E.FIELD WIRING CONTROL BOX COMPARTMENT - 230 V, 50 HZ

WARNING: Risk of electrical shock. Make sure the power has been disconnected before performing the following procedures. Refer to Important Safety Instructions located on page 2.

CAUTION: Risk of electrical shock. All services must have an Earth Leakage Circuit Breaker (ELCB) which will provide additional protection against line-to-ground shock hazard. A separate service is required for the whirlpool.

The whirlpool controls and system have been prewired at the factory. A licensed electrician should make a routine service connection to the field wiring compartment of the control box containing blue and brown wires and earth lug.

Air

 

 

Actuator

Control

Field Wiring

 

Compartment

Air

Box

 

Actuator

 

 

Tube

 

 

 

 

Bonding

Pump

 

(Earthing) Lug*

 

 

*For bonding in accordance with National and Local Codes.

F.CONNECT CONTROL BOX - 230 V, 50 HZ

Connect service to the field wiring compartment of the control box. The 50 Hz model control box contains blue and brown wires and earth lug.

A 230 V, 15 A, 50 Hz dedicated circuit is required. Provide an Earth Leakage Circuit Breaker.

Provide a separate equipment earthing conductor for the inside earth lug. The earthing conductor must not be connected to any current carrying conductor. Follow local electrical codes. A 230 V, 15A, 50 Hz separate circuit is required.

Blue Neutral (Neutral)

Brown (Phase)

Wire Connectors

Earth (Ground) Lug

Earth (Ground)

Phase (Line)

Earthing Lug (for bonding in accor- dance with national and local codes)

Kohler Co., Kohler WI

19

106548-CA(9437)

Image 19
Contents 106548- CA Copyright E1994 Kohler Co Important Safety Instructions Table of Contents Introduction ROUGHING-IN K-1200-AC, K-1201-AC ROUGHING-IN K-1205-AC, K-1206-AC ROUGHING-IN K-1210-AC, K-1211-AC ROUGHING-IN K-1215-AC, K-1216-AC ROUGHING-IN K-1220-AC, K-1221-AC Product Notices Installer Hazard NotificationProduct Requirements Clearance Requirements Installation RequirementsNEW or Replacement Installation Requirements Tools Required Materials RequiredStud Pocket Preparation Site RequirementsOLD Bath Removal Subfloor PreparationPlumbing Preparation Before Installing UnitTILING-IN Bead Installation Partially Install Bath DrainWhirlpool SET-IN Install WhirlpoolInstall Plumbing Height AdjustmentSecure Whirlpool Electrical Connections AIR Actuator Versions Wiring Information 120 V, 60 HZ Excluding -J1 ModelsIdentify Electrical Requirements Field Wiring Diagram 120 V, 60 HZ -J1 Models only Locate Field Wiring Compartment 120 V, 60 HZ -J1 Models onlyConnect Control BOX 230 V, 50 HZ Field Wiring Control BOX Compartment 230 V, 50 HZWiring Information 120 V, 60 HZ Wall Timer Versions Electrical Connections Wall Timer VersionsComplete Finish Wall Water Test Whirlpool & ElectronicsOptional K-1507 Apron Installation Optional K-1515 Apron Installation CLEAN-UP After Installation Complete InstallationInstall Handles and Spout START-UP Whirlpool Confirm Proper OperationOperating Sequence Recommended Action SymptomsTroubleshoot Whirlpool System Probable CausesKohler Co., Kohler WI 106548-CA1093 106548-CA1093 Kohler Co., Kohler WI