Emerson 4500 manual Transmitter Data Flow with Calibration Options

Page 43

Reference Manual

00809-0100-4027, Rev AA December 2005

Rosemount 4500

Figure 4-1also identifies the approximate transmitter location for each calibration task. Data flows from left to right, and a parameter change affects all values to the right of the changed parameter.

Not all calibration procedures should be performed for each 4500 transmitter. Some procedures are appropriate for bench calibration, but should not be performed during field calibration. Table 4-1identifies the recommended calibration procedures for bench or field calibration.

Figure 4-1. Transmitter Data

Flow with Calibration Options

Transmitter Ranged 0 to 100 inH2O (0 to 0,25 bar)

A/D MICRO D/A

100 in. H20

20.00 mA

4500:LT-8793

 

Online

 

1

Device setup

2

PV

100.00 in.H20

3

AO

20.00 mA

4

LRV

0.00 in.H20

5

URV

100.00 in.H20

 

SAVE

 

NOTE

Value on PV line should equal the input pressure.

Value on AO line should equal the output device reading.

CALIBRATION

4-3

Image 43
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Section Operation MaintenanceSection Introduction Using this ManualService Support Overview Safety Messages Section InstallationGeneral ConsiderationsEnvironmental Hart Installation Flowchart Mount the Transmitter Installation ProceduresLCD Switches LOI Switches Set SwitchesAMS Configure Alarm DirectionHart Terminal Blocks Connect Wiring and Power UpGrounding Installing the LCD MeterSection Configuration Commissioning on the Bench with Hart Setting the Loop to ManualWiring Diagrams Menu Tree Hart CommunicatorFunction Hart Fast Key Sequence Fast Key SequenceReview Configuration Data Check Output Sensor TemperatureProcess Variables Set Process Variable Units Basic SetupRerange Fast Keys 3, 1 LCD Display DampingFailure Mode Alarm and Saturation Detailed SetupAlarm and Saturation Level Configuration Alarm and Saturation Values for Multidrop Mode Alarm and Saturation Levels for Burst ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Diagnostics Service Sensor Temperature UnitTransmitter Test Loop Test Advanced Functions for Hart Protocol Saving, Recalling, Cloning Configuration DataRosemount Burst Mode Multidrop Communication Communicating with a Multidropped Transmitter Changing a Transmitter AddressPolling a Multidropped Transmitter Overview Calibration for Hart Protocol Operation and MaintenanceCalibration Overview Transmitter Data Flow with Calibration Options Determining Calibration Frequency Calculate total probable error TPEChoosing a Trim Procedure Sensor Trim Full Trim Zero TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Analog Output Trim Digital-to-Analog Trim Recall Factory Trim- Analog OutputDigital-to-Analog Trim Using Other Scale Fail Module Diagnostic MessagesNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Performance Specifications SpecificationsAppendix a Reference Data 00809-0100-4027, Rev AA December Range and Sensor Limits Functional SpecificationsRosemount Physical Specifications 11/2 inch Tri-Clamp Module Dimensional DrawingsInch Tri-Clamp Module Fractional Line Fitting Module Code Process Connection Style Ordering InformationAppendix B Product Certificates North American Certifications Hazardous Locations CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤