Heat Controller HTS SERIES SPLIT SYSTEM HSS Typical Unit Operating Pressures and Temperatures

Page 40

H E AT C O N T R O L L E R , I N C . WAT E R - S O U R C E H E AT P U M P S

R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A

R e v. : 5 J u n e , 2 0 0 8

Unit Operating Conditions

Table 14d: Size 060 HTS Two-Stage R-410A Typical Unit Operating Pressures and Temperatures

Entering

Water

 

Full Load Cooling - without HWG active

 

 

Full Load Heating - without HWG active

 

Flow

 

 

 

 

 

 

 

 

 

 

 

 

Water

Suction

Discharge

Super-

Sub-

Water Temp

Air Temp

Suction

Discharge

Super-

Sub-

Water Temp

Air Temp

GPM/

Temp °F

Pressure

Pressure

Drop °F

Pressure

Pressure

Rise °F

ton

heat

cooling

Rise °F

heat

cooling

Drop °F

 

PSIG

PSIG

 

 

 

DB

PSIG

PSIG

 

 

 

DB

 

1.5

117-127

160-180

16-21

8-13

17.5-19.5

16-22

66-76

282-302

9-15

8-13

8-10

21-27

30

2.25

116-126

133-153

17-22

6-11

11.9-13.9

16-22

69-79

285-305

9-15

8-13

6-8

21-27

 

3

115-125

125-145

18-23

5-10

6.3-8.3

16-22

72-82

289-309

9-15

9-14

4-6

22-28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

126-136

228-248

8-13

8-13

19.8-21.8

20-26

95-105

318-338

9-15

12-17

11.3-13.3

27-33

50

2.25

124-134

212-232

11-16

6-11

14.2-16.2

20-26

100-110

321-341

9-15

12-17

8.5-10.5

28-34

 

3

123-133

195-215

14-19

5-10

8.5-10.5

20-26

105-115

324-344

9-15

12-17

5.7-7.7

30-36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

130-140

305-325

8-13

10-15

20.3-22.3

21-27

128-138

360-380

8-14

12-17

14-16

33-38

70

2.25

129-139

286-306

9-14

9-14

14.8-16.8

21-27

133-143

364-384

8-14

12-17

10.6-12.6

34-40

 

3

128-138

266-286

11-16

7-12

9.3-11.3

21-27

139-149

368-388

8-14

12-17

7.3-9.3

35-41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

133-143

398-418

8-13

10-15

19.4-21.4

20-26

173-183

407-427

8-14

13-18

18.2-20.2

42-50

90

2.25

132-142

376-396

8-13

9-14

14.1-16.1

20-26

177-187

411-431

8-14

13-18

13.9-15.9

43-51

 

3

132-142

354-374

8-13

7-12

8.8-10.8

20-26

182-192

415-435

8-14

14-19

9.6-11.6

44-52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

138-148

505-525

6-11

10-15

18.3-20.3

19-25

 

 

 

 

 

 

110

2.25

137-147

483-503

6-11

9-14

13.3-15.3

19-25

 

Operation Not Recommended

 

 

3

136-146

459-479

6-11

8-13

8.3-10.3

19-25

 

 

 

 

 

 

Table 15: R-22 HSS Typical Unit Operating Pressures and Temperatures

Entering

Water

 

Full Load Cooling - without HWG active

 

 

Full Load Heating - without HWG active

 

Flow

 

 

 

 

 

 

 

 

 

 

 

 

Water

Suction

Discharge

Super-

Sub-

Water Temp

Air Temp

Suction

Discharge

Super-

Sub-

Water Temp

Air Temp

GPM/

Temp °F

Pressure

Pressure

cooling

Drop °F

Pressure

Pressure

cooling

Rise °F

ton

heat

Rise *** °F

heat

Drop *** °F

 

PSIG

PSIG

 

****

 

DB

PSIG

PSIG

 

****

 

DB

 

1.5

61-70

100-117

12-18

12-22

21-24

21-26

34-39

163-183

5-10

5-9

7.6-8.4

14-20

30

2.3

62-71

92-109

12-18

12-22

13-16

21-26

37-42

165-185

5-10

5-9

4.8-5.6

16-22

 

3

62-71

88-104

12-18

12-22

6-11

21-26

38-44

167-186

5-10

5-9

3.4-4.2

16-22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

79-85

145-170

10-15

9-16

20-23

20-25

51-58

175-202

9-12

8-12

10.8-11.9

23-29

50

2.3

75-83

130-155

10-15

9-16

12-15

20-25

53-62

178-206

9-12

8-12

6.7-8.1

24-30

 

3

72-82

125-150

10-15

9-16

8-12

20-25

55-65

180-208

9-12

8-12

5.1-5.9

25-31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

78-88

180-200

8-12

7-12

19-22

19-24

71-82

215-250

10-14

6-10

14.0-15.2

28-34

70

2.3

78-90

169-187

8-12

7-12

11-14

19-24

77-89

203-235

10-14

6-10

9.0-10.2

30-37

 

3

78-91

160-180

8-12

7-12

7-12

19-24

81-92

200-235

10-14

6-10

6.7-7.9

31-38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

79-82

230-272

8-10

7-11

18-21

17-23

 

 

 

 

 

 

90

2.3

80-93

215-248

8-10

7-11

10-14

17-23

 

Operation Not Recommended

 

 

3

80-93

208-240

8-10

7-11

6-11

17-23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Based on Nominal 400 CFM per ton per circuit ariflow and 70°F EAT heating and 80/67°F cooling.

** Cooling air and water numbers can vary greatly with changes in humidity.

*** Water temperature difference based upon 1.5 - 3 GPM per ton of active circuit water flow.

**** Using liquid line pressure.

40

H e a t C o n t r o l l e r, I n c . Wa t e r - S o u r c e H e a t i n g a n d C o o l i n g S y s t e m s

Image 40
Contents Split Products This page left intentionally blank Model Nomenclature for Indoor Split Series Safety SafetyGeneral Information Equipment Selection GeneralIndoor Coil Selection HTS GeoMax GeoMax 2 HTS Air Handler Matches for ARI RatingsCFM Indoor Coil Selection For HSS R-22 UnitsAir Handler Selection Example Installation Removing Existing Condensing Unit Where ApplicableAir Handler Installation Indoor Compressor Section LocationHTS/HSS Installation Piping Installation GROUND-LOOP Heat Pump ApplicationsLow Water Temperature Cutout Setting CXM Control Ground-Loop Heat Pump ApplicationsFlushing the Earth Loop AntifreezeApproximate Fluid Volume U.S. gal. L per 100 of Pipe Fluid Volume gal liters per 100’ 30 meters PipeAntifreeze Percentages by Volume Compressor section must be sealed to prevent entryWater Quality Standards Expansion Tank and PumpWater Control Valve Flow RegulationWater Coil Low Temperature Limit Setting Water Well ConnectionsWater Quality Standards Erosion and CloggingLine Set Installation Refrigeration InstallationLineset Diameters and Charge Information Add-On Heat Pump Applications Evacuation and Charging the UnitRefrigeration Installation Evacuation Of The Lineset And Coil Charging The SystemExample R-22 refrigerant Checking Superheat and Subcooling Determining SuperheatDetermining Sub-Cooling Typical HWG Installation Indoor Compressor Section Hot Water GeneratorWater Tank Preparation HWG Water PipingWater Tank Refill Initial Start-UpHot Water Generator Module Refrigeration Installation GeoMax 2 HTS Series Electrical Data Electrical Line VoltageHSS Series Electrical Data Electrical Power Wiring Electrical HWG Wiring HWG Wiring Indoor Compressor SectionLow Water Temperature Cutout Selection Thermostat ConnectionsElectrical Low Voltage Wiring Accessory ConnectionsTwo-stage HTS Units Taco ValveThermostat Installation Two-Stage HTS PipingCXM Controls Safety Features CXM Control Water coil low temperature FP1 The FP1 thermistorAir coil low temperature FP2 The FP2 thermistor temperature Diagnostic FeaturesPage Variable Speed PSC Air Handler CXM Control Start-up OperationY1, Y2, O Stage 2 cooling Nominal resistance at various temperatures CXM Thermostat DetailsUnit Starting and Operating Conditions Operating LimitsStarting Conditions Unit OperationUnit Start-up Procedure Before Powering SYSTEM, please check the followingUnit and System Checkout Unit Start-Up Procedure Test Mode PinsUnit Operating Conditions Water Temperature Change Through Heat ExchangerR-22 HSS Compressor Section Coax Water Pressure Drop GPM 22 HSS Typical Unit Operating Pressures and Temperatures Preventive Maintenance Troubleshooting CXM Process Flow Chart Functional Troubleshooting Functional Troubleshooting Performance Troubleshooting Troubleshooting Form S i d e n t i a l S p l i t 6 0 H z R 2 2 & R 4 1 0 a 08/08