Emerson 4500 manual Alarm and Saturation Levels for Burst Mode

Page 29

Reference Manual

00809-0100-4027, Rev AA December 2005

Rosemount 4500

Alarm and Saturation Levels for Burst Mode

AMS

Right click on the device, select “Device Configuration”, then select “Alarm/Saturation Levels,” then “Alarm Levels” from the menu.

1.Click Next after setting the control loop to manual.

2.Click Next after acknowledging the current alarm levels.

3.Select the desired alarm settings: NAMUR, Rosemount, Other

4.If “Other” is selected, enter desired “HI Value” and “LO Value” custom values.

5.Click Next to acknowledge new alarm levels.

6.Select Next to acknowledge the loop can be returned to automatic control.

7.Select Finish to acknowledge the method is complete.

8.Right click on the device, select “Device Configuration,” then select “Alarm/Saturation Levels,” then “Alarm Levels” from the menu.

9.Select Saturation Levels.

10.Repeat steps 2 - 8 to configure saturation levels.

Transmitters set to burst mode handle saturation and alarm conditions differently.

Alarm Conditions:

Analog output switches to alarm value

Primary variable is burst with a status bit set

Percent of range follows primary variable

Temperature is burst with a status bit set

Saturation:

Analog output switches to saturation value

Primary variable is burst normally

Temperature is burst normally

Alarm and Saturation Values for Multidrop Mode

Transmitters set to multidrop mode handle saturation and alarm conditions differently.

Alarm Conditions:

Primary variable is sent with a status bit set

Percent of range follows primary variable

Temperature is sent with a status bit set

Saturation:

Primary variable is sent normally

Temperature is sent normally

3-13

Image 29
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Section Operation MaintenanceSection Introduction Using this ManualService Support Overview Safety Messages Section InstallationEnvironmental ConsiderationsGeneral Hart Installation Flowchart Mount the Transmitter Installation ProceduresLCD Switches LOI Switches Set SwitchesAMS Configure Alarm DirectionHart Terminal Blocks Connect Wiring and Power UpGrounding Installing the LCD MeterSection Configuration Commissioning on the Bench with Hart Setting the Loop to ManualWiring Diagrams Menu Tree Hart CommunicatorFunction Hart Fast Key Sequence Fast Key SequenceReview Configuration Data Process Variables Sensor TemperatureCheck Output Rerange Basic SetupSet Process Variable Units Fast Keys 3, 1 LCD Display DampingFailure Mode Alarm and Saturation Detailed SetupAlarm and Saturation Level Configuration Alarm and Saturation Values for Multidrop Mode Alarm and Saturation Levels for Burst ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Transmitter Test Sensor Temperature UnitDiagnostics Service Loop Test Advanced Functions for Hart Protocol Saving, Recalling, Cloning Configuration DataRosemount Burst Mode Multidrop Communication Polling a Multidropped Transmitter Changing a Transmitter AddressCommunicating with a Multidropped Transmitter Overview Calibration for Hart Protocol Operation and MaintenanceCalibration Overview Transmitter Data Flow with Calibration Options Determining Calibration Frequency Calculate total probable error TPEChoosing a Trim Procedure Sensor Trim Full Trim Zero TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Analog Output Trim Digital-to-Analog Trim Recall Factory Trim- Analog OutputDigital-to-Analog Trim Using Other Scale Fail Module Diagnostic MessagesNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Appendix a Reference Data SpecificationsPerformance Specifications 00809-0100-4027, Rev AA December Range and Sensor Limits Functional SpecificationsRosemount Physical Specifications 11/2 inch Tri-Clamp Module Dimensional DrawingsInch Tri-Clamp Module Fractional Line Fitting Module Code Process Connection Style Ordering InformationAppendix B Product Certificates North American Certifications Hazardous Locations CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤