Heat Controller HSS Water Tank Preparation, HWG Water Piping, Water Tank Refill, Initial Start-Up

Page 23

T h e Q u a l i t y L e a d e r i n C o n d i t i o n i n g A i r

Hot Water Generator

Figure 17: Alternate HWG Piping with concentric/coaxial fitting (part #S69619804 not included with unit)

(Indoor Compressor Section)

The heat pump, water piping, pump, and hot water tank should be located where the ambient temperature does not fall below 50°F [10°C]. Keep water piping lengths at a minimum. DO NOT use a one way length greater than 50 ft. [15 m].

All installations must be in accordance with local codes. The installer is responsible for knowing the local requirements, and for performing the installation accordingly. DO NOT connect the pump wiring until “Initial Start-Up” section, below. Powering the pump before all installation steps are completed will damage the pump.

Water Tank Preparation

1.Turn off power or fuel supply to the hot water tank.

2.Connect a hose to the drain valve on the water tank.

3.Shut off the cold water supply to the water tank.

4.Open the drain valve and open the pressure relief valve or a hot water faucet to drain tank.

5.When using an existing tank, it should be flushed with cold water after it is drained until the water leaving the drain hose is clear and free of sediment.

6.Close all valves and remove the drain hose.

7.Install HWG water piping.

HWG Water Piping

1.Using at least 5/8” [16mm] O.D. copper, route and install the water piping, valves and air vent as shown in Figures 15 to 18. The air vent MUST be at the high point of the

HWG water piping.

2.Insulate all HWG water piping with no less than 3/8” [10mm] wall closed cell insulation.

3.Open both shut off valves and make sure the tank drain valve is closed.

R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A

R e v. : 5 J u n e , 2 0 0 8

Water Tank Refill

1.Open the cold water supply to the tank.

2.Open a hot water faucet to vent air from the system until water flows from the faucet; turn off faucet.

3.Depress the hot water tank pressure relief valve handle to ensure that there is no air remaining in the tank.

4.Inspect all work for leaks.

5.Before restoring power or fuel supply to the water heater, adjust the temperature setting on the tank thermostat(s) to insure maximum utilization of the heat available from the refrigeration system and conserve the most energy. On tanks with both upper and lower elements and thermostats, the lower element should be turned down to 100°F [38°C] or the lowest setting; the upper element should be adjusted to 120-130°F [49-54°C]. Depending upon the specific needs of the customer, you may want to adjust the upper element differently. On tanks with a single thermostat, a preheat tank should be used (figure 16).

6.Replace access cover(s) and restore power or fuel supply.

Initial Start-Up

1.Make sure all valves in the HWG water circuit are fully open.

2.Turn on the heat pump and allow it to run for 10-15 minutes.

3.Turn the heat pump and heat pump power supply “OFF” and CONNECT POWER TO THE HWG PUMP as shown in the unit wiring diagram. Connect the pump power lead as instructed on the tag attached to the pump wiring.

4.The HWG pump should not run if the compressor is not running.

5.The temperature difference between the water entering and leaving the HWG coil should be approximately 5-10°F [3-6°C].

6.Allow the unit to operate for 20 to 30 minutes to insure that it is functioning properly.

w w w. h e a t c o n t o l l e r. c o m

23

Image 23
Contents Split Products This page left intentionally blank Model Nomenclature for Indoor Split Series Safety SafetyGeneral Information GeoMax 2 HTS Air Handler Matches for ARI Ratings Equipment SelectionGeneral Indoor Coil Selection HTS GeoMaxIndoor Coil Selection For HSS R-22 Units CFMAir Handler Selection Example Indoor Compressor Section Location InstallationRemoving Existing Condensing Unit Where Applicable Air Handler InstallationHTS/HSS Installation GROUND-LOOP Heat Pump Applications Piping InstallationAntifreeze Low Water Temperature Cutout Setting CXM ControlGround-Loop Heat Pump Applications Flushing the Earth LoopCompressor section must be sealed to prevent entry Approximate Fluid Volume U.S. gal. L per 100 of PipeFluid Volume gal liters per 100’ 30 meters Pipe Antifreeze Percentages by VolumeFlow Regulation Water Quality StandardsExpansion Tank and Pump Water Control ValveWater Well Connections Water Coil Low Temperature Limit SettingErosion and Clogging Water Quality StandardsLineset Diameters and Charge Information Refrigeration InstallationLine Set Installation Evacuation and Charging the Unit Add-On Heat Pump ApplicationsRefrigeration Installation Charging The System Evacuation Of The Lineset And CoilDetermining Sub-Cooling Checking Superheat and Subcooling Determining SuperheatExample R-22 refrigerant Hot Water Generator Typical HWG Installation Indoor Compressor SectionInitial Start-Up Water Tank PreparationHWG Water Piping Water Tank RefillHot Water Generator Module Refrigeration Installation HSS Series Electrical Data Electrical Line VoltageGeoMax 2 HTS Series Electrical Data Electrical Power Wiring Thermostat Connections Electrical HWG WiringHWG Wiring Indoor Compressor Section Low Water Temperature Cutout SelectionTaco Valve Electrical Low Voltage WiringAccessory Connections Two-stage HTS UnitsTwo-Stage HTS Piping Thermostat InstallationCXM Controls Diagnostic Features Safety Features CXM ControlWater coil low temperature FP1 The FP1 thermistor Air coil low temperature FP2 The FP2 thermistor temperaturePage Y1, Y2, O Stage 2 cooling CXM Control Start-up OperationVariable Speed PSC Air Handler CXM Thermostat Details Nominal resistance at various temperaturesUnit Operation Unit Starting and Operating ConditionsOperating Limits Starting ConditionsUnit and System Checkout Before Powering SYSTEM, please check the followingUnit Start-up Procedure Test Mode Pins Unit Start-Up ProcedureR-22 HSS Compressor Section Coax Water Pressure Drop Water Temperature Change Through Heat ExchangerUnit Operating Conditions GPM 22 HSS Typical Unit Operating Pressures and Temperatures Preventive Maintenance Troubleshooting CXM Process Flow Chart Functional Troubleshooting Functional Troubleshooting Performance Troubleshooting Troubleshooting Form S i d e n t i a l S p l i t 6 0 H z R 2 2 & R 4 1 0 a 08/08