Rosemount 4500

Reference Manual

00809-0100-4027, Rev AA December 2005

Configure Alarm Direction

HART Communicator

Fast Keys

1, 3, 4, 5

 

 

Usage Note

The HART Communicator can be used to configure the security on and off. Otherwise, if the transmitter contains the D1 option, the switch will override any software configuration.

AMS

Right click on the device and select “Device Configuration”, then “Config Write Protect” from the menu.

1.Enter write protect setting, click Next.

2.Click Next to acknowledge setting has changed. If hardware adjustments are activated, click Next to acknowledge the “Switch option detected, function disabled, write protect unchanged” screen. If the hardware adjustments are activated, the write protect will not configure.

3.Click Finish to acknowledge the method is complete.

The transmitter alarm direction is set by repositioning the Alarm slider switch. Position the switch in the HI position for fail high and in the LO position for fail low.

HART Communicator

Fast Keys

1, 4, 2, 7, 6

Usage Note

The HART Communicator can be used to configure the alarm direction to High (HI) or Low (LO). Otherwise, if the transmitter contains the D1 option, the switch on the transmitter will override the HART Communicator.

AMS

Right click on the device and select “Device Configuration,” then “Alarm/Saturation Levels,” then “Alarm Direction” from the menu.

1.Enter desired alarm direction, click Next.

2.Click Next to acknowledge setting has changed. If hardware adjustments are activated, click Next to acknowledge the “Switch option detected, function disabled, alarm direction unchanged” screen. If the hardware adjustments are activated, the write protect will not configure.

3.Click Finish to acknowledge the method is complete.

2-6

Image 14
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Operation Maintenance SectionUsing this Manual Section IntroductionService Support Section Installation Overview Safety MessagesEnvironmental ConsiderationsGeneral Hart Installation Flowchart Installation Procedures Mount the TransmitterSet Switches LCD Switches LOI SwitchesConfigure Alarm Direction AMSConnect Wiring and Power Up Hart Terminal BlocksInstalling the LCD Meter GroundingSection Configuration Setting the Loop to Manual Commissioning on the Bench with HartWiring Diagrams Hart Communicator Menu TreeFast Key Sequence Function Hart Fast Key SequenceReview Configuration Data Process Variables Sensor TemperatureCheck Output Rerange Basic SetupSet Process Variable Units Fast Keys 3, 1 Damping LCD DisplayDetailed Setup Failure Mode Alarm and SaturationAlarm and Saturation Level Configuration Alarm and Saturation Levels for Burst Mode Alarm and Saturation Values for Multidrop ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Transmitter Test Sensor Temperature UnitDiagnostics Service Loop Test Saving, Recalling, Cloning Configuration Data Advanced Functions for Hart ProtocolRosemount Burst Mode Multidrop Communication Polling a Multidropped Transmitter Changing a Transmitter AddressCommunicating with a Multidropped Transmitter Operation and Maintenance Overview Calibration for Hart ProtocolCalibration Overview Transmitter Data Flow with Calibration Options Calculate total probable error TPE Determining Calibration FrequencyChoosing a Trim Procedure Sensor Trim Zero Trim Full TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Recall Factory Trim- Analog Output Analog Output Trim Digital-to-Analog TrimDigital-to-Analog Trim Using Other Scale Diagnostic Messages Fail ModuleNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Appendix a Reference Data SpecificationsPerformance Specifications Functional Specifications 00809-0100-4027, Rev AA December Range and Sensor LimitsRosemount Physical Specifications Dimensional Drawings 11/2 inch Tri-Clamp ModuleInch Tri-Clamp Module Fractional Line Fitting Module Ordering Information Code Process Connection StyleAppendix B Product Certificates Hazardous Locations Certifications North American CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤