Recall Factory Trim— Analog Output

Fast Keys

1, 2, 3, 4, 2

 

 

Analog Output Trim

Digital-to-Analog Trim

Fast Keys

1, 2, 3, 2, 1

 

 

This command resets the transmitter analog output trim to the “as shipped” factory settings. The Recall Factory Trim—Analog Output command can be useful for recovering from an inadvertent trim, incorrect Plant Standard or faulty meter.

AMS

Right click on the device and select “Calibrate,” then “Recall Factory Trim” from the menu.

1.Click Next after setting the control loop to manual.

2.Select “Analog output trim” under “Trim to recall” and click Next.

3.Click Next to acknowledge restoration of trim values is complete.

4.Select Next to acknowledge the loop can be returned to automatic control.

5.Select Finish to acknowledge the method is complete.

The Analog Output Trim commands allow you to adjust the transmitter’s current output at the 4 and 20 mA points to match the plant standards. This command adjusts the digital to analog signal conversion (see Figure 4-1 on page 4-3).

HART Communicator

To perform a digital-to-analog trim with a HART Communicator, perform the following procedure.

1.From the HOME screen, enter the fast key sequence for “Digital-to-Analog Trim.” Select OK after setting the control loop to manual, see “Setting the Loop to Manual” on page 3-2.

2.Connect an accurate reference ammeter to the transmitter at the CONNECT REFERENCE METER prompt. Connect the positive lead to the positive terminal and the negative lead to the test terminal in the transmitter terminal compartment, or shunt power through the reference meter at some point.

3.Select OK after connecting the reference meter.

4.Select OK at the SETTING FLD DEV OUTPUT TO 4 MA prompt. The transmitter outputs 4.0 mA.

5.Record the actual value from the reference meter, and enter it at the ENTER METER VALUE prompt. The HART Communicator prompts you to verify whether or not the output value equals the value on the reference meter.

6.Select 1: Yes, if the reference meter value equals the transmitter output

value, or 2: No if it does not.

a.If 1 is selected: Yes, proceed to Step 7.

b.If 2 is selected: No, repeat Step 5.

7.Select OK at the SETTING FLD DEV OUTPUT TO 20 MA prompt, and repeat Steps 5 and 6 until the reference meter value equals the transmitter output value.

8.Select OK after the control loop is returned to automatic control.

4-8

Image 48
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Operation Maintenance SectionUsing this Manual Section IntroductionService Support Section Installation Overview Safety MessagesConsiderations GeneralEnvironmental Hart Installation Flowchart Installation Procedures Mount the TransmitterSet Switches LCD Switches LOI SwitchesConfigure Alarm Direction AMSConnect Wiring and Power Up Hart Terminal BlocksInstalling the LCD Meter GroundingSection Configuration Setting the Loop to Manual Commissioning on the Bench with HartWiring Diagrams Hart Communicator Menu TreeFast Key Sequence Function Hart Fast Key SequenceReview Configuration Data Sensor Temperature Check OutputProcess Variables Basic Setup Set Process Variable UnitsRerange Fast Keys 3, 1 Damping LCD DisplayDetailed Setup Failure Mode Alarm and SaturationAlarm and Saturation Level Configuration Alarm and Saturation Levels for Burst Mode Alarm and Saturation Values for Multidrop ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Sensor Temperature Unit Diagnostics ServiceTransmitter Test Loop Test Saving, Recalling, Cloning Configuration Data Advanced Functions for Hart ProtocolRosemount Burst Mode Multidrop Communication Changing a Transmitter Address Communicating with a Multidropped TransmitterPolling a Multidropped Transmitter Operation and Maintenance Overview Calibration for Hart ProtocolCalibration Overview Transmitter Data Flow with Calibration Options Calculate total probable error TPE Determining Calibration FrequencyChoosing a Trim Procedure Sensor Trim Zero Trim Full TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Recall Factory Trim- Analog Output Analog Output Trim Digital-to-Analog TrimDigital-to-Analog Trim Using Other Scale Diagnostic Messages Fail ModuleNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Specifications Performance SpecificationsAppendix a Reference Data Functional Specifications 00809-0100-4027, Rev AA December Range and Sensor LimitsRosemount Physical Specifications Dimensional Drawings 11/2 inch Tri-Clamp ModuleInch Tri-Clamp Module Fractional Line Fitting Module Ordering Information Code Process Connection StyleAppendix B Product Certificates Hazardous Locations Certifications North American CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤