Emerson AC4 user manual Setup Operation Standby Testing

Page 80

Setup Menu

Standby Testing

For details on this feature, see 7.8.2 - Turn Standby Testing On or Off.

Setup Operation - Standby Testing

SETUP OPERATION

Select operation to edit

OPERATION

STATE

1=AUTO SEQUENCING

OFF

2=STANDBY TESTING

OFF

3=FAILED STANDBY

N

4=HOLD DELAY

10:00

5=RESTART DELAY

00:06

6=RETURN TO SETUP MENU

 

7=RETURN TO MAIN MENU

 

SELECT A NUMBER:2

 

 

 

>STANDBY TESTING- N FOR ON, F FOR OFF >[N]

>[N]

>COMMAND SUCCESSFUL

>EVERY ## DAYS >[03] DAYS

>[

>COMMAND SUCCESSFUL

>AT

>[00:00]

>[

>COMMAND SUCCESSFUL

>FOR >[10] MIN >[

>COMMAND SUCCESSFUL

Liebert® AC4

74

Image 80
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Appendix a Service Terminal Interface Setup MenuFigures Methods of Viewing and Configuring the Liebert AC4 Available AlarmsData Logs IntroductionOperation LCD for configurationOutside Enclosure Overview Device RS232 LiebertLiebert HimodHimod Typical ConfigurationDevice Liebert Challenger Controller Board Overview Controller board componentsConnector DIP switchLCD connector 24VAC powerOutput LEDs Status LEDs Input LEDs LED IndicatorsLED indicators summary Typical Sequence Installation Considerations InstallationPacking Contents Unpacking and Preliminary InspectionMounting the Panel Surface-Mounting the Liebert AC4Required tools Flush-Mounting the Liebert AC4 Connect Power to the Liebert AC4 Electrical connections to panelWiring specifications Wiring SpecificationsWiring and Connections Connecting Digital Inputs and Outputs Connecting Liebert Precision Cooling UnitsConnecting Digital Inputs Numbering keysDigital output jumper settings Connecting Digital OutputsSetting the Digital Output Jumpers Connecting Common Alarm Outputs RS232 ConnectorCommon alarm outputs Serial interface connector RS232/EIA5Overview of Menus Guide to Liebert AC4 functionsLCD Menu Overview Opening Screen OverviewMain Menu Overview View Status Options View Active Alarms Active AlarmsClearing Active Alarms Active AlarmsView Alarm Log Alarm LogAlarm log conditions Alarm LogView Event Log Event LogEvent log conditions Event LogView Input Status Input StatusViewing Additional Input Data Digital input statesView Output Status Output StatusViewing Additional Output Data Digital output statesSilence Alarm & Backup LOG Files Service Terminal Interface Silence Alarm Service Terminal Interface onlyBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Login LoginSystem and Control Options Valid characters for data entryLogin Screen System & Control menu Clear Alarms&Logs selectedSetup System menu Clear Alarms/Logs menuSetup System Overview Setup System Setup InputsDefine Input as Normally Open or Normally Closed Define Input as Alarmable or EventChange Label Name of Input Set Up Alarmable Inputs in Latched or Unlatched Mode Set Up Delay TimeDelay Time Latched / UnlatchedReset Common Alarm Setup System Setup Common AlarmChange to Reset Y or Not Reset N Setup System Setup Zones Set Up a ZoneMessage if too few devices entered Message if too many devices enteredSetup System Setup Outputs Define Output as Normally Open or Normally ClosedDefine Operating or Standby Mode Enable or Disable an Output Device in Alarm StatusConfigure Output for Loss of Power Fail-Safe Set ModeSetup System Setup System Info Change PasswordChange the Password Reset Password to the Factory Default AaaaSetup Site ID Setup Site IDSet Date & Time/Automatic Daylight Saving Time Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Firmware Update Service Terminal Interface only Factory DefaultsFactory Defaults Perform Firmware UPDATE-YESY or NON? N Setup Operation Select Setup OperationSetup Operation Menu Default settings operation featuresTurn Automatic Sequencing On or Off Activate / DeactivateSet Interval & Start Time 1- to 99-Day Interval Set Start Time Hour IntervalTurn Standby Testing On or Off Change Standby TestingSpecify Failed Standby Response Failed Standby responseSpecify Hold Delay Time Hold Delay TimeRestart Delay Time Setup Operation MenuOverride Output Clear Alarms & Logs Clear Active AlarmsClear the Alarm Log Clear the Event LogLiebert AC4 Specifications SpecificationsSpecifications Liebert AC4 Appendix a Service Terminal Interface Comparison of Functions LCD and Service Terminal InterfaceConnecting to the Service Terminal Interface Specify COM Port Connection COM1 Port SetupCreate a Connection Properties Setup Ascii SetupSettings tab Ascii Setup buttonConnect to the Service Terminal Interface Click on the file name for example, AC4.htSilence Alarm and Backup Log Files Setup Menu OverviewView Status Overview Main Menu For sample screens, seeView Active Alarms View Active AlarmsView Status Menus Main MenuView Alarm Log View Alarm LogView Event Log View Input StatusView Event Log View Input StatusView Output Status View Output StatusSilence Alarm Section A.5.1 Section A.5.2Back Up Alarm Log File Backup Log Files Alarm Log FileBackup Log Files Event Log File Back Up Event Log FileLogin Setup MenuLogin Menu Setup Menu Setup MenuTips on Using the Service Terminal Interface See DescriptionSetup Inputs Setup InputsSetup Common Alarm Setup ZonesSetup Common Alarm Setup ZonesSetup Outputs Setup OutputsChange Password Setup System InfoSetup System Info Setup Site ID Set Date & TimeBackup & Upload Configuration File Backup Backup & Upload Configuration File Upload Factory DefaultsFirmware Update Service Terminal Interface only Firmware UpdateAuto Sequencing Setup OperationSetup Operation Auto Sequencing Standby Testing Setup Operation Standby TestingHold Delay Setup Operation Failed StandbySetup Operation Hold Delay Failed StandbyRestart Delay Setup Operation Restart DelayOverride Output Override OutputClear Alarms & Logs Clear the Alarm Log Clear Alarms & LogsClear Alarms & Logs Clear Active Alarms Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Ne t Is tTwor k Care