Emerson 4500 manual Basic Setup, Set Process Variable Units, Rerange

Page 24

Rosemount 4500

Reference Manual

00809-0100-4027, Rev AA December 2005

BASIC SETUP

Set Process Variable Units

Fast Keys

1, 3, 2

 

 

Rerange

The PV Unit command sets the process variable units to allow you to monitor your process using the appropriate units of measure.

HART Communicator

Enter the fast key sequence for “Set Process Variable Units.” Select from the following engineering units:

inH2O

bar

torr

inHg

mbar

atm

ftH2O

g/cm2

MPa

mmH2O

kg/cm2

• inH2O at 4 °C

mmHg

Pa

• mmH2O at 4 °C

psi

kPa

 

 

AMS

Right click on the device and select “Configuration Properties” from the menu. In the Basic Setup tab, use “Unit” drop down menu to select units.

The Range Values command sets the 4 and 20 mA points (lower and upper range values). In practice, you may reset the transmitter range values as often as necessary to reflect changing process conditions. Changing the lower or upper range point results in similar changes to the span.

NOTE

Transmitters are shipped from Rosemount Inc. fully calibrated per request or to the factory default of full scale (span = upper range limit.)

Use one of the methods below to rerange the transmitter. Each method is unique; examine all options closely before deciding which method works best for your process.

Rerange with a HART Communicator only.

Rerange with a pressure input source and a HART Communicator.

Rerange with a pressure input source and the local zero and span buttons (option D1).

Rerange with AMS only.

Rerange with a pressure input source and AMS.

NOTE

If the transmitter security switch is ON, adjustments to the zero and span cannot be made. Refer to “Set Switches” on page 2-5for security information.

3-8

Image 24
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Operation Maintenance SectionUsing this Manual Section IntroductionService Support Section Installation Overview Safety MessagesConsiderations GeneralEnvironmental Hart Installation Flowchart Installation Procedures Mount the TransmitterSet Switches LCD Switches LOI SwitchesConfigure Alarm Direction AMSConnect Wiring and Power Up Hart Terminal BlocksInstalling the LCD Meter GroundingSection Configuration Setting the Loop to Manual Commissioning on the Bench with HartWiring Diagrams Hart Communicator Menu TreeFast Key Sequence Function Hart Fast Key SequenceReview Configuration Data Sensor Temperature Check OutputProcess Variables Basic Setup Set Process Variable UnitsRerange Fast Keys 3, 1 Damping LCD DisplayDetailed Setup Failure Mode Alarm and SaturationAlarm and Saturation Level Configuration Alarm and Saturation Levels for Burst Mode Alarm and Saturation Values for Multidrop ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Sensor Temperature Unit Diagnostics ServiceTransmitter Test Loop Test Saving, Recalling, Cloning Configuration Data Advanced Functions for Hart ProtocolRosemount Burst Mode Multidrop Communication Changing a Transmitter Address Communicating with a Multidropped TransmitterPolling a Multidropped Transmitter Operation and Maintenance Overview Calibration for Hart ProtocolCalibration Overview Transmitter Data Flow with Calibration Options Calculate total probable error TPE Determining Calibration FrequencyChoosing a Trim Procedure Sensor Trim Zero Trim Full TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Recall Factory Trim- Analog Output Analog Output Trim Digital-to-Analog TrimDigital-to-Analog Trim Using Other Scale Diagnostic Messages Fail ModuleNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Specifications Performance SpecificationsAppendix a Reference Data Functional Specifications 00809-0100-4027, Rev AA December Range and Sensor LimitsRosemount Physical Specifications Dimensional Drawings 11/2 inch Tri-Clamp ModuleInch Tri-Clamp Module Fractional Line Fitting Module Ordering Information Code Process Connection StyleAppendix B Product Certificates Hazardous Locations Certifications North American CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤