Rosemount 4500
Reference Manual
Configure Alarm Direction
HART Communicator
Fast Keys | 1, 3, 4, 5 |
|
|
Usage Note
The HART Communicator can be used to configure the security on and off. Otherwise, if the transmitter contains the D1 option, the switch will override any software configuration.
AMS
Right click on the device and select “Device Configuration”, then “Config Write Protect” from the menu.
1.Enter write protect setting, click Next.
2.Click Next to acknowledge setting has changed. If hardware adjustments are activated, click Next to acknowledge the “Switch option detected, function disabled, write protect unchanged” screen. If the hardware adjustments are activated, the write protect will not configure.
3.Click Finish to acknowledge the method is complete.
The transmitter alarm direction is set by repositioning the Alarm slider switch. Position the switch in the HI position for fail high and in the LO position for fail low.
HART Communicator
Fast Keys
1, 4, 2, 7, 6
Usage Note
The HART Communicator can be used to configure the alarm direction to High (HI) or Low (LO). Otherwise, if the transmitter contains the D1 option, the switch on the transmitter will override the HART Communicator.
AMS
Right click on the device and select “Device Configuration,” then “Alarm/Saturation Levels,” then “Alarm Direction” from the menu.
1.Enter desired alarm direction, click Next.
2.Click Next to acknowledge setting has changed. If hardware adjustments are activated, click Next to acknowledge the “Switch option detected, function disabled, alarm direction unchanged” screen. If the hardware adjustments are activated, the write protect will not configure.
3.Click Finish to acknowledge the method is complete.