Mitsubishi Electronics FR-V500 Multi-speed setting 233, Speed 239 Multi-speed setting

Page 66

Function list (Extended function parameters)

 

 

 

 

 

 

At-a-glance Guide to Func-

 

 

 

 

 

 

 

tions

 

 

 

 

 

 

 

": Usable function

Function

Parameter

 

 

 

Cus-

×: Unusable function

 

 

 

 

 

* : Functions that can be used

 

 

Name

Outline

Factory

tomer

 

 

for param eter-set position con-

 

 

Setting

Set-

 

 

 

 

 

trol

 

 

 

 

 

 

ting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vector Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed

Torque

Position

 

 

 

 

 

 

control

control

control

 

 

232

Multi-speed setting

By setting any value other than "9999", set speeds 8 to 15.

 

 

9999

"

"

× *

 

 

 

(speed 8)

 

 

 

 

 

 

 

 

 

 

This function is designed to change the running speed in stages by changing the ON/

 

 

 

 

 

 

 

Multi-speed setting

 

 

 

× *

 

 

233

OFF combination of the contact signals (RH, RM, RL, REX signals).

9999

"

"

 

 

(speed 9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

234

Multi-speed setting

 

 

 

 

 

 

 

 

 

9999

"

"

× *

operation

 

Speed 9

 

RH

 

RM

RL

REX

 

235

(speed 11)

 

 

OFF

 

OFF

ON

ON

 

9999

"

"

× *

 

 

 

(speed 10)

 

 

 

 

 

 

 

 

 

 

 

 

 

speed-Multi

 

Multi-speed setting

 

Speed 8

 

OFF

 

OFF

OFF

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed 10

 

OFF

 

ON

OFF

ON

 

 

 

 

 

 

 

236

Multi-speed setting

 

 

 

 

9999

"

"

× *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed 11

 

OFF

 

ON

ON

ON

 

 

 

(speed 12)

 

 

 

 

 

 

 

 

 

Speed 12

 

ON

 

OFF

OFF

ON

 

 

 

 

 

 

 

237

Multi-speed setting

9999

"

"

× *

 

 

 

 

 

 

 

 

 

 

 

 

 

(speed 13)

 

Speed 13

 

ON

 

OFF

ON

ON

 

 

 

 

 

 

Speed 14

 

ON

 

ON

OFF

ON

 

 

 

 

 

 

 

238

Multi-speed setting

 

 

9999

"

"

× *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed 15

 

ON

 

ON

ON

ON

 

 

 

 

(speed 14)

 

 

 

 

 

 

 

 

 

 

239

Multi-speed setting

0 to 3600r/min, 9999

 

 

 

 

 

 

9999

"

"

× *

 

 

 

(speed 15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can select to exercise Soft-PWM control and

long wiring mode. When Soft-PWM

 

 

 

 

 

 

 

 

control is made valid, you can change the metallic tone of motor sound into an

 

 

 

 

 

 

 

 

unoffending complex tone. Surge voltage is surpressed in the long wiring mode

 

 

 

 

 

 

 

 

regardless of the wiring length between the inverter and motor. (When operating a

 

 

 

 

functions

240

Soft-PWM setting

400V motor with wiring length of 40m or more, select long wiring mode.)

10

"

"

"

10: Soft-PWM control invalid, long wiring mode valid (carrier frequency is 2.25Hz *)

 

 

 

 

0: Soft-PWM control invalid, long wiring mode invalid

 

 

 

 

 

 

 

 

 

 

1: Soft-PWM control valid (when Pr. 72 = "1 or 2"), long wiring mode invalid

 

 

 

 

Sub

 

 

11: Soft-PWM control valid, long wiring mode valid (carrier frequency is 2.25Hz *)

 

 

 

 

 

 

 

*The Pr.72 "PWM frequency selection" setting is made invalid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling fan operation

You can control the operation of the cooling fan built in the inverter.

 

 

 

 

 

 

244

0: The fan is always operated at power-on of the inverter.

 

 

0

"

"

"

 

 

 

selection

1: The fan is always on while the inverter is running. During a stop, the inverter status is

 

 

 

 

 

 

 

 

monitored and the fan switches on-off according to the temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selectionStop

function

 

 

Set to allow the motor to be coasted to a stop by turning off the start command during

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

Stop selection

V/F or speed control.

 

 

 

 

 

 

9999

"

"

×

 

 

0 to 100s: Coasting to stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9999: Deceleration to stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selectionOperation

function

 

Output phase failure

You can disable the output phase failure function that stops the inverter output if one of

 

 

 

 

 

 

 

 

 

 

 

 

 

251

the inverter output side (load side) three phases (U, V, W) opens.

1

"

"

"

 

 

 

protection selection

0: Without output phase failure protection

 

 

 

 

 

 

 

 

 

 

 

 

1: With output phase failure protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional

functions

253

Override gain

 

 

 

 

 

 

 

 

 

150%

"

"

×

 

 

252

Override bias

When you selected the override in Pr. 73, you can adjust the override bias (0 to 200%)

50%

"

"

×

 

 

 

 

and override gain (0 to 200%).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

261

Power failure stop

You can select the stopping method at a power failure.

 

 

 

"

"

×

 

 

0: Coasting to stop, inverter output shutoff

 

 

 

0

 

 

 

selection

1: Inverter is decelerated to a stop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

263

Subtraction starting

0 to 3600r/min, 9999

 

 

 

 

 

 

1500r/m in

"

"

×

 

 

262

Subtracted speed at

0 to 600r/min

 

 

 

 

 

 

90r/min

"

"

×

 

 

 

deceleration start

 

 

 

 

 

 

 

 

 

 

 

 

 

stop

 

speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

failure

264

Power-failure

0 to 3600/0 to 360s

 

 

 

 

 

 

5s

"

"

×

 

deceleration time 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

265

Power-failure

0 to 3600/0 to 360s, 9999

 

 

 

 

 

 

9999

"

"

×

 

deceleration time 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power-failure

 

 

 

 

 

 

 

 

 

 

 

 

×

 

 

266

deceleration time

0 to 3600r/min

 

 

 

 

 

 

1500r/m in

"

"

 

 

 

switchover speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

278

Brake opening speed

 

 

 

 

 

 

 

 

 

20r/min

"

×

×

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

279

Brake opening

 

 

 

 

 

 

 

 

 

130%

"

×

×

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

280

Brake opening

Set when outputting the operation timing signal of the mechanical brake in vertical lift

0.3s

"

×

×

 

 

current detection time

sequence

applications. (When speed control (invalid for V/F control) is selected)

282

Brake operation speed

0 to 5s (Pr. 281)

 

 

 

 

 

 

25r/min

"

×

×

 

 

281

Brake operation time

0 to 900r/min (Pr. 278)

 

 

 

 

 

 

0.3s

"

×

×

 

 

at start

0 to 200% (Pr. 279)

 

 

 

 

 

 

Brake

 

 

0 to 2s (Pr. 280)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 to 900r/min (Pr. 282)

 

 

 

 

 

 

 

 

 

 

 

 

283

Brake operation time

 

 

 

 

 

 

0.3s

"

×

×

 

 

0 to 5s (Pr. 283)

 

 

 

 

 

 

 

 

 

at stop

0, 1 (Pr. 284)

 

 

 

 

 

 

 

 

 

 

 

 

 

Deceleration

0 to 900r/min, 9999 (Pr. 285)

 

 

 

 

 

 

 

 

×

×

 

 

284

detection function

 

 

 

 

 

 

 

 

 

0

"

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

285

Overspeed detection

 

 

 

 

 

 

 

 

 

9999

"

×

×

 

 

 

speed

 

 

 

 

 

 

 

 

 

 

 

 

 

PARAMETERS

Parameter

5

62

Image 66
Contents 101 Biases and gains of speed setting terminalsThank you for choosing this Mitsubishi Vector Inverter 102Electric Shock Prevention Trial run Transportation and installationWiring OperationDisposing of the inverter Maintenance, inspection and parts replacementEmergency stop General instructionsProduct check and name of parts AbbreviationsHarmonic Suppression Guideline Front viewBasic configuration and connection of peripheral devices Basic configuration and connection of peripheral devicesBasic configuration 200V class Select the NFB type according to the power supply capacitySelection of peripheral devices 400V classStructure Removal and reinstallation of the front coverReinstallation StructureStructure Removal and reinstallation of the operation panel Reinstallation using the connection cableReinstallation Installation of the inverter Installation of the inverterInstall the inverter under the following conditions Connection diagram, PLG cable, PU connector Connection diagram, PLG cable, PU connectorConnection diagram Connection diagram, PLG cable, PU connector Main circuit Specification of main circuit terminalTerminal Symbol Terminal Name Description Terminal arrangement of the main circuit terminal Screw size M8400V class Screw size M6400V class When input power supply is Cables and wiring length200V class When input power supply is Cable gause for the control circuit powerSetting the PLG PLG output circuit jumper connectorType Length L m Parameter Name Factory Setting Setting Range Remarks Pr Setting Relationship between the motor and PLGConnection diagram, PLG cable, PU connector Control circuit Specifications of control circuit terminalsType Terminal Terminal Name Description Symbol Wiring instructions Not output during inverter resetControl circuit terminal layout Changing the control logic When using an external power supply for transistor output For computer link communication Parameter Name Factory Setting Setting Range Setting the m otorSetting the motor Dedicated motor SF-V5R 1500r/min seriesAt-a-glance guide to motor setting When using other manufacturers’ motorsPrecautions for use of the vector inverter Precautions for use of the vector inverterMotor Rated Voltage Checks prior to test run Basic operation Speed setting, run, speed meter adjustmentSetting the speed and running the motor Checks prior to test runPU jog operation Basic operation Speed setting, run, speed meter adjustmentTurn on the start switch STF or STR Operation status indication FWD or REV flickersExternal jog operation It may take some time until the pointer moves Changing exampleDisplay the present operation speed by pressing SET to To stop the inverterKey indication Names and functions of the operation panelNames and functions of the opera- tion panel Unit indication, operation status indicationAlarm *1 absent Speed settingUsed to set the running speed in the PU operation mode MonitoringOperation mode Once, press SET , and restart the setting from the beginningNames and functions of the opera- tion panel Help mode Alarm historyAlarm history clear Clears all alarm history Parameter clear All clearNames and functions of the opera- tion panel Copy mode Parameter setting modeSpeed control operation Setting procedureSpeed control operation Speed controlSpeed command Speed control operation Operation command settingForward and reverse rotation commands terminals STF, STR Torque restrictionTorque restriction level Second torque restriction levelTorque restrictions during acceleration and deceleration Gain adjustmentPreset speed-speed Pr deceleration torqueTorque control operation When 0 is set in Pr or Pr acceleration/deceleration timeTorque control operation Torque controlSignal Terminal Name Remarks O signalsFollowing table indicates the operations of the signals Operation example Pr =0Torque command setting Torque control operation Setting procedureTorque command right selection Perform secure wiring. Refer to Set the PLG. Refer toSpeed restriction When Pr = Used to give a speed restriction command10E +10V Position control operation Position command from parameter settingPosition command from PLC Position control operation〈 Example Speed Position, when Pr = 4〉 Control mode switchover timingControl mode switchover timing Assumes that the Pr value is the factory settingEasy gain tuning execution procedure Easy gain tuningEasy gain tuning Start signalChecking the Pr control system selection value Easy gain tuning Precautions for easy gain tuningAutomatically set parameters by easy gain tuning Load inertia estimation restriction conditionsPage 2 Pr =1 start-time tuning Online auto tuningOnline auto tuning 3 Pr = 2 normal tuning/adaptive magnetic flux observerTorque % SettingOutput speed 10VSetting change 1.5 s Read Pr to display the currently set gain speedCurrent analog voltage adjustment value Example When the analogValue is 100% Function list Simple mode parameters Function list Simple mode parametersSimple mode parameter list Refer to page 62 for Pr soft PW M control Setting Carrier FrequencyYou can change the motor sound Pr maximum speed, Pr minimum speedRefer to page 46 for details Pr extended function display selection Setting Drive System Control Method RemarksRefer to page 43 for details Pr control system selectionFunction list Extended function parameters Function list Extended function parametersSpeed jump 1A Deceleration patternRegenerative Speed jump 1BAlarm occurrence Remote settingIntelligent mode DA1 terminal functionSpeed setting signal Applied motorPWM frequency Selection Operation mode Reset selectionParameter write Disable selection Reverse rotation Online auto tuning Selection Auto tuning setting Switchover 123 Waiting time setting 144 Speed setting 117 Station numberPower failure 157 OL signal outputTimer Stall prevention 156 Operation selection171 Actual operation hour Maker setting parameters. Do not make setting 169168 Meter clear DI1 terminal function234 Multi-speed setting 232 Multi-speed settingMulti-speed setting 233 236 Multi-speed settingCommand 357 In-position zone Command selectionSwitchover speed 286 Droop gainCommand filter Position commandCommand pulse 420 Scaling factor Numerator 427 Excessive level error465 First position feed Digital position464 Control sudden stop Amount lower 4 digits805 Torque command Selection 801 Torque characteristicCharacteristic Value RAM Torque command826 Torque setting filter 818 Easy gain tuning Response level setting 819822 Speed setting filter 832 Speed setting filter841 Torque bias Adjustment840 Torque bias selection 842 Torque bias890 Maintenance output 874 OLT level settingFault definition Setting time 892 Maintenance outputErrors Alarms Errors AlarmsMajor faults Motor Overload OV During AccOV During Dec Inv. OverloadInst. Pwr. Loss Br. Cct. FaultGround Fault Under VoltageOption slot alarm 1 to OH FaultOption Fault Stll Prev STP OL shown during stallCorrupt Memry Fault 1 to FaultCPU Fault PU Leave OutOperation Panel P24 FaultIndication Fault Name Operation Panel P12No encoder a signal No encoder signalExcessive position error Overspeed occurrenceMinor fault Fan FailureStall prevention Operation Panel Err Indication Errors Alarms How to recover from PU stop error PS Reset from operation panelResetting the inverter Correspondences between digital and actual charactersCorrespondences between digital and actual characters Memo Motor generates abnormal noise TroubleshootingTroubleshooting Vector controlTroubleshooting Motor does not rotate Vector controlFor speed restriction? Command beenIs the torque ParameterF control Troubleshooting Motor generates heat abnormally Troubleshooting Motor hunts Speed controlBeing made? Troubleshooting Machine operates unstably Troubleshooting Speed command does not match motor speed Have you set the motor type? Is the PLG setting correct?Does the inverters speed command match the motor speed? Troubleshooting Motor rotates but speed does not change Torque control Troubleshooting Torque control is not exercised normallyIs the wiring length short? Pr , Pr Is an externalFrequency low? Is the torque command unvaried?Reduce noise Filter PrInsulation resistance test using megger Precautions for maintenance and inspectionPrecautions for maintenance and inspection Check itemsPrecautions for maintenance and inspection Pressure test Daily and periodic inspectionDo not conduct a pressure test. Deterioration may occur Interval Replacement of partsPart Name Standard Replacement Interval Description Area Inspection DescriptionCooling fan Smoothing capacitorsRelays Measurement of main circuit voltages, currents and powers Examples of Measuring Points and Instruments100% Measuring Points and Instruments100% Pf1 = Pf2 =Model specifications Model specifications10.0 12.8 19.0 24.6 30.4 35.8 46.3 59.5 68.5 91.0 Three-phase, 380 to 480V 50Hz/60HzThree-phase, 380V to 480V 50Hz/60Hz 10.0 14.5 18.5 27.5 35.5 51.8 132Common specifications Common specificationsInverter outline dimension drawings Outline dimension drawingsOutline dimension drawings FR-V520-1.5K‚ 2.2K FR-V540-1.5K‚ 2.2KFR-V520-11K‚ 15K FR-V540-7.5K‚ 11K, 15K, 18.5K FR-V520-18.5K250 FR-V520-22K, 30K‚ 37K !FR-V540-22K, 30K‚ 37K Inverter TypeSF-V5RH 1K SF-V5RH 2K ‚ 3KSF-V5RH 5K ‚ 7K SF-V5RH 30K ‚ 37K ‚ 45K ‚ 55K 110For Maximum Safety Print Date Manual Number Revision