Rosemount 4500

NOTE

Select pressure input values so that low and high values are equal to or outside the 4 and 20 mA points. Do not attempt to obtain reverse output by reversing the high and low points. The transmitter allows approximately five percent URL deviation from the characterized curve established at the factory.

4.Follow the commands provided by the HART Communicator to complete the adjustment of the lower value.

5.Repeat the procedure for the upper value, replacing 2: Lower sensor trim

with 3: Upper sensor trim in Step 3.

Recall Factory Trim

Recall Factory Trim— Sensor Trim

Fast Keys

1, 2, 3, 4, 1

 

 

AMS

Right click on the device and select “Calibrate,” then “Sensor trim” from the menu.

1.Select “Lower sensor trim.”

2.Click Next after setting the control loop to manual.

3.Click Next after applying appropriate pressure to sensor.

4.Select Next to acknowledge the loop can be returned to automatic control.

5.Select Finish to acknowledge the method is complete.

6.Right click on the device and select “Calibrate,” select “Sensor trim” from the menu.

7.Select “Upper sensor trim” and repeat steps 2-5.

The Recall Factory Trim commands allow the restoration of the as-shipped factory settings of the sensor trim and analog output trim.

This command resets the transmitter sensor trim to the “as shipped” factory settings. The Recall Factory Trim—Sensor Trim command can be useful for recovering from an inadvertent zero trim of an absolute pressure unit or inaccurate pressure source.

AMS

Right click on the device and select “Calibrate,” then “Recall Factory Trim” from the menu.

1.Click Next after setting the control loop to manual.

2.Select “Sensor trim” under “Trim to recall” and click Next.

3.Click Next to acknowledge restoration of trim values is complete.

4.Select Next to acknowledge the loop can be returned to automatic control.

5.Select Finish to acknowledge the method is complete.

4-7

Image 47
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Section Operation MaintenanceSection Introduction Using this ManualService Support Overview Safety Messages Section InstallationEnvironmental ConsiderationsGeneral Hart Installation Flowchart Mount the Transmitter Installation ProceduresLCD Switches LOI Switches Set SwitchesAMS Configure Alarm DirectionHart Terminal Blocks Connect Wiring and Power UpGrounding Installing the LCD MeterSection Configuration Commissioning on the Bench with Hart Setting the Loop to ManualWiring Diagrams Menu Tree Hart CommunicatorFunction Hart Fast Key Sequence Fast Key SequenceReview Configuration Data Process Variables Sensor TemperatureCheck Output Rerange Basic SetupSet Process Variable Units Fast Keys 3, 1 LCD Display DampingFailure Mode Alarm and Saturation Detailed SetupAlarm and Saturation Level Configuration Alarm and Saturation Values for Multidrop Mode Alarm and Saturation Levels for Burst ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Transmitter Test Sensor Temperature UnitDiagnostics Service Loop Test Advanced Functions for Hart Protocol Saving, Recalling, Cloning Configuration DataRosemount Burst Mode Multidrop Communication Polling a Multidropped Transmitter Changing a Transmitter AddressCommunicating with a Multidropped Transmitter Overview Calibration for Hart Protocol Operation and MaintenanceCalibration Overview Transmitter Data Flow with Calibration Options Determining Calibration Frequency Calculate total probable error TPEChoosing a Trim Procedure Sensor Trim Full Trim Zero TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Analog Output Trim Digital-to-Analog Trim Recall Factory Trim- Analog OutputDigital-to-Analog Trim Using Other Scale Fail Module Diagnostic MessagesNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Appendix a Reference Data SpecificationsPerformance Specifications 00809-0100-4027, Rev AA December Range and Sensor Limits Functional SpecificationsRosemount Physical Specifications 11/2 inch Tri-Clamp Module Dimensional DrawingsInch Tri-Clamp Module Fractional Line Fitting Module Code Process Connection Style Ordering InformationAppendix B Product Certificates North American Certifications Hazardous Locations CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤