Emerson AC4 user manual Turn Automatic Sequencing On or Off, Activate / Deactivate

Page 50

System and Control Options

7.8.1Turn Automatic Sequencing On or Off

Use automatic sequencing to set up a schedule for rotation of redundant devices. For example, three devices might be in operating mode while a fourth device is in standby mode. Every two days, the Liebert AC4 returns the standby device to operating mode and places one of the operating devices on standby.

When zones are used, the Liebert AC4 manages the rotation sequence for each zone separately, so each zone might have one device in operating mode and one in standby mode.

Auto sequencing is OFF (deactivated) by default. When auto sequencing is activated (ON or 12h, for a

12-hour interval), the Liebert AC4 cycles devices at the specified interval and time of day as follows:

An output device in Standby mode is returned to Operating mode.

An output device that is Operating is put in Standby mode.

When more than one device is in Standby mode or turned On, the Liebert AC4 performs the operations in a sequence that rotates the order. For example, in a sequence set up to occur every two days:

• Monday:

Device 1 is placed on Standby, and Devices 2, 3 and 4 operate.

• Wednesday:

Device 2 is placed on Standby, and Devices 1, 3 and 4 operate.

• Friday:

Device 3 is placed on Standby, and Devices 1, 2 and 4 operate.

• Sunday:

Device 4 is placed on Standby, and Devices 1, 2 and 3 operate.

NOTE

The Liebert AC4 will not cycle outputs that have been manually forced On or Off through the Override Output Menu or the hardware switch (see 7.9 Override Output).

To change the auto sequencing settings:

1.From the Setup System Operation Menu, use the arrows ↑↓ to choose Auto Sequencing, then press Enter .

2.In the Activate / Deactivate screen, use the arrows ↑↓ to choose one of three options:

a.ON for intervals of every 1 to 99 days, then press Enter and proceed to Step 3.

b.12h for an interval of every 12 hours, then press Enter and proceed to Step 4.

c.OFF to deactivate auto sequencing, then press Enter to return to the previous menu.

3.Select the interval for how often the sequencing should occur in the Every 03 Days field. The default is 3 days; valid entries range from 0 to 99 days.

For each digit, use the arrows ↑↓ to choose a number from 0 to 9, then press Enter to advance to the next digit.

When finished, press Enter to set the time of day.

4.Specify the time of day the sequencing should begin in the At 00:00 field. The format is HH:MM for hours and minutes.

Use the arrows ↑↓ to choose from available entries for hours (00-23), then press Enter to advance to minutes.

Use the arrows ↑↓ to select minutes (00-59).

When finished, press Enter again.

Setup Operation Menu

>AUTO SEQUENCING OFF STANDBY TESTING OFF

FAILED STANDBY N ↑↓=NEXT =SELECT

HOLD DELAY

:

10:00

RESTART

:

00:06

Activate / Deactivate

> AUTO SEQUENCING OFF

↑↓=NEXT =EDIT

Set Interval & Start Time (1- to 99-Day Interval)

>AUTO SEQUENCING ON EVERY 03 DAYS

AT 00:00

↑↓=NEXT =EDIT

Set Start Time

(12-Hour Interval)

>AUTO SEQUENCING 12h

AT 00:00

↑↓=NEXT =EDIT

Liebert® AC4

44

Image 50
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Appendix a Service Terminal Interface Setup MenuFigures Data Logs Methods of Viewing and Configuring the Liebert AC4Available Alarms IntroductionOperation LCD for configurationOutside Enclosure Overview Device RS232 LiebertLiebert HimodHimod Typical ConfigurationDevice Liebert Challenger Controller Board Overview Controller board componentsLCD connector ConnectorDIP switch 24VAC powerOutput LEDs Status LEDs Input LEDs LED IndicatorsLED indicators summary Typical Sequence Packing Contents Installation ConsiderationsInstallation Unpacking and Preliminary InspectionMounting the Panel Surface-Mounting the Liebert AC4Required tools Flush-Mounting the Liebert AC4 Connect Power to the Liebert AC4 Electrical connections to panelWiring specifications Wiring SpecificationsWiring and Connections Connecting Digital Inputs Connecting Digital Inputs and OutputsConnecting Liebert Precision Cooling Units Numbering keysDigital output jumper settings Connecting Digital OutputsSetting the Digital Output Jumpers Common alarm outputs Connecting Common Alarm OutputsRS232 Connector Serial interface connector RS232/EIA5Overview of Menus Guide to Liebert AC4 functionsLCD Menu Overview Opening Screen OverviewMain Menu Overview View Status Options Clearing Active Alarms View Active AlarmsActive Alarms Active AlarmsAlarm log conditions View Alarm LogAlarm Log Alarm LogEvent log conditions View Event LogEvent Log Event LogViewing Additional Input Data View Input StatusInput Status Digital input statesViewing Additional Output Data View Output StatusOutput Status Digital output statesSilence Alarm & Backup LOG Files Service Terminal Interface Silence Alarm Service Terminal Interface onlyBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface System and Control Options LoginLogin Valid characters for data entrySetup System menu Login ScreenSystem & Control menu Clear Alarms&Logs selected Clear Alarms/Logs menuSetup System Overview Setup System Setup InputsDefine Input as Normally Open or Normally Closed Define Input as Alarmable or EventChange Label Name of Input Delay Time Set Up Alarmable Inputs in Latched or Unlatched ModeSet Up Delay Time Latched / UnlatchedReset Common Alarm Setup System Setup Common AlarmChange to Reset Y or Not Reset N Message if too few devices entered Setup System Setup ZonesSet Up a Zone Message if too many devices enteredSetup System Setup Outputs Define Output as Normally Open or Normally ClosedConfigure Output for Loss of Power Fail-Safe Define Operating or Standby ModeEnable or Disable an Output Device in Alarm Status Set ModeChange the Password Setup System Setup System InfoChange Password Reset Password to the Factory Default AaaaSet Date & Time/Automatic Daylight Saving Time Setup Site IDSetup Site ID Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Firmware Update Service Terminal Interface only Factory DefaultsFactory Defaults Perform Firmware UPDATE-YESY or NON? N Setup Operation Menu Setup OperationSelect Setup Operation Default settings operation featuresSet Interval & Start Time 1- to 99-Day Interval Turn Automatic Sequencing On or OffActivate / Deactivate Set Start Time Hour IntervalSpecify Failed Standby Response Turn Standby Testing On or OffChange Standby Testing Failed Standby responseRestart Delay Time Specify Hold Delay TimeHold Delay Time Setup Operation MenuOverride Output Clear the Alarm Log Clear Alarms & LogsClear Active Alarms Clear the Event LogLiebert AC4 Specifications SpecificationsSpecifications Liebert AC4 Appendix a Service Terminal Interface Comparison of Functions LCD and Service Terminal InterfaceConnecting to the Service Terminal Interface Specify COM Port Connection COM1 Port SetupCreate a Connection Settings tab Properties SetupAscii Setup Ascii Setup buttonConnect to the Service Terminal Interface Click on the file name for example, AC4.htView Status Overview Silence Alarm and Backup Log FilesSetup Menu Overview Main Menu For sample screens, seeView Status Menus View Active AlarmsView Active Alarms Main MenuView Alarm Log View Alarm LogView Event Log View Event LogView Input Status View Input StatusView Output Status View Output StatusSilence Alarm Section A.5.1 Section A.5.2Backup Log Files Event Log File Back Up Alarm Log FileBackup Log Files Alarm Log File Back Up Event Log FileLogin Setup MenuLogin Menu Tips on Using the Service Terminal Interface Setup MenuSetup Menu See DescriptionSetup Inputs Setup InputsSetup Common Alarm Setup Common AlarmSetup Zones Setup ZonesSetup Outputs Setup OutputsChange Password Setup System InfoSetup System Info Setup Site ID Set Date & TimeBackup & Upload Configuration File Backup Backup & Upload Configuration File Upload Factory DefaultsFirmware Update Service Terminal Interface only Firmware UpdateAuto Sequencing Setup OperationSetup Operation Auto Sequencing Standby Testing Setup Operation Standby TestingSetup Operation Hold Delay Hold DelaySetup Operation Failed Standby Failed StandbyOverride Output Restart DelaySetup Operation Restart Delay Override OutputClear Alarms & Logs Clear the Alarm Log Clear Alarms & LogsClear Alarms & Logs Clear Active Alarms Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Twor k Ne tIs t Care