Rosemount 4500
Reference Manual
Table
Symptom | Corrective Actions |
|
|
Transmitter milliamp reading is zero | Verify power is applied to signal terminals |
| Check power wires for reversed polarity |
| Verify terminal voltage is 11.25 to 30 V dc |
| Check for open diode across test terminal |
|
|
Transmitter Not Communicating with | Verify the output is between 4 and 20 mA or saturation levels |
HART Communicator | Verify clean DC Power to transmitter (Max AC noise 0.2 volts peak to peak) |
| |
| Check loop resistance, 250 Ω minimum (PS voltage |
| Check if unit is addressed properly |
|
|
Transmitter milliamp reading is low or high | Verify applied pressure |
| Verify 4 and 20 mA range points |
| Verify output is not in alarm condition |
| Verify if 4 – 20 mA output trim is required |
|
|
Transmitter will not respond to changes in | Check test equipment |
applied pressure | Verify applied pressure is between the 4 and 20 mA set points |
| |
| Verify output is not in alarm condition |
| Verify transmitter is not in Loop Test mode |
|
|
Digital Pressure Variable reading is low or high | Check test equipment (verify accuracy) |
| Verify transmitter is calibrated properly |
| Verify pressure calculations for application |
|
|
Digital Pressure Variable reading is erratic | Check application for faulty equipment in pressure line |
| Verify transmitter is not reacting directly to equipment turning on/off |
| Verify damping is set properly for application |
|
|
Milliamp reading is erratic | Verify power source to transmitter has adequate voltage and current |
| Check for external electrical interference |
| Verify transmitter is properly grounded |
| Verify shield for twisted pair is only grounded at one end |
|
|