Heat Controller HTS SERIES SPLIT SYSTEM, HSS manual Air Handler Selection Example

Page 8

H E AT C O N T R O L L E R , I N C . WAT E R - S O U R C E H E AT P U M P S

R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A

R e v. : 5 J u n e , 2 0 0 8

Equipment Selection

Air Handler Selection Example

Figure 1 shows a typical performance table for a heat pump air handler. Suppose the evaporator temperature required is 50ºF, the capacity required is 35,000 Btuh and the airflow required is 1,200 CFM. Each evaporator temperature listed in the table shows three wet bulb temperatures. As recommended in the table notes above, select the 67ºF WB column. At 1,200 CFM, the model 003 capacity is 36 MBtuh, which is higher than the minimum capacity required of 35,000 Btuh. In this example, model 003 would be the appropriate match.

Figure 1: Selecting Air Handler

Utilizing the Existing Air Handler or Coil (R22 units only) It is recommended that a new coil or air handler be installed with any geothermal split system compressor section due to the low initial cost of the additional equipment versus the reliability and benefit of new technology, increased reliability and warranty. However, if the existing air handler must be used (R22 systems only), the following conditions apply:

If the existing coil currently uses an orifice, the orifice must be removed and replaced with a TXV. If the coil utilizes capillary tubes, it will not operate properly with the geothermal split system and should be replaced.

If life expectancy of indoor coil (and associated components - fan, cabinet, etc.) is less than 7-10 years, indoor section should be replaced.

8

H e a t C o n t r o l l e r, I n c . Wa t e r - S o u r c e H e a t i n g a n d C o o l i n g S y s t e m s

Image 8
Contents Split Products This page left intentionally blank Model Nomenclature for Indoor Split Series Safety SafetyGeneral Information Equipment Selection GeneralIndoor Coil Selection HTS GeoMax GeoMax 2 HTS Air Handler Matches for ARI RatingsCFM Indoor Coil Selection For HSS R-22 UnitsAir Handler Selection Example Installation Removing Existing Condensing Unit Where ApplicableAir Handler Installation Indoor Compressor Section LocationHTS/HSS Installation Piping Installation GROUND-LOOP Heat Pump ApplicationsLow Water Temperature Cutout Setting CXM Control Ground-Loop Heat Pump ApplicationsFlushing the Earth Loop AntifreezeApproximate Fluid Volume U.S. gal. L per 100 of Pipe Fluid Volume gal liters per 100’ 30 meters PipeAntifreeze Percentages by Volume Compressor section must be sealed to prevent entryWater Quality Standards Expansion Tank and PumpWater Control Valve Flow RegulationWater Coil Low Temperature Limit Setting Water Well ConnectionsWater Quality Standards Erosion and CloggingLineset Diameters and Charge Information Refrigeration InstallationLine Set Installation Add-On Heat Pump Applications Evacuation and Charging the UnitRefrigeration Installation Evacuation Of The Lineset And Coil Charging The SystemDetermining Sub-Cooling Checking Superheat and Subcooling Determining SuperheatExample R-22 refrigerant Typical HWG Installation Indoor Compressor Section Hot Water GeneratorWater Tank Preparation HWG Water PipingWater Tank Refill Initial Start-UpHot Water Generator Module Refrigeration Installation HSS Series Electrical Data Electrical Line VoltageGeoMax 2 HTS Series Electrical Data Electrical Power Wiring Electrical HWG Wiring HWG Wiring Indoor Compressor SectionLow Water Temperature Cutout Selection Thermostat ConnectionsElectrical Low Voltage Wiring Accessory ConnectionsTwo-stage HTS Units Taco ValveThermostat Installation Two-Stage HTS PipingCXM Controls Safety Features CXM Control Water coil low temperature FP1 The FP1 thermistorAir coil low temperature FP2 The FP2 thermistor temperature Diagnostic FeaturesPage Y1, Y2, O Stage 2 cooling CXM Control Start-up OperationVariable Speed PSC Air Handler Nominal resistance at various temperatures CXM Thermostat DetailsUnit Starting and Operating Conditions Operating LimitsStarting Conditions Unit OperationUnit and System Checkout Before Powering SYSTEM, please check the followingUnit Start-up Procedure Unit Start-Up Procedure Test Mode PinsR-22 HSS Compressor Section Coax Water Pressure Drop Water Temperature Change Through Heat ExchangerUnit Operating Conditions GPM 22 HSS Typical Unit Operating Pressures and Temperatures Preventive Maintenance Troubleshooting CXM Process Flow Chart Functional Troubleshooting Functional Troubleshooting Performance Troubleshooting Troubleshooting Form S i d e n t i a l S p l i t 6 0 H z R 2 2 & R 4 1 0 a 08/08