Emerson AC4 user manual Set Up Alarmable Inputs in Latched or Unlatched Mode, Set Up Delay Time

Page 37

System and Control Options

7.3.4Set Up Alarmable Inputs in Latched or Unlatched Mode

Alarmable input points may be set up in Latched mode (Y), which requires the user to clear the Liebert AC4 alarms after an alarm has occurred, or Unlatched mode (N), in which alarms will automatically clear after a return-to-normal state. The default setting for alarmable inputs is Y (Latched). Any input defined as an event is automatically Unlatched.

An input defined as Latched does not reset automatically after an alarm. It will remain in the triggered position even after the monitored device returns to normal. After an alarm, the user must manually reset Latched inputs, as described in 7.10.1 Clear Active Alarms. This also means that any outputs linked to a Latched digital input will remain triggered until the input is manually reset.

An input defined as Unlatched will automatically track the status of the monitored device. No action by the user is required.

From the Setup Inputs Menu, choose Latched, as shown above right, and press Enter .

To change this feature, use the arrows ↑↓ to choose Y (Yes - Latched) or N (No - Unlatched), then press Enter .

NOTE: Only alarmable input points may be set up as Latched. If you attempt to set up an event as Latched, the message shown at right appears. Press the ESC key to return to the previous screen to continue configuring the digital input.

The only way to reset latched alarms is by clearing active alarms. This step is required to return latched points to their normal state. For details, see 7.10.1 Clear Active Alarms.

7.3.5Set Up Delay Time

Each input may be set up with a specified time delay between the occurrence of an alarm or event—a monitored device changes state— and any response by the Liebert AC4. This feature can prevent needless responses to transient conditions.

This delay is the amount of time that must elapse before the Liebert AC4 acknowledges the change of state in the monitored device and takes any further action, such as dialing configured pagers. The default time delay is 1 second (displayed as 00 MIN : 01 SEC).

The time delay applies only when a monitored device changes from its normal state—for example, the Liebert AC4 detects a closed contact that is defined as Normally Open.

When the monitored device returns to its normal state, the Liebert AC4 acknowledges the change of state after the delay timer ends its countdown.

Setup Inputs Menu

SETUP DEVICE_1 LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑↓=NEXT =SELECT

>LATCHED: N

DELAY: 00:01

Latched / Unlatched

IS ALARM

LATCHED? N

↑↓=Y/N =END

Message (if input has been defined as an event)

LATCH NOT ALLOWED WHEN IN EVENT MODE

ESC=BACK

Setup Inputs Menu

SETUP DEVICE_1 LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑↓=NEXT =SELECT

LATCHED: N

DELAY: 00:01

Delay Time

DELAY TIME BEFORE TRIGGER?

00 MIN : 01 SEC ↑↓=SELECT =NEXT/END

From the Setup Inputs Menu, choose Delay, as shown at right, and press Enter .

To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):

For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-99.

Press Enter to advance to seconds (SEC).

For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.

When finished, press Enter again.

31

Liebert® AC4

Image 37
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Available Alarms Methods of Viewing and Configuring the Liebert AC4Data Logs IntroductionOutside Enclosure Overview LCD for configurationOperation Device Liebert Challenger Typical ConfigurationDevice RS232 LiebertLiebert HimodHimod Controller board components Controller Board OverviewDIP switch ConnectorLCD connector 24VAC powerLED indicators summary LED IndicatorsOutput LEDs Status LEDs Input LEDs Typical Sequence Installation Installation ConsiderationsPacking Contents Unpacking and Preliminary InspectionRequired tools Surface-Mounting the Liebert AC4Mounting the Panel Flush-Mounting the Liebert AC4 Electrical connections to panel Connect Power to the Liebert AC4Wiring and Connections Wiring SpecificationsWiring specifications Connecting Liebert Precision Cooling Units Connecting Digital Inputs and OutputsConnecting Digital Inputs Numbering keysSetting the Digital Output Jumpers Connecting Digital OutputsDigital output jumper settings RS232 Connector Connecting Common Alarm OutputsCommon alarm outputs Serial interface connector RS232/EIA5Guide to Liebert AC4 functions Overview of MenusMain Menu Overview Opening Screen OverviewLCD Menu Overview View Status Options Active Alarms View Active AlarmsClearing Active Alarms Active AlarmsAlarm Log View Alarm LogAlarm log conditions Alarm LogEvent Log View Event LogEvent log conditions Event LogInput Status View Input StatusViewing Additional Input Data Digital input statesOutput Status View Output StatusViewing Additional Output Data Digital output statesSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Login LoginSystem and Control Options Valid characters for data entrySystem & Control menu Clear Alarms&Logs selected Login ScreenSetup System menu Clear Alarms/Logs menuSetup System Setup Inputs Setup System OverviewChange Label Name of Input Define Input as Alarmable or EventDefine Input as Normally Open or Normally Closed Set Up Delay Time Set Up Alarmable Inputs in Latched or Unlatched ModeDelay Time Latched / UnlatchedChange to Reset Y or Not Reset N Setup System Setup Common AlarmReset Common Alarm Set Up a Zone Setup System Setup ZonesMessage if too few devices entered Message if too many devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsEnable or Disable an Output Device in Alarm Status Define Operating or Standby ModeConfigure Output for Loss of Power Fail-Safe Set ModeChange Password Setup System Setup System InfoChange the Password Reset Password to the Factory Default AaaaSetup Site ID Setup Site IDSet Date & Time/Automatic Daylight Saving Time Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only Perform Firmware UPDATE-YESY or NON? N Select Setup Operation Setup OperationSetup Operation Menu Default settings operation featuresActivate / Deactivate Turn Automatic Sequencing On or OffSet Interval & Start Time 1- to 99-Day Interval Set Start Time Hour IntervalChange Standby Testing Turn Standby Testing On or OffSpecify Failed Standby Response Failed Standby responseHold Delay Time Specify Hold Delay TimeRestart Delay Time Setup Operation MenuOverride Output Clear Active Alarms Clear Alarms & LogsClear the Alarm Log Clear the Event LogSpecifications Liebert AC4 SpecificationsSpecifications Liebert AC4 Comparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface Create a Connection COM1 Port SetupSpecify COM Port Connection Ascii Setup Properties SetupSettings tab Ascii Setup buttonClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceSetup Menu Overview Silence Alarm and Backup Log FilesView Status Overview Main Menu For sample screens, seeView Active Alarms View Active AlarmsView Status Menus Main MenuView Alarm Log View Alarm LogView Input Status View Event LogView Event Log View Input StatusView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBackup Log Files Alarm Log File Back Up Alarm Log FileBackup Log Files Event Log File Back Up Event Log FileLogin Menu Setup MenuLogin Setup Menu Setup MenuTips on Using the Service Terminal Interface See DescriptionSetup Inputs Setup InputsSetup Zones Setup Common AlarmSetup Common Alarm Setup ZonesSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlySetup Operation Auto Sequencing Setup OperationAuto Sequencing Setup Operation Standby Testing Standby TestingSetup Operation Failed Standby Hold DelaySetup Operation Hold Delay Failed StandbySetup Operation Restart Delay Restart DelayOverride Output Override OutputClear Alarms & Logs Clear Active Alarms Clear Alarms & LogsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Is t Ne tTwor k Care