Rosemount 4500
Reference Manual
Table
Calibration Tasks
Transmitter | Bench Calibration Tasks | Field Calibration Tasks |
|
|
|
4500_ G | 1. Set output configuration parameters: | 1. | Reconfigure parameters if necessary. |
4500_ A | a. Set the range points. | 2. | Perform low trim value section of the |
| |||
| b. Set the output units. |
| full sensor trim procedure to correct for |
|
| mounting position effects. | |
| c. Set the output type. |
| |
|
|
| |
| d. Set the damping value. |
|
|
| 2. Optional: Perform a full sensor trim if |
|
|
| equipment available (accurate pressure |
|
|
| source required), otherwise perform the |
|
|
| low trim value section of the full sensor |
|
|
| trim procedure. |
|
|
| 3. Optional: Perform an analog output trim |
|
|
| (Accurate multimeter required) |
|
|
Calibration Overview
NOTE:
The transmitter performs to specification only when completely and correctly calibrated, including full sensor and analog output trim.
Complete calibration of the 4500 pressure transmitter involves the following tasks:
Configure the output parameters
•Set Process Variable Units (page
•Set Output Type (page
•Rerange (page
•Set Damping (page
Calibrate the sensor
•Full Trim (page
•Zero Trim (page
Calibrate the
•
•