%Model specifications Model specifications10.0 14.5 18.5 27.5 35.5 51.8 132 Three-phase, 380 to 480V 50Hz/60HzThree-phase, 380V to 480V 50Hz/60Hz 10.0 12.8 19.0 24.6 30.4 35.8 46.3 59.5 68.5 91.0Common specifications Common specificationsFR-V520-1.5K‚ 2.2K FR-V540-1.5K‚ 2.2K Outline dimension drawingsOutline dimension drawings Inverter outline dimension drawings250 FR-V520-11K‚ 15K FR-V540-7.5K‚ 11K, 15K, 18.5KFR-V520-18.5K Inverter Type FR-V520-22K, 30K‚ 37K !FR-V540-22K, 30K‚ 37KSF-V5RH 2K ‚ 3K SF-V5RH 1KSF-V5RH 5K ‚ 7K 110 SF-V5RH 30K ‚ 37K ‚ 45K ‚ 55KPrint Date Manual Number Revision For Maximum Safety