Emerson AC4 Setup System Setup Zones, Set Up a Zone, Message if too few devices entered

Page 39

System and Control Options

7.5Setup System - Setup Zones

The Liebert AC4 has two zones that may be used to define different areas—rooms or sections of a room. The Liebert AC4 effectively performs as two separate units, controlling each zone separately, for examply, using a different rotation sequence for devices in each zone.

Each zone may have two to four outputs associated with it. By default, Zone 1 has four associated outputs and Zone 2 has none.

To set up zones:

Log In and Choose Setup System

From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter (see 7.1 Login for help).

Enter your password at the Login screen.

From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter .

Select Setup Zones

From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Zones and press Enter .

7.5.1Set Up a Zone

From the Setup Zones Menu, choose a zone—for example, Zone 1—and press Enter .

On the Number of Devices screen, Use the arrows ↑↓ to select the number of outputs for this zone, then press Enter . The example at right shows four outputs in Zone 1.

Table 15 shows the default number of outputs for each zone.

Table 15 Default zones

Zone

Default number of outputs

 

 

Zone 1

4

 

 

Zone 2

0

 

 

Setup System Menu

SETUP INPUTS SETUP COMMON ALARM

>SETUP ZONES

↑↓=NEXT =SELECT

SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION

Setup Zones

SETUP ZONES

>ZONE 1 4

ZONE 2 0

↑↓=NEXT =SELECT

Number of Devices

# DEVICES IN ZONE

ZONE 1 4 ↑↓=SELECT =NEXT/END

NOTE: Each zone that is used must have at least two outputs, and the total for the two zones cannot exceed four.

A message appears if you enter too few or too many devices, as shown at right. Press Escape to return to the Setup Zones menu.

Table 16 shows the possible combinations of outputs for each zone. For example, if Zone 1 has four outputs, then Zone 2 may not be used (0 outputs).

Table 16 Possible combinations - outputs per zone

If Zone 1 has:

Zone 2 must have:

 

 

4 or 3 outputs

0 (not used)

 

 

2 outputs

0 (not used) or 2 outputs

 

 

0 (not used)

2 or 3 or 4 outputs

 

 

Message (if too few devices entered)

MINIMUM OF 2 DEVICES ESC BACK

Message (if too many devices entered)

TOO MANY DEVICES ESC BACK

33

Liebert® AC4

Image 39
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Introduction Methods of Viewing and Configuring the Liebert AC4Available Alarms Data LogsLCD for configuration Outside Enclosure OverviewOperation Typical Configuration Device Liebert ChallengerDevice RS232 LiebertLiebert HimodHimod Controller board components Controller Board Overview24VAC power ConnectorDIP switch LCD connectorLED Indicators LED indicators summaryOutput LEDs Status LEDs Input LEDs Typical Sequence Unpacking and Preliminary Inspection Installation ConsiderationsInstallation Packing ContentsSurface-Mounting the Liebert AC4 Required toolsMounting the Panel Flush-Mounting the Liebert AC4 Electrical connections to panel Connect Power to the Liebert AC4Wiring Specifications Wiring and ConnectionsWiring specifications Numbering keys Connecting Digital Inputs and OutputsConnecting Liebert Precision Cooling Units Connecting Digital InputsConnecting Digital Outputs Setting the Digital Output JumpersDigital output jumper settings Serial interface connector RS232/EIA5 Connecting Common Alarm OutputsRS232 Connector Common alarm outputsGuide to Liebert AC4 functions Overview of MenusOpening Screen Overview Main Menu OverviewLCD Menu Overview View Status Options Active Alarms View Active AlarmsActive Alarms Clearing Active AlarmsAlarm Log View Alarm LogAlarm Log Alarm log conditionsEvent Log View Event LogEvent Log Event log conditionsDigital input states View Input StatusInput Status Viewing Additional Input DataDigital output states View Output StatusOutput Status Viewing Additional Output DataSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Valid characters for data entry LoginLogin System and Control OptionsClear Alarms/Logs menu Login ScreenSystem & Control menu Clear Alarms&Logs selected Setup System menuSetup System Setup Inputs Setup System OverviewDefine Input as Alarmable or Event Change Label Name of InputDefine Input as Normally Open or Normally Closed Latched / Unlatched Set Up Alarmable Inputs in Latched or Unlatched ModeSet Up Delay Time Delay TimeSetup System Setup Common Alarm Change to Reset Y or Not Reset NReset Common Alarm Message if too many devices entered Setup System Setup ZonesSet Up a Zone Message if too few devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsSet Mode Define Operating or Standby ModeEnable or Disable an Output Device in Alarm Status Configure Output for Loss of Power Fail-SafeReset Password to the Factory Default Aaaa Setup System Setup System InfoChange Password Change the PasswordSet Date & Time Setup Site IDSetup Site ID Set Date & Time/Automatic Daylight Saving TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only Perform Firmware UPDATE-YESY or NON? N Default settings operation features Setup OperationSelect Setup Operation Setup Operation MenuSet Start Time Hour Interval Turn Automatic Sequencing On or OffActivate / Deactivate Set Interval & Start Time 1- to 99-Day IntervalFailed Standby response Turn Standby Testing On or OffChange Standby Testing Specify Failed Standby ResponseSetup Operation Menu Specify Hold Delay TimeHold Delay Time Restart Delay TimeOverride Output Clear the Event Log Clear Alarms & LogsClear Active Alarms Clear the Alarm LogSpecifications Liebert AC4 SpecificationsSpecifications Liebert AC4 Comparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface COM1 Port Setup Create a ConnectionSpecify COM Port Connection Ascii Setup button Properties SetupAscii Setup Settings tabClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceMain Menu For sample screens, see Silence Alarm and Backup Log FilesSetup Menu Overview View Status OverviewMain Menu View Active AlarmsView Active Alarms View Status MenusView Alarm Log View Alarm LogView Input Status View Event LogView Input Status View Event LogView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBack Up Event Log File Back Up Alarm Log FileBackup Log Files Alarm Log File Backup Log Files Event Log FileSetup Menu Login MenuLogin See Description Setup MenuSetup Menu Tips on Using the Service Terminal InterfaceSetup Inputs Setup InputsSetup Zones Setup Common AlarmSetup Zones Setup Common AlarmSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlySetup Operation Setup Operation Auto SequencingAuto Sequencing Setup Operation Standby Testing Standby TestingFailed Standby Hold DelaySetup Operation Failed Standby Setup Operation Hold DelayOverride Output Restart DelaySetup Operation Restart Delay Override OutputClear Alarms & Logs Clear Alarms & Logs Clear Active AlarmsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Care Ne tIs t Twor k