Heat Controller HSS, HTS SERIES SPLIT SYSTEM manual Unit Start-Up Procedure, Test Mode Pins

Page 37

T h e Q u a l i t y L e a d e r i n C o n d i t i o n i n g A i r

Unit Start-Up Procedure

flow rate is correct by measuring pressure drop through the heat exchanger using the P/T plugs and comparing to Tables 12a through 12b.

d.Check the elevation and cleanliness of the condensate lines. Dripping may be a sign of a blocked line. Check that the condensate trap is filled to provide a water seal.

e.Refer to Table 13. Check the temperature of both entering and leaving water. If temperature is within range, proceed with the test. If temperature is outside of the operating range, check refrigerant pressures and compare to Tables 14 and 15. Verify correct water flow by comparing unit pressure drop across the heat exchanger versus the data in Tables 12a through 12b. Heat of rejection (HR) can be calculated and compared to catalog data capacity pages. The formula for HR for systems with water is as follows:

HR = TD x GPM x 500, where TD is the temperature difference between the entering and leaving water, and GPM is the flow rate in U.S. GPM, determined by comparing the pressure drop across the heat exchanger to Tables 12a through 12b.

f.Check air temperature drop across the air coil when compressor is operating. Air temperature drop should be between 15°F and 25°F [8°C and 14°C].

g.Turn thermostat to “OFF” position. A hissing noise indicates proper functioning of the reversing valve.

6.Allow five (5) minutes between tests for pressure to equalize before beginning heating test.

a.Adjust the thermostat to the lowest setting. Place the thermostat mode switch in the “HEAT” position.

b.Slowly raise the thermostat to a higher temperature until the compressor activates.

c.Check for warm air delivery within a few minutes after the unit has begun to operate.

d.Refer to Table 13. Check the temperature of both entering and leaving water. If temperature is within range, proceed with the test. If temperature is outside of the operating range, check refrigerant pressures and compare to Tables 14 and 15 Verify correct water flow by comparing unit pressure drop across the heat exchanger versus the data in Tables 12a through

12b. Heat of extraction (HE) can be calculated and compared to submittal data capacity pages. The formula for HE for systems with water is as follows:

HE = TD x GPM x 500, where TD is the temperature difference between the entering and leaving water, and GPM is the flow rate in U.S. GPM, determined by comparing the pressure drop across the heat exchanger to Tables 12a through 12b.

e.Check air temperature rise across the air coil when compressor is operating. Air temperature rise should be between 20°F and 30°F [11°C and 17°C].

f.Check for vibration, noise, and water leaks.

7.If unit fails to operate, perform troubleshooting analysis

R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A

R e v. : 5 J u n e , 2 0 0 8

(see troubleshooting section). If the check described fails to reveal the problem and the unit still does not operate, contact a trained service technician to insure proper diagnosis and repair of the equipment.

8.When testing is complete, set system to maintain desired comfort level.

9.BE CERTAIN TO FILL OUT AND RETURN ALL WARRANTY REGISTRATION PAPERWORK.

Note: If performance during any mode appears abnormal, refer to the CXM section or troubleshooting section of this manual. To obtain maximum performance, the air coil should be cleaned before start-up. A 10% solution of dishwasher detergent and water is recommended.

x WARNING! x

WARNING! When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with energized equipment.

x CAUTION! x

CAUTION! Verify that ALL water control valves are open and allow water flow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.

Figure 29: Test Mode Pins

Short test pins together to enter Test Mode and speed-up timing and delays for 20 minutes.

w w w. h e a t c o n t o l l e r. c o m

37

Image 37
Contents Split Products This page left intentionally blank Model Nomenclature for Indoor Split Series Safety SafetyGeneral Information General Equipment SelectionIndoor Coil Selection HTS GeoMax GeoMax 2 HTS Air Handler Matches for ARI RatingsIndoor Coil Selection For HSS R-22 Units CFMAir Handler Selection Example Removing Existing Condensing Unit Where Applicable InstallationAir Handler Installation Indoor Compressor Section LocationHTS/HSS Installation GROUND-LOOP Heat Pump Applications Piping InstallationGround-Loop Heat Pump Applications Low Water Temperature Cutout Setting CXM ControlFlushing the Earth Loop AntifreezeFluid Volume gal liters per 100’ 30 meters Pipe Approximate Fluid Volume U.S. gal. L per 100 of PipeAntifreeze Percentages by Volume Compressor section must be sealed to prevent entryExpansion Tank and Pump Water Quality StandardsWater Control Valve Flow RegulationWater Well Connections Water Coil Low Temperature Limit SettingErosion and Clogging Water Quality StandardsLine Set Installation Refrigeration InstallationLineset Diameters and Charge Information Evacuation and Charging the Unit Add-On Heat Pump ApplicationsRefrigeration Installation Charging The System Evacuation Of The Lineset And CoilExample R-22 refrigerant Checking Superheat and Subcooling Determining SuperheatDetermining Sub-Cooling Hot Water Generator Typical HWG Installation Indoor Compressor SectionHWG Water Piping Water Tank PreparationWater Tank Refill Initial Start-UpHot Water Generator Module Refrigeration Installation GeoMax 2 HTS Series Electrical Data Electrical Line VoltageHSS Series Electrical Data Electrical Power Wiring HWG Wiring Indoor Compressor Section Electrical HWG WiringLow Water Temperature Cutout Selection Thermostat ConnectionsAccessory Connections Electrical Low Voltage WiringTwo-stage HTS Units Taco ValveTwo-Stage HTS Piping Thermostat InstallationCXM Controls Water coil low temperature FP1 The FP1 thermistor Safety Features CXM ControlAir coil low temperature FP2 The FP2 thermistor temperature Diagnostic FeaturesPage Variable Speed PSC Air Handler CXM Control Start-up OperationY1, Y2, O Stage 2 cooling CXM Thermostat Details Nominal resistance at various temperaturesOperating Limits Unit Starting and Operating ConditionsStarting Conditions Unit OperationUnit Start-up Procedure Before Powering SYSTEM, please check the followingUnit and System Checkout Test Mode Pins Unit Start-Up ProcedureUnit Operating Conditions Water Temperature Change Through Heat ExchangerR-22 HSS Compressor Section Coax Water Pressure Drop GPM 22 HSS Typical Unit Operating Pressures and Temperatures Preventive Maintenance Troubleshooting CXM Process Flow Chart Functional Troubleshooting Functional Troubleshooting Performance Troubleshooting Troubleshooting Form S i d e n t i a l S p l i t 6 0 H z R 2 2 & R 4 1 0 a 08/08