3. Outing Function
Outing function is a function that prevents the room temperature from increasing too much (or decreasing too much) when no one is in the room.
An air conditioner works automatically if this function is set effective.
General Performance of the Outing Function
COOL / DRY | Outing function upper limit |
|
① The air conditioner starts operation when the room
temperature increases up to
② The air conditioner stops operation when the room temperature decreases up to
Room temperature
EN
HEAT
①The air conditioner starts operation when the room temperature decreases up to +1°C of the lower limit.
②The air conditioner stops operation when the room temperature increases up to +2°C of the lower limit.
Room temperature
Outing function Lower limit
[Precautions]
・The outing control only starts/stops the air conditioner. It does not change the operation mode/ temperature setting.
Therefore, the operation mode/temperature needs to be set beforehand so that the outing function turns on the air conditioner with your desired operation mode/ temperature setting.
・If the room temperature rapidly changes, the room temperature may get over the upper or lower limit when the outing function is activated.
・The outing function is invalid during FAN/AUTO operation mode.
・The air conditioner’s stop order (stated in ② ⁄ above) is valid only when the outing function is operated.
If operated using other remote control units (or a centralized control device such as a system control), the outing function will not stop air conditioner operation.