Reference Manual

00809-0100-4027, Rev AA December 2005

Rosemount 4500

4.Select the back arrow from the HOME/ONLINE screen. The HART Communicator menu appears.

5.Select 1: Offline, 2: Saved Configuration, 1: Module Contents to reach the MODULE CONTENTS menu.

6.Use the DOWN ARROW to scroll through the list of configurations in the memory module, and use the RIGHT ARROW to select and retrieve the required configuration.

7.Select 1: Edit.

8.Select 1: Mark All.

9.Select F2 SAVE.

10.Use the DOWN ARROW to scroll through the list of configurations in the memory module, and use the RIGHT ARROW to select the configuration again.

11.Select 3: “Send” to download the configuration to the transmitter.

12.Select OK after the control loop is set to manual.

13.After the configuration has been sent, select OK to acknowledge that the loop can be returned to automatic control.

When finished, the HART Communicator informs you of the status. Repeat Steps 3 through 13 to configure another transmitter.

NOTE

The transmitter receiving cloned data must have the same software version (or later) as the original transmitter.

AMS creating a Reusable Copy

To create a reusable copy of a configuration perform the following procedure:

1.Select View then User Configuration View from the menu bar (or click the toolbar button).

2.In the User Configuration window, right click and select New from the context menu.

3.In the New window, select a device from the list of templates shown, and click OK.

4.The template is copied into the User Configurations window, with the tag name highlighted; rename it as appropriate and press Enter.

NOTE

A device icon can also be copied by dragging and dropping a device template or any other device icon from AMS Explorer or Device Connection View into the User Configurations window.

The “Compare Configurations” window appears, showing the Current values of the copied device on one side and mostly blank fields on the other (User Configuration) side.

5.Transfer values from the current configuration to the user configuration as appropriate or enter values by typing them into the available fields.

6.Click Apply to apply the values, or click OK to apply the values and close the window.

3-21

Image 37
Contents Reference Manual Page Rosemount 4500 Hygienic Pressure Transmitter Page Table of Contents Section Operation MaintenanceSection Introduction Using this ManualService Support Overview Safety Messages Section InstallationGeneral ConsiderationsEnvironmental Hart Installation Flowchart Mount the Transmitter Installation ProceduresLCD Switches LOI Switches Set SwitchesAMS Configure Alarm DirectionHart Terminal Blocks Connect Wiring and Power UpGrounding Installing the LCD MeterSection Configuration Commissioning on the Bench with Hart Setting the Loop to ManualWiring Diagrams Menu Tree Hart CommunicatorFunction Hart Fast Key Sequence Fast Key SequenceReview Configuration Data Check Output Sensor TemperatureProcess Variables Set Process Variable Units Basic SetupRerange Fast Keys 3, 1 LCD Display DampingFailure Mode Alarm and Saturation Detailed SetupAlarm and Saturation Level Configuration Alarm and Saturation Values for Multidrop Mode Alarm and Saturation Levels for Burst ModeAlarm Level Verification Process Alerts Scaled Variable Configuration Rosemount Re-mapping Diagnostics Service Sensor Temperature UnitTransmitter Test Loop Test Advanced Functions for Hart Protocol Saving, Recalling, Cloning Configuration DataRosemount Burst Mode Multidrop Communication Communicating with a Multidropped Transmitter Changing a Transmitter AddressPolling a Multidropped Transmitter Overview Calibration for Hart Protocol Operation and MaintenanceCalibration Overview Transmitter Data Flow with Calibration Options Determining Calibration Frequency Calculate total probable error TPEChoosing a Trim Procedure Sensor Trim Full Trim Zero TrimRecall Factory Trim Recall Factory Trim- Sensor Trim Analog Output Trim Digital-to-Analog Trim Recall Factory Trim- Analog OutputDigital-to-Analog Trim Using Other Scale Fail Module Diagnostic MessagesNonpv Limit Stuck KEY Troubleshooting Symptom Corrective Actions Performance Specifications SpecificationsAppendix a Reference Data 00809-0100-4027, Rev AA December Range and Sensor Limits Functional SpecificationsRosemount Physical Specifications 11/2 inch Tri-Clamp Module Dimensional DrawingsInch Tri-Clamp Module Fractional Line Fitting Module Code Process Connection Style Ordering InformationAppendix B Product Certificates North American Certifications Hazardous Locations CertificationsRosemount Rosemount Index Index-2 Page ¢00809-0100-4027 ¤