Emerson AC4 user manual Specify Hold Delay Time, Specify Restart Time, Restart Delay Time

Page 52

System and Control Options

7.8.4 Specify Hold Delay Time

Setup Operation Menu

 

After an output changes state, the hold delay timer directs the Liebert AC4 to ignore all inputs in the same zone for the specified time.

This delay is the amount of time that must elapse before the Liebert AC4 acknowledges a change of state in any input. The default is 10 minutes (displayed as 10 MIN : 00 SEC).

The time delay applies only when a monitored output device changes from its normal state—for example, the Liebert AC4 detects a closed contact that is defined as Normally Open.

When the output device returns to its normal state, the Liebert AC4 acknowledges any input change of state immediately.

The hold delay timer also takes effect when the Liebert AC4 is powered up. All alarms are ignored until the hold delay time expires.

AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT =SELECT

> HOLD DELAY : 10:00

RESTART

: 00:06

Hold Delay Time

HOLD DELAY

10 MIN : 00 SEC ↑↓=NEXT =EDIT

From the Setup Operation Menu, choose Hold Delay, as shown at right, and press Enter .

To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):

For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-99.

Press Enter to advance to seconds (SEC).

For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.

When finished, press Enter again.

7.8.5 Specify Restart Time

Setup Operation Menu

 

The restart delay timer directs the Liebert AC4 to wait a specified time before changing the state of an output. This feature can prevent needless responses to transient conditions.

If two or more outputs change state simultaneously, the Liebert AC4 begins a new countdown between each output change of state.

The default is 6 seconds (displayed as 00 MIN : 06 SEC).

From the Setup Operation Menu, choose Restart, as shown at right, and press Enter .

To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):

For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-99.

Press Enter to advance to seconds (SEC).

AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT =SELECT

HOLD DELAY

:

10:00

> RESTART

:

00:06

Restart Delay Time

RESTART DELAY

00 MIN : 06 SEC

↑↓=NEXT =EDIT

For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.

When finished, press Enter again.

Liebert® AC4

46

Image 52
Contents Liebert AC4 Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Appendix a Service Terminal Interface Setup MenuFigures Methods of Viewing and Configuring the Liebert AC4 Available AlarmsData Logs IntroductionOutside Enclosure Overview LCD for configurationOperation Device Liebert Challenger Typical ConfigurationDevice RS232 LiebertLiebert HimodHimod Controller Board Overview Controller board componentsConnector DIP switchLCD connector 24VAC powerLED indicators summary LED IndicatorsOutput LEDs Status LEDs Input LEDs Typical Sequence Installation Considerations InstallationPacking Contents Unpacking and Preliminary InspectionRequired tools Surface-Mounting the Liebert AC4Mounting the Panel Flush-Mounting the Liebert AC4 Connect Power to the Liebert AC4 Electrical connections to panelWiring and Connections Wiring SpecificationsWiring specifications Connecting Digital Inputs and Outputs Connecting Liebert Precision Cooling UnitsConnecting Digital Inputs Numbering keysSetting the Digital Output Jumpers Connecting Digital OutputsDigital output jumper settings Connecting Common Alarm Outputs RS232 ConnectorCommon alarm outputs Serial interface connector RS232/EIA5Overview of Menus Guide to Liebert AC4 functionsMain Menu Overview Opening Screen OverviewLCD Menu Overview View Status Options View Active Alarms Active AlarmsClearing Active Alarms Active AlarmsView Alarm Log Alarm LogAlarm log conditions Alarm LogView Event Log Event LogEvent log conditions Event LogView Input Status Input StatusViewing Additional Input Data Digital input statesView Output Status Output StatusViewing Additional Output Data Digital output statesSilence Alarm & Backup LOG Files Service Terminal Interface Silence Alarm Service Terminal Interface onlyBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Login LoginSystem and Control Options Valid characters for data entryLogin Screen System & Control menu Clear Alarms&Logs selectedSetup System menu Clear Alarms/Logs menuSetup System Overview Setup System Setup InputsChange Label Name of Input Define Input as Alarmable or EventDefine Input as Normally Open or Normally Closed Set Up Alarmable Inputs in Latched or Unlatched Mode Set Up Delay TimeDelay Time Latched / UnlatchedChange to Reset Y or Not Reset N Setup System Setup Common AlarmReset Common Alarm Setup System Setup Zones Set Up a ZoneMessage if too few devices entered Message if too many devices enteredSetup System Setup Outputs Define Output as Normally Open or Normally ClosedDefine Operating or Standby Mode Enable or Disable an Output Device in Alarm StatusConfigure Output for Loss of Power Fail-Safe Set ModeSetup System Setup System Info Change PasswordChange the Password Reset Password to the Factory Default AaaaSetup Site ID Setup Site IDSet Date & Time/Automatic Daylight Saving Time Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only Perform Firmware UPDATE-YESY or NON? N Setup Operation Select Setup OperationSetup Operation Menu Default settings operation featuresTurn Automatic Sequencing On or Off Activate / DeactivateSet Interval & Start Time 1- to 99-Day Interval Set Start Time Hour IntervalTurn Standby Testing On or Off Change Standby TestingSpecify Failed Standby Response Failed Standby responseSpecify Hold Delay Time Hold Delay TimeRestart Delay Time Setup Operation MenuOverride Output Clear Alarms & Logs Clear Active AlarmsClear the Alarm Log Clear the Event LogLiebert AC4 Specifications SpecificationsSpecifications Liebert AC4 Appendix a Service Terminal Interface Comparison of Functions LCD and Service Terminal InterfaceConnecting to the Service Terminal Interface Create a Connection COM1 Port SetupSpecify COM Port Connection Properties Setup Ascii SetupSettings tab Ascii Setup buttonConnect to the Service Terminal Interface Click on the file name for example, AC4.htSilence Alarm and Backup Log Files Setup Menu OverviewView Status Overview Main Menu For sample screens, seeView Active Alarms View Active AlarmsView Status Menus Main MenuView Alarm Log View Alarm LogView Event Log View Input StatusView Event Log View Input StatusView Output Status View Output StatusSilence Alarm Section A.5.1 Section A.5.2Back Up Alarm Log File Backup Log Files Alarm Log FileBackup Log Files Event Log File Back Up Event Log FileLogin Menu Setup MenuLogin Setup Menu Setup MenuTips on Using the Service Terminal Interface See DescriptionSetup Inputs Setup InputsSetup Common Alarm Setup ZonesSetup Common Alarm Setup ZonesSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Setup Site ID Set Date & TimeBackup & Upload Configuration File Backup Backup & Upload Configuration File Upload Factory DefaultsFirmware Update Service Terminal Interface only Firmware UpdateSetup Operation Auto Sequencing Setup OperationAuto Sequencing Standby Testing Setup Operation Standby TestingHold Delay Setup Operation Failed StandbySetup Operation Hold Delay Failed StandbyRestart Delay Setup Operation Restart DelayOverride Output Override OutputClear Alarms & Logs Clear Active Alarms Clear Alarms & LogsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Specifications Liebert AC4 Specifications Specifications Liebert AC4 Page Ne t Is tTwor k Care