Emerson AC4 Connecting Digital Inputs and Outputs, Connecting Liebert Precision Cooling Units

Page 19

Wiring and Connections

3.2Connecting Digital Inputs and Outputs

The digital inputs and outputs are on the lower right side of the Liebert AC4 printed wiring assembly board. This section describes how to connect devices to the Liebert AC4’s inputs and outputs.

Each input is tied to an output with the same number:

Input 1 is tied to Output 1 (default name: Device_1)

Input 2 is tied to Output 2 (default name: Device_2)

Input 3 is tied to Output 3 (default name: Device_3)

Input 4 is tied to Output 4 (default name: Device_4)

Up to four devices may be connected to the Liebert AC4. Each device must be connected to an input and an output with the same number.

To determine the proper wire size, see Table 4 Wiring specifications.

NOTE

Each terminal block is a removable assembly to permit easier connection of more than one input or output at a time. If making multiple connections, grasp the upper portion of a block and pull firmly until the assembly pulls apart.

After making the connections, push the removed piece back into the portion attached to the printed wiring assembly until the terminal block pieces lock together.

Connecting Liebert Precision Cooling Units

For Liebert Precision Cooling units, follow these steps (be sure to connect the same device to inputs and outputs with the same number (Input 1 and Output 1, Input 2 and Output 2, and so on):

Connect a digital input from the Liebert AC4 to the Common Alarm Relay of the environmental unit: terminals 75/76 or TB1-6,TB1-7.

Connect a digital output (numbered the same as the input) from the Liebert AC4 to the Remote Shutdown (Power Control) of the environmental unit: terminal 37/38 or TB1-4, TB1-5.

3.2.1Connecting Digital Inputs

The four digital inputs are on the lower right side of the Liebert AC4, just below the output terminal blocks, as shown at right. These inputs are numbered 1 through 4.

To connect an input:

1.Turn Off electrical power to the Liebert AC4.

2.If necessary, remove a conduit knockout to permit wire entry into the Liebert AC4 enclosure.

3.Bring the wire(s) into the Liebert AC4 enclosure through a conduit knockout or access slot.

4.Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.

5.Tighten the screw until it holds the wire snugly.

OUTPUT TERMINAL BLOCKS

Note numbering keys to right of terminal blocks; outputs are numbered from bottom (1) to top (4)

Numbering keys

INPUT TERMINAL

BLOCKS

Note numbering keys

to right of terminal

blocks; inputs are numbered from bottom (1) to top (4)

13

Liebert® AC4

Image 19
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Introduction Methods of Viewing and Configuring the Liebert AC4Available Alarms Data LogsOutside Enclosure Overview LCD for configurationOperation Device Liebert Challenger Typical ConfigurationDevice RS232 LiebertLiebert HimodHimod Controller board components Controller Board Overview24VAC power ConnectorDIP switch LCD connectorLED indicators summary LED IndicatorsOutput LEDs Status LEDs Input LEDs Typical Sequence Unpacking and Preliminary Inspection Installation ConsiderationsInstallation Packing ContentsRequired tools Surface-Mounting the Liebert AC4Mounting the Panel Flush-Mounting the Liebert AC4 Electrical connections to panel Connect Power to the Liebert AC4Wiring and Connections Wiring SpecificationsWiring specifications Numbering keys Connecting Digital Inputs and OutputsConnecting Liebert Precision Cooling Units Connecting Digital InputsSetting the Digital Output Jumpers Connecting Digital OutputsDigital output jumper settings Serial interface connector RS232/EIA5 Connecting Common Alarm OutputsRS232 Connector Common alarm outputsGuide to Liebert AC4 functions Overview of MenusMain Menu Overview Opening Screen OverviewLCD Menu Overview View Status Options Active Alarms View Active AlarmsActive Alarms Clearing Active AlarmsAlarm Log View Alarm LogAlarm Log Alarm log conditionsEvent Log View Event LogEvent Log Event log conditionsDigital input states View Input StatusInput Status Viewing Additional Input DataDigital output states View Output StatusOutput Status Viewing Additional Output DataSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Valid characters for data entry LoginLogin System and Control OptionsClear Alarms/Logs menu Login ScreenSystem & Control menu Clear Alarms&Logs selected Setup System menuSetup System Setup Inputs Setup System OverviewChange Label Name of Input Define Input as Alarmable or EventDefine Input as Normally Open or Normally Closed Latched / Unlatched Set Up Alarmable Inputs in Latched or Unlatched ModeSet Up Delay Time Delay TimeChange to Reset Y or Not Reset N Setup System Setup Common AlarmReset Common Alarm Message if too many devices entered Setup System Setup ZonesSet Up a Zone Message if too few devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsSet Mode Define Operating or Standby ModeEnable or Disable an Output Device in Alarm Status Configure Output for Loss of Power Fail-SafeReset Password to the Factory Default Aaaa Setup System Setup System InfoChange Password Change the PasswordSet Date & Time Setup Site IDSetup Site ID Set Date & Time/Automatic Daylight Saving TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only Perform Firmware UPDATE-YESY or NON? N Default settings operation features Setup OperationSelect Setup Operation Setup Operation MenuSet Start Time Hour Interval Turn Automatic Sequencing On or OffActivate / Deactivate Set Interval & Start Time 1- to 99-Day IntervalFailed Standby response Turn Standby Testing On or OffChange Standby Testing Specify Failed Standby ResponseSetup Operation Menu Specify Hold Delay TimeHold Delay Time Restart Delay TimeOverride Output Clear the Event Log Clear Alarms & LogsClear Active Alarms Clear the Alarm LogSpecifications Liebert AC4 SpecificationsSpecifications Liebert AC4 Comparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface Create a Connection COM1 Port SetupSpecify COM Port Connection Ascii Setup button Properties SetupAscii Setup Settings tabClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceMain Menu For sample screens, see Silence Alarm and Backup Log FilesSetup Menu Overview View Status OverviewMain Menu View Active AlarmsView Active Alarms View Status MenusView Alarm Log View Alarm LogView Input Status View Event LogView Input Status View Event LogView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBack Up Event Log File Back Up Alarm Log FileBackup Log Files Alarm Log File Backup Log Files Event Log FileLogin Menu Setup MenuLogin See Description Setup MenuSetup Menu Tips on Using the Service Terminal InterfaceSetup Inputs Setup InputsSetup Zones Setup Common AlarmSetup Zones Setup Common AlarmSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlySetup Operation Auto Sequencing Setup OperationAuto Sequencing Setup Operation Standby Testing Standby TestingFailed Standby Hold DelaySetup Operation Failed Standby Setup Operation Hold DelayOverride Output Restart DelaySetup Operation Restart Delay Override OutputClear Alarms & Logs Clear Active Alarms Clear Alarms & LogsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Care Ne tIs t Twor k