HART Communicator

To configure the scaled variable with a HART Communicator, perform the following procedure:

1.From the HOME screen follow the fast key sequence for “Scaled Variable Configuration.”

2.Select OK after the control loop is set to manual.

3.Enter the scaled variable units.

a.Units can be up to six characters long and include A — Z, 0 — 9, -, /,%, and *.

b.The first character is always an asterisk (*), which identifies the units displayed are scaled variable units.

4.Select the Linear Function, which will prompt for two data points.

5.Enter pressure value position 1. Pressure values must be within the range of the transmitter. Enter the lower known value point considering any linear offset.

6.Enter scaled variable position 1. Enter the lower known value point; this value must be no longer than seven digits.

7.Enter pressure value position 2. Pressure values must be within the range of the transmitter.

a.Enter the upper known value point.

8.Enter scaled variable position 2.

a.Enter custom unit equivalent to the upper known value point; this value must be no longer than seven digits.

9.Enter linear offset.

10.Select OK to acknowledge that the loop can be returned to automatic control.

3-16

Image 32
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Operation Maintenance SectionUsing this Manual Section IntroductionService Support Section Installation Overview Safety MessagesEnvironmental ConsiderationsGeneral Hart Installation Flowchart Installation Procedures Mount the TransmitterSet Switches LCD Switches LOI SwitchesConfigure Alarm Direction AMSConnect Wiring and Power Up Hart Terminal BlocksInstalling the LCD Meter GroundingSection Configuration Setting the Loop to Manual Commissioning on the Bench with HartWiring Diagrams Hart Communicator Menu TreeFast Key Sequence Function Hart Fast Key SequenceReview Configuration Data Process Variables Sensor TemperatureCheck Output Rerange Basic SetupSet Process Variable Units Fast Keys 3, 1 Damping LCD DisplayDetailed Setup Failure Mode Alarm and SaturationAlarm and Saturation Level Configuration Alarm and Saturation Levels for Burst Mode Alarm and Saturation Values for Multidrop ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Transmitter Test Sensor Temperature UnitDiagnostics Service Loop Test Saving, Recalling, Cloning Configuration Data Advanced Functions for Hart ProtocolRosemount Burst Mode Multidrop Communication Polling a Multidropped Transmitter Changing a Transmitter AddressCommunicating with a Multidropped Transmitter Operation and Maintenance Overview Calibration for Hart ProtocolCalibration Overview Transmitter Data Flow with Calibration Options Calculate total probable error TPE Determining Calibration FrequencyChoosing a Trim Procedure Sensor Trim Zero Trim Full TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Recall Factory Trim- Analog Output Analog Output Trim Digital-to-Analog TrimDigital-to-Analog Trim Using Other Scale Diagnostic Messages Fail ModuleNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Appendix a Reference Data SpecificationsPerformance Specifications Functional Specifications 00809-0100-4027, Rev AA December Range and Sensor LimitsRosemount Physical Specifications Dimensional Drawings 11/2 inch Tri-Clamp ModuleInch Tri-Clamp Module Fractional Line Fitting Module Ordering Information Code Process Connection StyleAppendix B Product Certificates Hazardous Locations Certifications North American CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤