Online auto tuning

4.6Online auto tuning

!Excellent torque accuracy is provided even if the secondary resistance value of the motor varies with the rise of the motor temperature.

4.6.1Parameters

• For the motor with PLG, set "2" in Pr. 95 "online auto tuning selection".

Parameter

Name

Factory Setting

Setting Range

Remarks

 

 

 

 

 

 

 

 

 

0: No online auto tuning

95

Online auto tuning selection

0

0, 1, 2

1: Start-time tuning (at start-up)

 

 

 

 

2: Adaptive magnetic flux observer (normal)

 

 

 

 

 

4.6.2Pr. 95="1" (start-time tuning)

The current at a start is detected to compensate for the secondary resistance of the motor so that excellent characteristics are provided regardless of the change in value of the secondary resistance of the motor with the rise of the motor temperature.

CAUTION

1.Perform offline auto tuning in the mode with rotation before performing start-time tuning of the online auto tuning.

4.6.3Pr. 95 = "2" (normal tuning)/adaptive magnetic flux observer

This function is effective for torque accuracy improvement when using the motor with PLG.

The current flowing in the motor and the inverter output voltage are used to estimate/observe the magnetic flux in the motor.

The magnetic flux of the motor is always detected with high accuracy so that excellent characteristics are provided regardless of the change in the temperature of the secondary resistance.

Set "2" when exercising PLG vector control.

CAUTION

1.For the SF-V5R, SF-JR (with PLG) or SF-HRCA (with PLG), it is not necessary to perform offline auto tuning to select adaptive magnetic flux observer. (Note that it is necessary to perform offline auto tuning (hon-rotation mode) for the wiring length resistance to be reflected on the control when the wiring length is long (30m or longer as reference).)

2.For using start-time tuning in vertical lift applications, examine the utilization of a brake sequence for the brake opening timing at a start. Though the tuning ends in about a maximum of 500ms after a start, torque is not provided fully during that period. Therefore, note that there may be a possibility of gravity drop.

REMARKS

1.Online auto tuning of the start-time tuning does not operate if the MRS is input, if the preset speed is less than the starting speed (Pr. 13), or if the starting conditions of the inverter are not satisfied, e.g. inverter error.

2.Online auto tuning of the start-time tuning does not operate during deceleration or at a restart during DC brake operation.

3.Invalid for jog operation.

4.The RUN signal is not output during online auto tuning of the start-time tuning. The RUN signal turns on at a start.

5.If the period from an inverter stop to a restart is within 4 seconds, online auto tuning of the start-time tuning is performed but the tuning results are not reflected.

6.Automatic restart after instantaneous power failure overrides when automatic restart after instantaneous power failure is selected.

7.Zero current detection and output current detection are valid during online auto tuning.

46

4

CONTROL

Image 50
Contents 101 Biases and gains of speed setting terminalsThank you for choosing this Mitsubishi Vector Inverter 102Electric Shock Prevention Trial run Transportation and installationWiring OperationDisposing of the inverter Maintenance, inspection and parts replacementEmergency stop General instructionsProduct check and name of parts AbbreviationsHarmonic Suppression Guideline Front viewBasic configuration Basic configuration and connection of peripheral devicesBasic configuration and connection of peripheral devices 200V class Select the NFB type according to the power supply capacitySelection of peripheral devices 400V classStructure Removal and reinstallation of the front coverReinstallation StructureReinstallation Structure Removal and reinstallation of the operation panelReinstallation using the connection cable Install the inverter under the following conditions Installation of the inverterInstallation of the inverter Connection diagram Connection diagram, PLG cable, PU connectorConnection diagram, PLG cable, PU connector Terminal Symbol Terminal Name Description Connection diagram, PLG cable, PU connector Main circuitSpecification of main circuit terminal Terminal arrangement of the main circuit terminal Screw size M8400V class Screw size M6400V class When input power supply is Cables and wiring length200V class When input power supply is Cable gause for the control circuit powerType Length L m Setting the PLGPLG output circuit jumper connector Parameter Name Factory Setting Setting Range Remarks Pr Setting Relationship between the motor and PLGType Terminal Terminal Name Description Symbol Connection diagram, PLG cable, PU connector Control circuitSpecifications of control circuit terminals Control circuit terminal layout Wiring instructionsNot output during inverter reset Changing the control logic When using an external power supply for transistor output For computer link communication Parameter Name Factory Setting Setting Range Setting the m otorSetting the motor Dedicated motor SF-V5R 1500r/min seriesAt-a-glance guide to motor setting When using other manufacturers’ motorsMotor Rated Voltage Precautions for use of the vector inverterPrecautions for use of the vector inverter Checks prior to test run Basic operation Speed setting, run, speed meter adjustmentSetting the speed and running the motor Checks prior to test runPU jog operation Basic operation Speed setting, run, speed meter adjustmentTurn on the start switch STF or STR Operation status indication FWD or REV flickersExternal jog operation It may take some time until the pointer moves Changing exampleDisplay the present operation speed by pressing SET to To stop the inverterKey indication Names and functions of the operation panelNames and functions of the opera- tion panel Unit indication, operation status indicationAlarm *1 absent Speed settingUsed to set the running speed in the PU operation mode MonitoringOperation mode Once, press SET , and restart the setting from the beginningAlarm history clear Clears all alarm history Names and functions of the opera- tion panel Help modeAlarm history Parameter clear All clearNames and functions of the opera- tion panel Copy mode Parameter setting modeSpeed control operation Setting procedureSpeed control operation Speed controlSpeed command Speed control operation Operation command settingForward and reverse rotation commands terminals STF, STR Torque restrictionTorque restriction level Second torque restriction levelTorque restrictions during acceleration and deceleration Gain adjustmentPreset speed-speed Pr deceleration torqueTorque control operation When 0 is set in Pr or Pr acceleration/deceleration timeTorque control operation Torque controlSignal Terminal Name Remarks O signalsFollowing table indicates the operations of the signals Operation example Pr =0Torque command setting Torque control operation Setting procedureTorque command right selection Perform secure wiring. Refer to Set the PLG. Refer toSpeed restriction 10E +10V When Pr =Used to give a speed restriction command Position control operation Position command from parameter settingPosition command from PLC Position control operation〈 Example Speed Position, when Pr = 4〉 Control mode switchover timingControl mode switchover timing Assumes that the Pr value is the factory setting Easy gain tuning execution procedure Easy gain tuning Easy gain tuning Start signalChecking the Pr control system selection value Easy gain tuning Precautions for easy gain tuningAutomatically set parameters by easy gain tuning Load inertia estimation restriction conditionsPage 2 Pr =1 start-time tuning Online auto tuningOnline auto tuning 3 Pr = 2 normal tuning/adaptive magnetic flux observerTorque % SettingOutput speed 10VSetting change 1.5 s Read Pr to display the currently set gain speedValue is 100% Current analog voltage adjustment valueExample When the analog Simple mode parameter list Function list Simple mode parametersFunction list Simple mode parameters Refer to page 62 for Pr soft PW M control Setting Carrier FrequencyYou can change the motor sound Pr maximum speed, Pr minimum speedRefer to page 46 for details Pr extended function display selection Setting Drive System Control Method RemarksRefer to page 43 for details Pr control system selectionFunction list Extended function parameters Function list Extended function parametersSpeed jump 1A Deceleration patternRegenerative Speed jump 1BAlarm occurrence Remote settingIntelligent mode DA1 terminal functionPWM frequency Selection Speed setting signalApplied motor Operation mode Reset selectionParameter write Disable selection Reverse rotation Online auto tuning Selection Auto tuning settingSwitchover 123 Waiting time setting144 Speed setting 117 Station numberPower failure 157 OL signal outputTimer Stall prevention 156 Operation selection171 Actual operation hour Maker setting parameters. Do not make setting 169168 Meter clear DI1 terminal function234 Multi-speed setting 232 Multi-speed settingMulti-speed setting 233 236 Multi-speed settingCommand 357 In-position zone Command selectionSwitchover speed 286 Droop gainCommand filter Position commandCommand pulse 420 Scaling factor Numerator 427 Excessive level error465 First position feed Digital position464 Control sudden stop Amount lower 4 digits805 Torque command Selection 801 Torque characteristicCharacteristic Value RAM Torque command826 Torque setting filter 818 Easy gain tuning Response level setting 819822 Speed setting filter 832 Speed setting filter841 Torque bias Adjustment840 Torque bias selection 842 Torque bias890 Maintenance output 874 OLT level settingFault definition Setting time 892 Maintenance outputMajor faults Errors AlarmsErrors Alarms Motor Overload OV During AccOV During Dec Inv. OverloadInst. Pwr. Loss Br. Cct. FaultGround Fault Under VoltageOption slot alarm 1 to OH FaultOption Fault Stll Prev STP OL shown during stallCorrupt Memry Fault 1 to FaultCPU Fault PU Leave OutOperation Panel P24 FaultIndication Fault Name Operation Panel P12No encoder a signal No encoder signalExcessive position error Overspeed occurrenceStall prevention Minor faultFan Failure Operation Panel Err Indication Errors Alarms How to recover from PU stop error PS Reset from operation panelCorrespondences between digital and actual characters Resetting the inverterCorrespondences between digital and actual characters Memo Motor generates abnormal noise TroubleshootingTroubleshooting Vector controlTroubleshooting Motor does not rotate Vector controlFor speed restriction? Command beenIs the torque ParameterF control Troubleshooting Motor generates heat abnormally Being made? Troubleshooting Motor huntsSpeed control Troubleshooting Machine operates unstably Does the inverters speed command match the motor speed? Troubleshooting Speed command does not match motor speedHave you set the motor type? Is the PLG setting correct? Troubleshooting Motor rotates but speed does not change Torque control Troubleshooting Torque control is not exercised normallyIs the wiring length short? Pr , Pr Is an externalFrequency low? Is the torque command unvaried?Reduce noise Filter PrInsulation resistance test using megger Precautions for maintenance and inspectionPrecautions for maintenance and inspection Check itemsDo not conduct a pressure test. Deterioration may occur Precautions for maintenance and inspection Pressure testDaily and periodic inspection Interval Replacement of partsPart Name Standard Replacement Interval Description Area Inspection DescriptionRelays Cooling fanSmoothing capacitors Measurement of main circuit voltages, currents and powers Examples of Measuring Points and Instruments100% Measuring Points and Instruments100% Pf1 = Pf2 =Model specifications Model specifications10.0 12.8 19.0 24.6 30.4 35.8 46.3 59.5 68.5 91.0 Three-phase, 380 to 480V 50Hz/60HzThree-phase, 380V to 480V 50Hz/60Hz 10.0 14.5 18.5 27.5 35.5 51.8 132Common specifications Common specificationsInverter outline dimension drawings Outline dimension drawingsOutline dimension drawings FR-V520-1.5K‚ 2.2K FR-V540-1.5K‚ 2.2K250 FR-V520-11K‚ 15K FR-V540-7.5K‚ 11K, 15K, 18.5KFR-V520-18.5K FR-V520-22K, 30K‚ 37K !FR-V540-22K, 30K‚ 37K Inverter TypeSF-V5RH 1K SF-V5RH 2K ‚ 3KSF-V5RH 5K ‚ 7K SF-V5RH 30K ‚ 37K ‚ 45K ‚ 55K 110For Maximum Safety Print Date Manual Number Revision