Emerson AC4 user manual View Event Log, Event log conditions, Digital Input Digital Output Panel

Page 27

View Status Options

5.3View Event Log

In addition to alarms, the Liebert AC4 tracks other changes in the Event Log to assist users with verifying operational and troubleshooting problems. Events reflect changes in the status of an input that is defined as an event or the change of state of an output (i.e., manually forced ON or OFF). Other events may be informational, such as a user login. The Event Log contains up to 99 records of events, which are added as they occur.

To view the Event Log:

From the Main Menu, use the arrows ↑↓ to choose View Status, then press Enter ↵.

From the View Status Menu, use the arrows ↑↓ to choose View Event Log, then press Enter .

5.3.1Event Log

The Event Log screen displays up to 99 recent events. If the log contains any event records, the Event Log screen displays details for each event:

the event source (for example, DEVICE_1)

the status of an input or output (CONTACT CLOSED) or a brief description of the event (USER LOGIN)

the date and time the event occurred

Table 9 shows conditions that the event log records for inputs and outputs and in the panel itself.

Table 9

Event log conditions

 

 

 

 

 

 

SOURCE

 

Digital Input

Digital Output

Panel

 

 

 

STARTED

ALARMS CLEARED

 

 

 

ON

ALARM SILENCED

 

 

 

OFF

NO STANDBY OUTPUTS

 

 

EVENT

HW FORCE ON

AVAILABLE

 

 

NORMAL

AUTO

NO STANDBY TESTING

CONDITIONS

 

FORCE ON

DEVICE AVAILABLE

 

FORCE OFF

TIME & DATE SET

RECORDED

 

RESTORED

USER LOGIN

Main Menu

>VIEW STATUS SYSTEM AND CONTROL

↑↓=NEXT =SELECT

View Status Menu

VIEW ACTIVE ALARMS

VIEW

ALARM LOG

> VIEW

EVENT

LOG

VIEW

INPUT

STATUS

VIEW

OUTPUT STATUS

Event Log

> EVENT RECORD 99/99

SYSTEM

USER LOGIN

19-MAY-04 10:07:00

DEVICE_1 HW FORCE ON

CONTACT CLOSED

18-MAY-04 06:47:03

DEVICE_4 FORCE OFF

CONTACT OPEN

18-MAY-04 05:22:17

DEVICE_3 AUTO

CONTACT OPEN

18-MAY-04 04:32:11

DATE AND TIME SET

18-MAY-04 03:11:43

DEVICE_4 FORCE ON

CONTACT CLOSED

18-MAY-04 02:34:00

If there are no records in the log, the screen displays the message:

NO EVENTS

Viewing Additional Screens

There may be up to 99 records of event data.

To view additional records, use the arrows ↑↓.

To return to the previous screen, press the ESC key.

5.3.2Backing Up the Event Log (Service Terminal Interface only)

The event log is stored as a file in the Liebert AC4; it can hold no more than 99 records. When the log is full, the oldest records are deleted from the end of the file as new event records are added at the beginning.

You may back up the event log file to a remote computer using the Service Terminal Interface, as described in 6.2 Back Up Log Files (Service Terminal Interface only).

To delete all records in the event log, see 7.10 Clear Alarms & Logs.

21

Liebert® AC4

Image 27
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Introduction Methods of Viewing and Configuring the Liebert AC4Available Alarms Data LogsLCD for configuration Outside Enclosure OverviewOperation Typical Configuration Device Liebert ChallengerDevice RS232 LiebertLiebert HimodHimod Controller board components Controller Board Overview24VAC power ConnectorDIP switch LCD connectorLED Indicators LED indicators summaryOutput LEDs Status LEDs Input LEDs Typical Sequence Unpacking and Preliminary Inspection Installation ConsiderationsInstallation Packing ContentsSurface-Mounting the Liebert AC4 Required toolsMounting the Panel Flush-Mounting the Liebert AC4 Electrical connections to panel Connect Power to the Liebert AC4Wiring Specifications Wiring and ConnectionsWiring specifications Numbering keys Connecting Digital Inputs and OutputsConnecting Liebert Precision Cooling Units Connecting Digital InputsConnecting Digital Outputs Setting the Digital Output JumpersDigital output jumper settings Serial interface connector RS232/EIA5 Connecting Common Alarm OutputsRS232 Connector Common alarm outputsGuide to Liebert AC4 functions Overview of MenusOpening Screen Overview Main Menu OverviewLCD Menu Overview View Status Options Active Alarms View Active AlarmsActive Alarms Clearing Active AlarmsAlarm Log View Alarm LogAlarm Log Alarm log conditionsEvent Log View Event LogEvent Log Event log conditionsDigital input states View Input StatusInput Status Viewing Additional Input DataDigital output states View Output StatusOutput Status Viewing Additional Output DataSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Valid characters for data entry LoginLogin System and Control OptionsClear Alarms/Logs menu Login ScreenSystem & Control menu Clear Alarms&Logs selected Setup System menuSetup System Setup Inputs Setup System OverviewDefine Input as Alarmable or Event Change Label Name of InputDefine Input as Normally Open or Normally Closed Latched / Unlatched Set Up Alarmable Inputs in Latched or Unlatched ModeSet Up Delay Time Delay TimeSetup System Setup Common Alarm Change to Reset Y or Not Reset NReset Common Alarm Message if too many devices entered Setup System Setup ZonesSet Up a Zone Message if too few devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsSet Mode Define Operating or Standby ModeEnable or Disable an Output Device in Alarm Status Configure Output for Loss of Power Fail-SafeReset Password to the Factory Default Aaaa Setup System Setup System InfoChange Password Change the PasswordSet Date & Time Setup Site IDSetup Site ID Set Date & Time/Automatic Daylight Saving TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only Perform Firmware UPDATE-YESY or NON? N Default settings operation features Setup OperationSelect Setup Operation Setup Operation MenuSet Start Time Hour Interval Turn Automatic Sequencing On or OffActivate / Deactivate Set Interval & Start Time 1- to 99-Day IntervalFailed Standby response Turn Standby Testing On or OffChange Standby Testing Specify Failed Standby ResponseSetup Operation Menu Specify Hold Delay TimeHold Delay Time Restart Delay TimeOverride Output Clear the Event Log Clear Alarms & LogsClear Active Alarms Clear the Alarm LogSpecifications Liebert AC4 SpecificationsSpecifications Liebert AC4 Comparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface COM1 Port Setup Create a ConnectionSpecify COM Port Connection Ascii Setup button Properties SetupAscii Setup Settings tabClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceMain Menu For sample screens, see Silence Alarm and Backup Log FilesSetup Menu Overview View Status OverviewMain Menu View Active AlarmsView Active Alarms View Status MenusView Alarm Log View Alarm LogView Input Status View Event LogView Input Status View Event LogView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBack Up Event Log File Back Up Alarm Log FileBackup Log Files Alarm Log File Backup Log Files Event Log FileSetup Menu Login MenuLogin See Description Setup MenuSetup Menu Tips on Using the Service Terminal InterfaceSetup Inputs Setup InputsSetup Zones Setup Common AlarmSetup Zones Setup Common AlarmSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlySetup Operation Setup Operation Auto SequencingAuto Sequencing Setup Operation Standby Testing Standby TestingFailed Standby Hold DelaySetup Operation Failed Standby Setup Operation Hold DelayOverride Output Restart DelaySetup Operation Restart Delay Override OutputClear Alarms & Logs Clear Alarms & Logs Clear Active AlarmsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Care Ne tIs t Twor k