Heat Controller HSS, HTS SERIES SPLIT SYSTEM manual Preventive Maintenance

Page 41

T h e Q u a l i t y L e a d e r i n C o n d i t i o n i n g A i r

Preventive Maintenance

Water Coil Maintenance

(Direct ground water applications only)

If the system is installed in an area with a known high mineral content (125 P.P.M. or greater) in the water, it is best to establish a periodic maintenance schedule with the owner so the coil can be checked regularly. Consult the well water applications section of this manual for a more detailed water coil material selection. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling. Therefore, 1.5 gpm per ton [2.0 l/m per kW] is recommended as a minimum flow. Minimum flow rate for entering water temperatures below 50°F [10°C] is 2.0 gpm per ton [2.6 l/m per kW].

Water Coil Maintenance

(All other water loop applications)

Generally water coil maintenance is not needed for closed loop systems. However, if the piping is known to have high dirt or debris content, it is best to establish a periodic maintenance schedule with the owner so the water coil can be checked regularly. Dirty installations are typically the result of deterioration of iron or galvanized piping or components in the system. Open cooling towers requiring heavy chemical treatment and mineral buildup through water use can also contribute to higher maintenance. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with both the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling. However, flow rates over 3 gpm per ton (3.9 l/m per kW) can produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks.

Hot Water Generator Coils

See water coil maintenance for ground water units. If the potable water is hard or not chemically softened, the high temperatures of the desuperheater will tend to scale even quicker than the water coil and may need more frequent inspections. In areas with extremely hard water, a HWG is not recommended.

Filters

Filters must be clean to obtain maximum performance. Filters should be inspected every month under normal operating conditions and be replaced when necessary. Units should never be operated without a filter.

Washable, high efficiency, electrostatic filters, when dirty, can exhibit a very high pressure drop for the fan motor and reduce air flow, resulting in poor performance. It is especially important to provide consistent washing of these filters (in the opposite direction of the normal air flow) once per month using a high pressure wash similar to those found at self- serve car washes.

R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A

R e v. : 5 J u n e , 2 0 0 8

Condensate Drain

In areas where airborne bacteria may produce a “slimy” substance in the drain pan, it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem. The condensate pan may also need to be cleaned periodically to insure indoor air quality. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect the drain twice a year to avoid the possibility of plugging and eventual overflow.

Compressor

Conduct annual amperage checks to insure that amp draw is no more than 10% greater than indicated on the serial plate data.

Fan Motors

Consult air handler I.O.M. for maintenance requirements.

Air Coil

The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum fins while cleaning. CAUTION: Fin edges are sharp.

Cabinet - “Indoor” Compressor Section

Do not allow water to stay in contact with the cabinet for long periods of time to prevent corrosion of the cabinet sheet metal. Generally, cabinets are set up from the floor a few inches [7 - 8 cm] to prevent water from entering the cabinet. The cabinet can be cleaned using a mild detergent.

Refrigerant System

To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Reference the operating charts for pressures and temperatures. Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit.

w w w. h e a t c o n t o l l e r. c o m

41

Image 41
Contents Split Products This page left intentionally blank Model Nomenclature for Indoor Split Series Safety SafetyGeneral Information General Equipment SelectionIndoor Coil Selection HTS GeoMax GeoMax 2 HTS Air Handler Matches for ARI RatingsIndoor Coil Selection For HSS R-22 Units CFMAir Handler Selection Example Removing Existing Condensing Unit Where Applicable InstallationAir Handler Installation Indoor Compressor Section LocationHTS/HSS Installation GROUND-LOOP Heat Pump Applications Piping InstallationGround-Loop Heat Pump Applications Low Water Temperature Cutout Setting CXM ControlFlushing the Earth Loop AntifreezeFluid Volume gal liters per 100’ 30 meters Pipe Approximate Fluid Volume U.S. gal. L per 100 of PipeAntifreeze Percentages by Volume Compressor section must be sealed to prevent entryExpansion Tank and Pump Water Quality StandardsWater Control Valve Flow RegulationWater Well Connections Water Coil Low Temperature Limit SettingErosion and Clogging Water Quality StandardsLineset Diameters and Charge Information Refrigeration InstallationLine Set Installation Evacuation and Charging the Unit Add-On Heat Pump ApplicationsRefrigeration Installation Charging The System Evacuation Of The Lineset And CoilDetermining Sub-Cooling Checking Superheat and Subcooling Determining SuperheatExample R-22 refrigerant Hot Water Generator Typical HWG Installation Indoor Compressor SectionHWG Water Piping Water Tank PreparationWater Tank Refill Initial Start-UpHot Water Generator Module Refrigeration Installation HSS Series Electrical Data Electrical Line VoltageGeoMax 2 HTS Series Electrical Data Electrical Power Wiring HWG Wiring Indoor Compressor Section Electrical HWG WiringLow Water Temperature Cutout Selection Thermostat ConnectionsAccessory Connections Electrical Low Voltage WiringTwo-stage HTS Units Taco ValveTwo-Stage HTS Piping Thermostat InstallationCXM Controls Water coil low temperature FP1 The FP1 thermistor Safety Features CXM ControlAir coil low temperature FP2 The FP2 thermistor temperature Diagnostic FeaturesPage Y1, Y2, O Stage 2 cooling CXM Control Start-up OperationVariable Speed PSC Air Handler CXM Thermostat Details Nominal resistance at various temperaturesOperating Limits Unit Starting and Operating ConditionsStarting Conditions Unit OperationUnit and System Checkout Before Powering SYSTEM, please check the followingUnit Start-up Procedure Test Mode Pins Unit Start-Up ProcedureR-22 HSS Compressor Section Coax Water Pressure Drop Water Temperature Change Through Heat ExchangerUnit Operating Conditions GPM 22 HSS Typical Unit Operating Pressures and Temperatures Preventive Maintenance Troubleshooting CXM Process Flow Chart Functional Troubleshooting Functional Troubleshooting Performance Troubleshooting Troubleshooting Form S i d e n t i a l S p l i t 6 0 H z R 2 2 & R 4 1 0 a 08/08