Emerson 4500 manual Digital-to-Analog Trim Using Other Scale

Page 49

Reference Manual

00809-0100-4027, Rev AA December 2005

Rosemount 4500

AMS

Digital-to-Analog Trim Using Other Scale

Fast Keys

1, 2, 3, 2, 2

 

 

Right click on the device and select “Calibrate,” then “D/A Trim” from the menu.

1.Click Next after setting the control loop to manual.

2.Click Next after connecting the reference meter.

3.Click Next at the “Setting fld dev output to 4mA” screen.

4.Record the actual value from the reference meter, and enter it at the “Enter meter value” screen and click Next.

5.Select Yes, if the reference meter value equals the transmitter output value, or No if it does not. Click Next.

a.If Yes is selected, proceed to Step 6.

b.If No is selected, repeat Step 4.

6.Click Next at the “Setting fld dev output to 20mA” screen.

7.Repeat Step 4 - Step 5 until the reference meter equals the transmitter output value.

8.Select Next to acknowledge the loop can be returned to automatic control.

9.Select Finish to acknowledge the method is complete.

The Scaled D/A Trim command matches the 4 and 20 mA points to a user selectable reference scale other than 4 and 20 mA (for example, 1 to 5 volts if measuring across a 250 ohm load, or 0 to 100 percent if measuring from a Distributed Control System (DCS)). To perform a scaled D/A trim, connect an accurate reference meter to the transmitter and trim the output signal to scale, as outlined in the Output Trim procedure.

NOTE

Use a precision resistor for optimum accuracy. If you add a resistor to the loop, ensure that the power supply is sufficient to power the transmitter to a 20 mA output with additional loop resistance.

AMS

Right click on the device and select “Calibrate,” then “Scaled D/A trim” from the menu.

1.Click Next after setting the control loop to manual.

2.Select Change to change scale, click Next.

3.Enter Set scale-Lo output value, click Next.

4.Enter Set scale-Hi output value, click Next.

5.Click Next to proceed with Trim.

6.Click Next after connecting the reference meter.

7.Click Next at the “Setting fld dev output to 4 mA” screen.

8.Record the actual value from the reference meter, and enter it at the “Enter meter value” screen and click Next.

9.Select Yes, if the reference meter value equals the transmitter output value, or No if it does not. Click Next.

4-9

Image 49
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Section Operation MaintenanceSection Introduction Using this ManualService Support Overview Safety Messages Section InstallationGeneral ConsiderationsEnvironmental Hart Installation Flowchart Mount the Transmitter Installation ProceduresLCD Switches LOI Switches Set SwitchesAMS Configure Alarm DirectionHart Terminal Blocks Connect Wiring and Power UpGrounding Installing the LCD MeterSection Configuration Commissioning on the Bench with Hart Setting the Loop to ManualWiring Diagrams Menu Tree Hart CommunicatorFunction Hart Fast Key Sequence Fast Key SequenceReview Configuration Data Check Output Sensor TemperatureProcess Variables Set Process Variable Units Basic SetupRerange Fast Keys 3, 1 LCD Display DampingFailure Mode Alarm and Saturation Detailed SetupAlarm and Saturation Level Configuration Alarm and Saturation Values for Multidrop Mode Alarm and Saturation Levels for Burst ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Diagnostics Service Sensor Temperature UnitTransmitter Test Loop Test Advanced Functions for Hart Protocol Saving, Recalling, Cloning Configuration DataRosemount Burst Mode Multidrop Communication Communicating with a Multidropped Transmitter Changing a Transmitter AddressPolling a Multidropped Transmitter Overview Calibration for Hart Protocol Operation and MaintenanceCalibration Overview Transmitter Data Flow with Calibration Options Determining Calibration Frequency Calculate total probable error TPEChoosing a Trim Procedure Sensor Trim Full Trim Zero TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Analog Output Trim Digital-to-Analog Trim Recall Factory Trim- Analog OutputDigital-to-Analog Trim Using Other Scale Fail Module Diagnostic MessagesNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Performance Specifications SpecificationsAppendix a Reference Data 00809-0100-4027, Rev AA December Range and Sensor Limits Functional SpecificationsRosemount Physical Specifications 11/2 inch Tri-Clamp Module Dimensional DrawingsInch Tri-Clamp Module Fractional Line Fitting Module Code Process Connection Style Ordering InformationAppendix B Product Certificates North American Certifications Hazardous Locations CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤