7.2Setup System - Overview

The Setup System screen displays six options that allow you to configure input and output devices, the common alarm, and a variety of system details, such as login password and system date and time:

Setup Inputs

Setup Common Alarm

Setup Zones

 

• Setup Outputs

Setup System Menu

 

• Setup System Info

 

 

 

 

 

 

 

 

> SETUP INPUTS

 

• Setup Operation

 

 

SETUP COMMON ALARM

7.3

Setup System - Setup Inputs

 

SETUP ZONES

 

↑↓=NEXT

=SELECT

 

 

 

 

The Liebert AC4 has four digital input points that may be configured

 

SETUP OUTPUTS

 

 

 

SETUP SYSTEM INFO

 

individually. These inputs may have a wide variety of Liebert or other

 

SETUP OPERATION

 

manufacturers’ equipment connected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To configure a digital input:

Select Input Menu

 

 

SELECT

 

INPUT

 

Log In and Choose Setup System

 

 

 

> DEVICE_1

 

NO-AL-NL

 

• From the Main Menu, use the arrows ↑↓ to choose System and

 

DEVICE_2

 

NO-AL-NL

 

 

↑↓=NEXT

 

=SELECT

 

 

Control, then press Enter (see 7.1 Login for help).

 

 

 

 

DEVICE_3 NO-AL-NL

 

• Enter your password at the Login screen.

 

 

 

DEVICE_4

 

NO-AL-NL

From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter .

Select a Digital Input to Configure

From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Inputs and press Enter .

From the Select Input Menu, choose an input—for example, Device_1—and press Enter .

Table 13 shows the digital input features you may change, along with the default settings: you may change the name of the input, define it as normally open or closed, and specify it as alarmable or as an event.

Alarmable inputs may be defined as either Unlatched or Latched.

Event status allows you to monitor a digital input’s state—and use a change in state to initiate an action through an output, if desired—without triggering an alarm. Events are always Unlatched.

You may also specify a time delay before the Liebert AC4 responds to an alarm or event.

Use the steps following Table 13 to change the default settings for any digital input.

Table 13 Default settings - digital inputs

Feature

Default

Other Options

 

 

 

LABEL

DEVICE_1

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

L (Latched) / Y (Yes)*

NL (Unlatched) / N (No)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.

 

Settings - Select Input Menu

When configuring an input

 

(see Section 7.3)

(see Section 7.3.4)

Unlatched

NL (Not Latched)

N (No, not latched)

Latched

L (Latched)

Y (Yes, latched)

29

Liebert® AC4

Image 35
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Introduction Methods of Viewing and Configuring the Liebert AC4Available Alarms Data LogsOperation LCD for configurationOutside Enclosure Overview Device RS232 LiebertLiebert HimodHimod Typical ConfigurationDevice Liebert Challenger Controller board components Controller Board Overview24VAC power ConnectorDIP switch LCD connectorOutput LEDs Status LEDs Input LEDs LED IndicatorsLED indicators summary Typical Sequence Unpacking and Preliminary Inspection Installation ConsiderationsInstallation Packing ContentsMounting the Panel Surface-Mounting the Liebert AC4Required tools Flush-Mounting the Liebert AC4 Electrical connections to panel Connect Power to the Liebert AC4Wiring specifications Wiring SpecificationsWiring and Connections Numbering keys Connecting Digital Inputs and OutputsConnecting Liebert Precision Cooling Units Connecting Digital InputsDigital output jumper settings Connecting Digital OutputsSetting the Digital Output Jumpers Serial interface connector RS232/EIA5 Connecting Common Alarm OutputsRS232 Connector Common alarm outputsGuide to Liebert AC4 functions Overview of MenusLCD Menu Overview Opening Screen OverviewMain Menu Overview View Status Options Active Alarms View Active AlarmsActive Alarms Clearing Active AlarmsAlarm Log View Alarm LogAlarm Log Alarm log conditionsEvent Log View Event LogEvent Log Event log conditionsDigital input states View Input StatusInput Status Viewing Additional Input DataDigital output states View Output StatusOutput Status Viewing Additional Output DataSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Valid characters for data entry LoginLogin System and Control OptionsClear Alarms/Logs menu Login ScreenSystem & Control menu Clear Alarms&Logs selected Setup System menuSetup System Setup Inputs Setup System OverviewDefine Input as Normally Open or Normally Closed Define Input as Alarmable or EventChange Label Name of Input Latched / Unlatched Set Up Alarmable Inputs in Latched or Unlatched ModeSet Up Delay Time Delay TimeReset Common Alarm Setup System Setup Common AlarmChange to Reset Y or Not Reset N Message if too many devices entered Setup System Setup ZonesSet Up a Zone Message if too few devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsSet Mode Define Operating or Standby ModeEnable or Disable an Output Device in Alarm Status Configure Output for Loss of Power Fail-SafeReset Password to the Factory Default Aaaa Setup System Setup System InfoChange Password Change the PasswordSet Date & Time Setup Site IDSetup Site ID Set Date & Time/Automatic Daylight Saving TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Firmware Update Service Terminal Interface only Factory DefaultsFactory Defaults Perform Firmware UPDATE-YESY or NON? N Default settings operation features Setup OperationSelect Setup Operation Setup Operation MenuSet Start Time Hour Interval Turn Automatic Sequencing On or OffActivate / Deactivate Set Interval & Start Time 1- to 99-Day IntervalFailed Standby response Turn Standby Testing On or OffChange Standby Testing Specify Failed Standby ResponseSetup Operation Menu Specify Hold Delay TimeHold Delay Time Restart Delay TimeOverride Output Clear the Event Log Clear Alarms & LogsClear Active Alarms Clear the Alarm LogSpecifications Liebert AC4 SpecificationsSpecifications Liebert AC4 Comparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface Specify COM Port Connection COM1 Port SetupCreate a Connection Ascii Setup button Properties SetupAscii Setup Settings tabClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceMain Menu For sample screens, see Silence Alarm and Backup Log FilesSetup Menu Overview View Status OverviewMain Menu View Active AlarmsView Active Alarms View Status MenusView Alarm Log View Alarm LogView Input Status View Event LogView Input Status View Event LogView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBack Up Event Log File Back Up Alarm Log FileBackup Log Files Alarm Log File Backup Log Files Event Log FileLogin Setup MenuLogin Menu See Description Setup MenuSetup Menu Tips on Using the Service Terminal InterfaceSetup Inputs Setup InputsSetup Zones Setup Common AlarmSetup Zones Setup Common AlarmSetup Outputs Setup OutputsChange Password Setup System InfoSetup System Info Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlyAuto Sequencing Setup OperationSetup Operation Auto Sequencing Setup Operation Standby Testing Standby TestingFailed Standby Hold DelaySetup Operation Failed Standby Setup Operation Hold DelayOverride Output Restart DelaySetup Operation Restart Delay Override OutputClear Alarms & Logs Clear the Alarm Log Clear Alarms & LogsClear Alarms & Logs Clear Active Alarms Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Care Ne tIs t Twor k