INSTALLATION
MINIMUM FIREPLACE
DIMENSIONS
The minimum fireplace dimensions for the Regency gas space heater are shown in the following diagrams:
MINIMUM
CLEARANCES TO
COMBUSTIBLES
The minimum fireplace clearances for the Regency gas space heater are shown in the following diagrams:
Mantel Clearances
Premium Flush Front Framing
When installing the Premium Flush Front, the walls surrounding the zero clearance kit must be made of
From Unit: |
|
|
Sides | A | 250 mm |
Ceiling | B | 1220 mm |
Mantel | C | see Mantel |
|
| Clearances |
From Surround (660 mm x 1016 mm):
Sides | D | 96 mm |
Ceiling | E | 1066 mm |
Max. Mantle Depth | G | 305 mm |
Hearth Height | H | 0 mm |
Hearth Depth | I | 300 mm* |
Hearth Width | J | 1100 mm |
Min. Alcove Width | K | 1262 mm |
Max. Alcove Depth | L | 915 mm |
*NOTE: No hearth required with screen. Floor finishing material must not be any higher then the base of the fireplace.
Note: A
GAS CONNECTION
GAS CONNECTION WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.
1)If the appliance is to be installed into an existing chimney system or Zero Clearance Box, thoroughly clean the masonry or factory built fireplace.
2)The gas connection is 1/2" BSP.
3)Locate the center point where the flue will pass through the chimney above the appli- ance. Move the appliance into the exact location where it is to be installed. Ensure that the Insert is level.
CAUTION: If the glass is removed for servic- ing, it must be replaced and closed prior to operating the appliance.
6 | Regency IG35 Gas Inbuilt Fireplace |