Emerson 4500 manual Check Output, Process Variables, Sensor Temperature

Page 23

Reference Manual

00809-0100-4027, Rev AA December 2005

Rosemount 4500

CHECK OUTPUT

Before performing other transmitter on-line operations, review the digital output parameters to ensure that the transmitter is operating properly and is configured to the appropriate process variables.

Process Variables

Fast Keys

1, 1

 

 

The process variables for the 4500 provide transmitter output, and are continuously updated. The pressure reading in both engineering units and percent of range will continue to track with pressures outside of the defined range from the lower to the upper range limit of the Transmitter.

HART Communicator

The process variable menu displays the following process variables:

Pressure

Percent of range

Analog output

Sensor temperature

Scaled Variable (SV)

Sensor Temperature

Fast Keys

1, 1, 4

 

 

NOTE

Regardless of the range points, the 4500 will measure and report all readings within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 100 psi, and the transmitter detects a pressure of 150 psi, it digitally outputs the 150 psi reading and a 150% of span reading. However, there may be up to ±5.0% error associated with output outside of the range points.

AMS

Right click on the device and select “Process Variables...” from the menu.The process variable screen displays the following process variables:

Pressure

Percent of range

Analog output

Sensor temperature

Scaled Variable (SV)

The 4500 contains a temperature sensor near the pressure sensor in the Transmitter. When reading this temperature, keep in mind the sensor is not a process temperature reading.

HART Communicator

Enter the fast key sequence for “Sensor Temperature” to view the sensor temperature reading.

AMS

Right click on the device and select “Process Variables...” from the menu. “Snsr Temp” is the sensor temperature reading.

3-7

Image 23
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Section Operation MaintenanceSection Introduction Using this ManualService Support Overview Safety Messages Section InstallationEnvironmental ConsiderationsGeneral Hart Installation Flowchart Mount the Transmitter Installation ProceduresLCD Switches LOI Switches Set SwitchesAMS Configure Alarm DirectionHart Terminal Blocks Connect Wiring and Power UpGrounding Installing the LCD MeterSection Configuration Commissioning on the Bench with Hart Setting the Loop to ManualWiring Diagrams Menu Tree Hart CommunicatorFunction Hart Fast Key Sequence Fast Key SequenceReview Configuration Data Process Variables Sensor TemperatureCheck Output Rerange Basic SetupSet Process Variable Units Fast Keys 3, 1 LCD Display DampingFailure Mode Alarm and Saturation Detailed SetupAlarm and Saturation Level Configuration Alarm and Saturation Values for Multidrop Mode Alarm and Saturation Levels for Burst ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Transmitter Test Sensor Temperature UnitDiagnostics Service Loop Test Advanced Functions for Hart Protocol Saving, Recalling, Cloning Configuration DataRosemount Burst Mode Multidrop Communication Polling a Multidropped Transmitter Changing a Transmitter AddressCommunicating with a Multidropped Transmitter Overview Calibration for Hart Protocol Operation and MaintenanceCalibration Overview Transmitter Data Flow with Calibration Options Determining Calibration Frequency Calculate total probable error TPEChoosing a Trim Procedure Sensor Trim Full Trim Zero TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Analog Output Trim Digital-to-Analog Trim Recall Factory Trim- Analog OutputDigital-to-Analog Trim Using Other Scale Fail Module Diagnostic MessagesNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Appendix a Reference Data SpecificationsPerformance Specifications 00809-0100-4027, Rev AA December Range and Sensor Limits Functional SpecificationsRosemount Physical Specifications 11/2 inch Tri-Clamp Module Dimensional DrawingsInch Tri-Clamp Module Fractional Line Fitting Module Code Process Connection Style Ordering InformationAppendix B Product Certificates North American Certifications Hazardous Locations CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤