Emerson 400501-08 manual Interger File N10 High Byte Low Byte

Page 70

Epsilon Ei DeviceNet Drive Reference Manual

Index 1 Velocity is mapped to class 0x68, instance 0x02, attribute 0x09, as shown in the table below.

The following parameters will be used to set up this explicit message.

Interger File N10

High Byte

 

Low Byte

N10:0

TXID=0x01

 

COMMAND=0x01

 

 

 

 

N10:1

PORT=0x00

 

SIZE OF DATA FIELD=0x0A

 

 

 

 

N10:2

SERVICE=0x10 (SET)

 

MacID=0x04

 

 

 

 

N10:3

 

CLASS=0x68

 

 

 

N10:4

 

INSTANCE=0x02

 

 

 

N10:5

 

ATTRIBUTE=0x09

 

 

 

 

After the N10 file is set, B3:0/0 can be set high to send the explicit message to the scanner card. After bit I:3/15 is set by the PLC, the message can be viewed by setting B3:0/2 high which copies the M1: file to the N11: file.

The response from the drive should resemble the following.

Figure 24: PLC Configuration Example 2

The following table reflects the results of the Index 1 Velocity example. These results are verifiable via the keypad interface.

58

Image 70
Contents Reference Manual Page Epsilon Ei DeviceNet Drive Reference Manual Page Website and Email Customer Support952 Technical Support 952 995-8033 or 800Document Conventions Training Services 952 995-8000 or 800Customer Service Sales 952 995-8000 or 800 Application Engineering 952 995-8000 or 800This Represents General Warning Safety InstructionsReference Materials Qualified PersonSetup, Commissioning and Maintenance Safety ConsiderationsSafety Precautions EnclosureSafety of Machinery General warningTable of Contents Drive Parameters Network Configuration Quick StartExplicit Messaging Quick Start Appendix Glossary IndexIntroduction PurposeDeviceNet Overview DeviceNet Communications LinkDeviceNet Messaging and Communications Master/Slave RelationshipMaster/Slave Relationship DeviceNet Hardware Components InstallationMechanical Installation CablesPower Supply Requirements Electrical InstallationConnectors Physical Connections to the DeviceNet NetworkInstallation Epsilon Ei DeviceNet Drive Reference Manual DeviceNet Tab Connection TypesSoftware Interface Polled I/O Connections Implicit MessagingBaud Rate Master Receive and Master Send Assembly Block SelectionsMacID Index Select Predefined Index Sel PredefConfiguring the DeviceNet Network Index Select User Defined Index Sel UserDefIndex Type Position ControlNo Operation CCWInput Word Select Data Pointer Code DescriptionOutput Word Select Data Pointer Command Assembly Code Response Assembly CodesConfiguring the DeviceNet Network Host Mode Enable Ei-DN Input Processing LogicInformation DeviceNet Online TabCounters Network Status LED StatusEstablished Connections Module Status LEDInput and Output Tab DeviceNet BitsFaults and Diagnostic Display DN Allocation Master MacID DN Allocation Choice Connections EstablishedEi-DN Modbus Address DN Bus Off Counter DN Bus Off Fault CountDN Baud Rate DN Bus Off InterruptDN Device Type DN Comm Time-out Fault CountDN Duplicate MacID Fault Count DN FAB Master Receive BlockDN FAB Master Send Block DN Host ModeDN MacID DN Master Receive FAB Type DN Master Receive BitmapDN Master Send Bitmap DN Master Send FAB Type DN Module StatusDN Network Status DN Status Major Recoverable FaultDN Status Major Unrecoverable Fault DN Receive CounterDN Transmit Counter DN Status Minor Recoverable FaultDN Status Minor Unrecoverable Fault DN Vendor IDHardware Interface Accessing the EDS FileModule Status LED Network Status LED Setting the Baud Rate and MacID Externally One TouchViewing and Changing the Baud Rate and MacID Display Value Baud Epsilon Ei DeviceNet Drive Reference Manual Network Configuration Quick Start EquipmentPolled I/O Setup Example #1 Index SelPredefNetwork Configuration Quick Start Example #2 Index Sel Userdef DN Setup / Index Sel Userdef Inputs Tab Outputs Tab Example #3 Index Type DN Setup / Index Type Output Word Select Input Word Select Example #4 Position Control Dn Setup / Position Control Network Configuration Quick Start Master Configuration RS Networx ConfigurationScanlist Tab Input Tab Output Tab Epsilon Ei DeviceNet Drive Reference Manual How to Send Explicit Messages Explicit Messaging Quick StartExecute Explicit Messaging Examples Description of N10 Integer FileExamples Explanation of PLC ProgramExample 1 Read Index 0 Velocity Example 2 Write Index 1 Velocity Integer File N11 High Byte Low ByteInterger File N10 High Byte Low Byte Explicit Messaging Quick Start Epsilon Ei DeviceNet Drive Reference Manual Name Drive ParametersBy Name DeviceNet Data TypeUdint Drive Parameters ProductID.Option1IDFunctionModule By DeviceNet Class 0x01 DeviceNet.DeviceNetIdentityObject.DeviceType 104 0x68 See Note 0x09 Index.Instance#.RegistrationOffset 109 0x6D 0x01 0x04 Position.FollowingError 0x01 0x0D Status.TorqueFeedback Epsilon Ei DeviceNet Drive Reference Manual Appendix Index Select PredefinedMaster Receive Assembly Block Index Sel User Def Index Select User DefinedIndex Type Position Control CCWGlossary Explicit Message Drop LineEpsilon Drive Explicit Messaging ConnectionsLink Consumer Object One touch ConfigurationConnections Link Producer ObjectUcmm Index Epsilon Ei DeviceNet Drive Reference Manual Index Epsilon Ei DeviceNet Drive Reference Manual