INSTALLATION
FLUEING
THEAPPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE.
This appliance is designed to attach to a 100
mmdiameter twin skin or listed gas fuel type flue liner running the full length of the chimney. A minimum flue height of 1.5 m. is recommended. The Regency Inbuilt Fireplace incorporates its own internal draft diverter, so no additional external draft diverter is required.
Periodically check that the flue is unrestricted
and an adequate draft is present when the unit is in operation.
Before installing flue system ensure that the
damper plate is open and secure to prevent the
damper plate from falling down and crushing the liner.
Install to
(New Zealand).
Combustion and Ventilation Air
WARNING: This appliance needs fresh air for safe operation and must be installed with provisions for ad- equate combustion and ventilation air available to the room in which it is to be operating.
Air for combustion is drawn in through the front of the unit, therefore, the front of the unit must be kept clear of any obstructions.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual
The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1)Make sure the valve is in the "OFF" position.
2)Loosen the "IN" (# 3) and/or "OUT" (# 4) pressure tap(s), turning counterclockwise with a 1/8" wide flat screwdriver.
3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" (8mm) ID hose.
4)Seal and or check the pilot outlet (# 8)
5)The pressure check should be carried out with the unit burning and the setting should be within the limits specified on the safety label.
6)When finished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" flat screwdriver. Screw should be snug, but do not over tighten.
S.I.T. Valve Description
1)
2)
3)Inlet Pressure Test Point
4)Outlet Pressure Test Point
5)Connection for Pressure Regulator/ Combustion Chamber Compensation
6)Pressure Regulator for Minimum and Maximum Outlet Pressure
7)Gas Outlet Pressure Electric Modulator
8)Pilot Outlet
9)Main Gas Outlet
10)Side Outlet