Reference Manual

00809-0100-4027, Rev AA December 2005

Rosemount 4500

 

NOTE

 

Sensor burst pressure limits may be less than clamp pressure limits.

 

 

 

 

 

NOTE

 

Most transmitters are calibrated in the vertical position. Mounting the

 

transmitter in any other position will shift the zero point to the equivalent

 

amount of liquid head caused by the varied mounting position. To reset zero

 

point, refer to “Sensor Trim” on page 4-5.

Set Switches

 

Security (Write Protect)

 

Changes can be prevented to the transmitter configuration data with the write

 

protection switches on the optional LCD or the switches on the optional LOI

 

board. Position the switch in the “ON” position to prevent change of

 

configuration data.

 

If the transmitter write protection switch is in the “ON” position, the transmitter

 

will not accept any “writes” to its memory. Configuration changes, such as

 

digital trim and reranging, cannot take place when the transmitter security is

 

on.

 

To reposition the switches, follow the procedure described below.

 

1. If the transmitter is installed, set the loop to manual and remove power.

 

2. Remove the electronics compartment cover.

 

3. Follow the procedure in Figure 2-4to reposition the switches as desired

 

for the specific housing compartment.

 

4. Re-install the transmitter cover.

Figure 2-4. Switch configuration

LCD Switches

LOI Switches

 

 

Security

Alarm

4500_26_AA

Slide the security and alarm switches into the preferred position by using a small screwdriver.

ALARM

SECURITY

SPAN

ZERO

AlarmSecurity

-LOOP

+LOOP

Slide the security and alarm switches into the preferred position by using a small screwdriver.

NOTE

If alarm and security adjustments are not installed, the transmitter will operate normally with the default condition alarm high and the security off.

2-5

Image 13
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Section Operation MaintenanceSection Introduction Using this ManualService Support Overview Safety Messages Section Installation General Considerations Environmental Hart Installation Flowchart Mount the Transmitter Installation ProceduresLCD Switches LOI Switches Set SwitchesAMS Configure Alarm DirectionHart Terminal Blocks Connect Wiring and Power UpGrounding Installing the LCD MeterSection Configuration Commissioning on the Bench with Hart Setting the Loop to ManualWiring Diagrams Menu Tree Hart CommunicatorFunction Hart Fast Key Sequence Fast Key SequenceReview Configuration Data Check Output Sensor TemperatureProcess Variables Set Process Variable Units Basic SetupRerange Fast Keys 3, 1 LCD Display DampingFailure Mode Alarm and Saturation Detailed SetupAlarm and Saturation Level Configuration Alarm and Saturation Values for Multidrop Mode Alarm and Saturation Levels for Burst ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Diagnostics Service Sensor Temperature UnitTransmitter Test Loop Test Advanced Functions for Hart Protocol Saving, Recalling, Cloning Configuration DataRosemount Burst Mode Multidrop Communication Communicating with a Multidropped Transmitter Changing a Transmitter AddressPolling a Multidropped Transmitter Overview Calibration for Hart Protocol Operation and MaintenanceCalibration Overview Transmitter Data Flow with Calibration Options Determining Calibration Frequency Calculate total probable error TPEChoosing a Trim Procedure Sensor Trim Full Trim Zero TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Analog Output Trim Digital-to-Analog Trim Recall Factory Trim- Analog OutputDigital-to-Analog Trim Using Other Scale Fail Module Diagnostic MessagesNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Performance Specifications SpecificationsAppendix a Reference Data 00809-0100-4027, Rev AA December Range and Sensor Limits Functional SpecificationsRosemount Physical Specifications 11/2 inch Tri-Clamp Module Dimensional DrawingsInch Tri-Clamp Module Fractional Line Fitting Module Code Process Connection Style Ordering InformationAppendix B Product Certificates North American Certifications Hazardous Locations CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤