Configuring the DeviceNet Network

Connection Types

The Epsilon Ei-DN DeviceNet interface was designed to communicate with a DeviceNet network in two ways. Polled I/O connections and Explicit Messaging connections can be used to access all read or read/write data from the Epsilon Ei-DN.

Polled I/O Connections (Implicit Messaging)

The Poll Command is an I/O Message that is transmitted by the Master. A Poll Command is directed towards a single, specific Slave (point-to-point). A Master must transmit a separate Poll Command Message for each one of its Slaves that is to be polled. The Poll Response is an I/O Message that a Slave transmits back to the Master.

A Polled Message contains I/O data that can be read by the PLC on every scan. Polled messages are used for high priority data and are typically used to transmit parameters, such as index initiates or position feedback.

Explicit Messaging

Explicit Messages are initiated from a user-created program inside a PLC or PC-based software program. In a PLC, these messages are sent and received using the PLC-specific explicit message setup. Using Explicit Messaging, all user parameters can be accessed in the Ei-DN drive. These messages allow parameters to be sent in messages that may take multiple scans of the PLC. Explicit Messages are lower priority than Polled I/O messaging connections and work well for transferring recipes or any 32 bit parameters to the drive.

Software Interface

This section discusses how to configure a DeviceNet Network with PowerTools FM software and discusses the parameters that appear on the tabs related to DeviceNet configuration. Other tabs are described in the Epsilon Ei Indexing Drive and FM-2 Indexing Module Reference Manual (P/N 400507-01).

DeviceNet Tab

The DeviceNet tab allows the user to configure DeviceNet parameters and watch the DeviceNet Parameters while online with the drive through PowerTools FM. The DeviceNet tab has two sub-tabs: DN Setup and Online.

The DN Setup tab allows the user to set up MacID, Baud Rate, choice of predefined assembly blocks, and host-mode enable as well as display the fixed assembly block word mapping.

9

Image 21
Contents Reference Manual Page Epsilon Ei DeviceNet Drive Reference Manual Page 952 Customer SupportWebsite and Email Technical Support 952 995-8033 or 800Customer Service Sales 952 995-8000 or 800 Training Services 952 995-8000 or 800Document Conventions Application Engineering 952 995-8000 or 800This Represents Reference Materials Safety InstructionsGeneral Warning Qualified PersonSafety Precautions Safety ConsiderationsSetup, Commissioning and Maintenance EnclosureGeneral warning Safety of MachineryTable of Contents Explicit Messaging Quick Start Network Configuration Quick StartDrive Parameters Appendix Glossary IndexPurpose IntroductionDeviceNet Communications Link DeviceNet OverviewMaster/Slave Relationship DeviceNet Messaging and CommunicationsMaster/Slave Relationship Mechanical Installation InstallationDeviceNet Hardware Components CablesConnectors Electrical InstallationPower Supply Requirements Physical Connections to the DeviceNet NetworkInstallation Epsilon Ei DeviceNet Drive Reference Manual Software Interface Connection TypesDeviceNet Tab Polled I/O Connections Implicit MessagingMacID Master Receive and Master Send Assembly Block SelectionsBaud Rate Index Select Predefined Index Sel PredefIndex Select User Defined Index Sel UserDef Configuring the DeviceNet NetworkPosition Control Index TypeCCW No OperationCode Description Input Word Select Data PointerOutput Word Select Data Pointer Response Assembly Codes Command Assembly CodeConfiguring the DeviceNet Network Ei-DN Input Processing Logic Host Mode EnableDeviceNet Online Tab InformationCounters Established Connections StatusNetwork Status LED Module Status LEDDeviceNet Bits Input and Output TabFaults and Diagnostic Display DN Allocation Choice Connections Established DN Allocation Master MacIDEi-DN Modbus Address DN Baud Rate DN Bus Off Fault CountDN Bus Off Counter DN Bus Off InterruptDN Duplicate MacID Fault Count DN Comm Time-out Fault CountDN Device Type DN FAB Master Receive BlockDN Host Mode DN FAB Master Send BlockDN MacID DN Master Receive Bitmap DN Master Receive FAB TypeDN Master Send Bitmap DN Module Status DN Master Send FAB TypeDN Status Major Unrecoverable Fault DN Status Major Recoverable FaultDN Network Status DN Receive CounterDN Status Minor Unrecoverable Fault DN Status Minor Recoverable FaultDN Transmit Counter DN Vendor IDAccessing the EDS File Hardware InterfaceModule Status LED Setting the Baud Rate and MacID Externally One Touch Network Status LEDViewing and Changing the Baud Rate and MacID Display Value Baud Epsilon Ei DeviceNet Drive Reference Manual Equipment Network Configuration Quick StartExample #1 Index SelPredef Polled I/O SetupNetwork Configuration Quick Start Example #2 Index Sel Userdef DN Setup / Index Sel Userdef Inputs Tab Outputs Tab Example #3 Index Type DN Setup / Index Type Output Word Select Input Word Select Example #4 Position Control Dn Setup / Position Control Network Configuration Quick Start RS Networx Configuration Master ConfigurationScanlist Tab Input Tab Output Tab Epsilon Ei DeviceNet Drive Reference Manual Explicit Messaging Quick Start How to Send Explicit MessagesExecute Description of N10 Integer File Explicit Messaging ExamplesExplanation of PLC Program ExamplesExample 1 Read Index 0 Velocity Integer File N11 High Byte Low Byte Example 2 Write Index 1 VelocityInterger File N10 High Byte Low Byte Explicit Messaging Quick Start Epsilon Ei DeviceNet Drive Reference Manual By Name Drive ParametersName DeviceNet Data TypeUdint Drive Parameters ProductID.Option1IDFunctionModule By DeviceNet Class 0x01 DeviceNet.DeviceNetIdentityObject.DeviceType 104 0x68 See Note 0x09 Index.Instance#.RegistrationOffset 109 0x6D 0x01 0x04 Position.FollowingError 0x01 0x0D Status.TorqueFeedback Epsilon Ei DeviceNet Drive Reference Manual Index Select Predefined AppendixIndex Select User Defined Master Receive Assembly Block Index Sel User DefIndex Type CCW Position ControlGlossary Epsilon Drive Drop LineExplicit Message Explicit Messaging ConnectionsConnections One touch ConfigurationLink Consumer Object Link Producer ObjectUcmm Index Epsilon Ei DeviceNet Drive Reference Manual Index Epsilon Ei DeviceNet Drive Reference Manual