Epsilon Ei DeviceNet Drive Reference Manual
Connectors
DeviceNet connectors can be either
Power Supply Requirements
A separate 24 VDC power supply is needed for the DeviceNet network. The
The
Fuse protection must be provided for each segment of the cable system.
The power supply must be correctly sized to provide each device with its required power.
Power supplies should be distributed throughout the DeviceNet network to maintain a maximum of 4 Amps per trunk branch.
For more details, refer to the ODVA Specification Volumes I and II, Release 2.0.
Terminating Resistors
Terminating resistors are used to reduce the reflection of signals over the network. Each terminator must be 121 ohms and installed on both ends of the network between CAN_L (pin 2) and CAN_H (pin 3).
Electrical Installation
Physical Connections to the DeviceNet Network
A standard five wire configuration is used to connect the
When multiple
Pin Number | Name | Insulation Color |
1 | V- | Black |
|
|
|
2 | CAN_L | Blue |
|
|
|
3 | Drain | None |
|
|
|
4 | CAN_H | White |
|
|
|
5 | V+ | Red |
|
|
|
6