Emerson AC4 user manual Turn Standby Testing On or Off, Specify Failed Standby Response

Page 51

System and Control Options

7.8.2Turn Standby Testing On or Off

Standby testing permits scheduling an automatic operational check of devices in Standby mode.

When this feature is activated (ON), the Liebert AC4 tests all devices in Standby mode by putting each device in operating mode for a designated time. You may specify the time of day the testing begins, the duration of the test and the interval between tests. Standby testing is OFF (deactivated) by default.

To change the standby testing settings:

From the Setup System Operation Menu, use the arrows ↑↓ to choose Standby Testing, then press Enter .

In the Change Standby Testing screen, press Enter to edit Standby Testing, then use the arrows ↑↓ to choose ON to activate or OFF to deactivate the standby testing feature. Press Enter .

Select the desired interval for how frequently the testing should occur in the Every 03 Days field. The default is 3 days; valid entries range from 0 to 99 days.

Setup Operation Menu

AUTO SEQUENCING OFF

>STANDBY TESTING OFF

FAILED STANDBY N ↑↓=NEXT =SELECT

HOLD DELAY

:

10:00

RESTART

:

00:06

For each digit, use the arrows ↑↓ to choose a number from 0 to 9, then press Enter to advance to the next digit.

When finished, press Enter to configure the time of day.

Specify the time of day the test should begin in the At 00:00 field. The format is HH:MM for hours and minutes.

Use the arrows ↑↓ to choose from available entries for hours (00-23), then press Enter to advance to minutes.

Use the arrows ↑↓ to select minutes (00-59).

When finished, press Enter again.

Change Standby Testing

>STANDBY TESTING ON EVERY 03 DAYS

AT 00:00 FOR 10 MIN ↑↓=NEXT =EDIT

Specify the duration of the test in minutes—the length of time the standby units will be turned On—in the For 10 Min field. Use the arrows ↑↓ to choose a number from 0 to 59 minutes. The default is 10 minutes.

When finished, press Enter .

7.8.3Specify Failed Standby Response

The Liebert AC4’s Failed Standby feature determines what happens when an operating device fails and a standby device then becomes an operating unit. A subsequent alarm in the newly operating unit (previously the standby device) results in either restarting the previously operating device that was alarmed or not. This feature specifies whether each device remains in its current state or returns to its previous state of operation.

When this feature is activated (Y), each device returns to its previous state, as Table 19 shows: the newly enabled Standby device is disabled and the previously operating device is returned to Operating mode. The default setting is N (deactivated), meaning that each device remains in its current state: the Standby device remains enabled and the previously operating unit remains disabled.

Table 19 Failed Standby response

Failed Standby

Previous Standby Device

Previously Operating

Setting

(alarm after being enabled)

Device

 

 

 

Activated (Y)

Disabled

Returned to Operating mode

 

 

 

Deactivated (N)

Remains enabled

Remains disabled

 

 

 

To change the Failed Standby settings:

From the Setup System Operation Menu, use the arrows ↑↓ to choose Failed Standby, then press Enter .

In the Change Failed Standby screen, press use the arrows ↑↓ to choose Y to activate or N to deactivate the feature.

Press Enter .

Setup Operation Menu

AUTO SEQUENCING OFF STANDBY TESTING OFF

>FAILED STANDBY N

↑↓=NEXT =SELECT

HOLD DELAY

:

10:00

RESTART

:

00:06

Change Failed Standby

>FAILED STANDBY N

↑↓=NEXT =END

45

Liebert® AC4

Image 51
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Introduction Methods of Viewing and Configuring the Liebert AC4Available Alarms Data LogsLCD for configuration Outside Enclosure OverviewOperation Typical Configuration Device Liebert ChallengerDevice RS232 LiebertLiebert HimodHimod Controller board components Controller Board Overview24VAC power ConnectorDIP switch LCD connectorLED Indicators LED indicators summaryOutput LEDs Status LEDs Input LEDs Typical Sequence Unpacking and Preliminary Inspection Installation ConsiderationsInstallation Packing ContentsSurface-Mounting the Liebert AC4 Required toolsMounting the Panel Flush-Mounting the Liebert AC4 Electrical connections to panel Connect Power to the Liebert AC4Wiring Specifications Wiring and ConnectionsWiring specifications Numbering keys Connecting Digital Inputs and OutputsConnecting Liebert Precision Cooling Units Connecting Digital InputsConnecting Digital Outputs Setting the Digital Output JumpersDigital output jumper settings Serial interface connector RS232/EIA5 Connecting Common Alarm OutputsRS232 Connector Common alarm outputsGuide to Liebert AC4 functions Overview of MenusOpening Screen Overview Main Menu OverviewLCD Menu Overview View Status Options Active Alarms View Active AlarmsActive Alarms Clearing Active AlarmsAlarm Log View Alarm LogAlarm Log Alarm log conditionsEvent Log View Event LogEvent Log Event log conditionsDigital input states View Input StatusInput Status Viewing Additional Input DataDigital output states View Output StatusOutput Status Viewing Additional Output DataSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Valid characters for data entry LoginLogin System and Control OptionsClear Alarms/Logs menu Login ScreenSystem & Control menu Clear Alarms&Logs selected Setup System menuSetup System Setup Inputs Setup System OverviewDefine Input as Alarmable or Event Change Label Name of InputDefine Input as Normally Open or Normally Closed Latched / Unlatched Set Up Alarmable Inputs in Latched or Unlatched ModeSet Up Delay Time Delay TimeSetup System Setup Common Alarm Change to Reset Y or Not Reset NReset Common Alarm Message if too many devices entered Setup System Setup ZonesSet Up a Zone Message if too few devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsSet Mode Define Operating or Standby ModeEnable or Disable an Output Device in Alarm Status Configure Output for Loss of Power Fail-SafeReset Password to the Factory Default Aaaa Setup System Setup System InfoChange Password Change the PasswordSet Date & Time Setup Site IDSetup Site ID Set Date & Time/Automatic Daylight Saving TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only Perform Firmware UPDATE-YESY or NON? N Default settings operation features Setup OperationSelect Setup Operation Setup Operation MenuSet Start Time Hour Interval Turn Automatic Sequencing On or OffActivate / Deactivate Set Interval & Start Time 1- to 99-Day IntervalFailed Standby response Turn Standby Testing On or OffChange Standby Testing Specify Failed Standby ResponseSetup Operation Menu Specify Hold Delay TimeHold Delay Time Restart Delay TimeOverride Output Clear the Event Log Clear Alarms & LogsClear Active Alarms Clear the Alarm LogSpecifications Liebert AC4 SpecificationsSpecifications Liebert AC4 Comparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface COM1 Port Setup Create a ConnectionSpecify COM Port Connection Ascii Setup button Properties SetupAscii Setup Settings tabClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceMain Menu For sample screens, see Silence Alarm and Backup Log FilesSetup Menu Overview View Status OverviewMain Menu View Active AlarmsView Active Alarms View Status MenusView Alarm Log View Alarm LogView Input Status View Event LogView Input Status View Event LogView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBack Up Event Log File Back Up Alarm Log FileBackup Log Files Alarm Log File Backup Log Files Event Log FileSetup Menu Login MenuLogin See Description Setup MenuSetup Menu Tips on Using the Service Terminal InterfaceSetup Inputs Setup InputsSetup Zones Setup Common AlarmSetup Zones Setup Common AlarmSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlySetup Operation Setup Operation Auto SequencingAuto Sequencing Setup Operation Standby Testing Standby TestingFailed Standby Hold DelaySetup Operation Failed Standby Setup Operation Hold DelayOverride Output Restart DelaySetup Operation Restart Delay Override OutputClear Alarms & Logs Clear Alarms & Logs Clear Active AlarmsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Care Ne tIs t Twor k