System and Control Options

7.8Setup Operation

The Liebert AC4 operation features allow you to set up a rotation sequence to alternate which devices are operating and which are placed on Standby, as well as test devices while in Standby mode and specify what to do when a Standby device goes into alarm as it is powered up. You may also specify delay times after an output changes state, directing the Liebert AC4 to wait before acknowledging inputs or turning an output on or off.

To change any operation features:

Log In and Choose Setup System

From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter (see 7.1 Login for help).

Enter your password at the Login screen.

From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter .

Select Setup Operation

From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Operation and press Enter .

Setup System Menu

SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT =SELECT

SETUP OUTPUTS SETUP SYSTEM INFO

> SETUP OPERATION

Setup Operation Menu

>AUTO SEQUENCING OFF STANDBY TESTING OFF

FAILED STANDBY N ↑↓=NEXT =SELECT

HOLD DELAY

:

10:00

RESTART

:

00:06

• Use the steps following Table 18 to access any of the Setup Operation options.

Table 18 shows the default settings for operation options: automatic sequencing, standby testing, failed standby, hold delay and restart.

Table 18 Default settings - operation features

Feature

Default

Other Options

 

 

 

AUTO SEQUENCING

OFF (Deactivated)

ON (Activated), 12h (Activated for 12-hour intervals)

STANDBY TESTING

OFF (Deactivated)

ON (Activated)

FAILED STANDBY

N (Deactivated)

Y (Activated)

HOLD DELAY

10:00 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

RESTART

00:06 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

43

Liebert® AC4

Image 49
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Available Alarms Methods of Viewing and Configuring the Liebert AC4Data Logs IntroductionOutside Enclosure Overview LCD for configurationOperation Device Liebert Challenger Typical ConfigurationDevice RS232 LiebertLiebert HimodHimod Controller board components Controller Board OverviewDIP switch ConnectorLCD connector 24VAC powerLED indicators summary LED IndicatorsOutput LEDs Status LEDs Input LEDs Typical Sequence Installation Installation ConsiderationsPacking Contents Unpacking and Preliminary InspectionRequired tools Surface-Mounting the Liebert AC4Mounting the Panel Flush-Mounting the Liebert AC4 Electrical connections to panel Connect Power to the Liebert AC4Wiring and Connections Wiring SpecificationsWiring specifications Connecting Liebert Precision Cooling Units Connecting Digital Inputs and OutputsConnecting Digital Inputs Numbering keysSetting the Digital Output Jumpers Connecting Digital OutputsDigital output jumper settings RS232 Connector Connecting Common Alarm OutputsCommon alarm outputs Serial interface connector RS232/EIA5Guide to Liebert AC4 functions Overview of MenusMain Menu Overview Opening Screen OverviewLCD Menu Overview View Status Options Active Alarms View Active AlarmsClearing Active Alarms Active AlarmsAlarm Log View Alarm LogAlarm log conditions Alarm LogEvent Log View Event LogEvent log conditions Event LogInput Status View Input StatusViewing Additional Input Data Digital input statesOutput Status View Output StatusViewing Additional Output Data Digital output statesSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Login LoginSystem and Control Options Valid characters for data entrySystem & Control menu Clear Alarms&Logs selected Login ScreenSetup System menu Clear Alarms/Logs menuSetup System Setup Inputs Setup System OverviewChange Label Name of Input Define Input as Alarmable or EventDefine Input as Normally Open or Normally Closed Set Up Delay Time Set Up Alarmable Inputs in Latched or Unlatched ModeDelay Time Latched / UnlatchedChange to Reset Y or Not Reset N Setup System Setup Common AlarmReset Common Alarm Set Up a Zone Setup System Setup ZonesMessage if too few devices entered Message if too many devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsEnable or Disable an Output Device in Alarm Status Define Operating or Standby ModeConfigure Output for Loss of Power Fail-Safe Set ModeChange Password Setup System Setup System InfoChange the Password Reset Password to the Factory Default AaaaSetup Site ID Setup Site IDSet Date & Time/Automatic Daylight Saving Time Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only Perform Firmware UPDATE-YESY or NON? N Select Setup Operation Setup OperationSetup Operation Menu Default settings operation featuresActivate / Deactivate Turn Automatic Sequencing On or OffSet Interval & Start Time 1- to 99-Day Interval Set Start Time Hour IntervalChange Standby Testing Turn Standby Testing On or OffSpecify Failed Standby Response Failed Standby responseHold Delay Time Specify Hold Delay TimeRestart Delay Time Setup Operation MenuOverride Output Clear Active Alarms Clear Alarms & LogsClear the Alarm Log Clear the Event LogSpecifications Liebert AC4 SpecificationsSpecifications Liebert AC4 Comparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface Create a Connection COM1 Port SetupSpecify COM Port Connection Ascii Setup Properties SetupSettings tab Ascii Setup buttonClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceSetup Menu Overview Silence Alarm and Backup Log FilesView Status Overview Main Menu For sample screens, seeView Active Alarms View Active AlarmsView Status Menus Main MenuView Alarm Log View Alarm LogView Input Status View Event LogView Event Log View Input StatusView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBackup Log Files Alarm Log File Back Up Alarm Log FileBackup Log Files Event Log File Back Up Event Log FileLogin Menu Setup MenuLogin Setup Menu Setup MenuTips on Using the Service Terminal Interface See DescriptionSetup Inputs Setup InputsSetup Zones Setup Common AlarmSetup Common Alarm Setup ZonesSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlySetup Operation Auto Sequencing Setup OperationAuto Sequencing Setup Operation Standby Testing Standby TestingSetup Operation Failed Standby Hold DelaySetup Operation Hold Delay Failed StandbySetup Operation Restart Delay Restart DelayOverride Output Override OutputClear Alarms & Logs Clear Active Alarms Clear Alarms & LogsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Is t Ne tTwor k Care