Emerson Process Management 53eA instruction manual Proportional Gain Plus Integral Reset

Page 88

MODEL 54eA

SECTION 15.0

 

CALIBRATION - CONTROL

Proportional (Gain) Plus Integral (Reset)

For the automatic elimination of deviation, I (Integral mode), also referred to as Reset, is used. The propor- tional function is modified by the addition of automatic reset. With the reset mode, the controller continues to change its output until the deviation between measure- ment and set point is eliminated.

The action of the reset mode depends on the propor- tional band. The rate at which it changes the controller output is based on the proportional band size and the reset adjustment. The reset time is the time required for the reset mode to repeat the proportional action once. It is expressed as seconds per repeat, adjustable from 0-2999 seconds.

The reset mode repeats the proportional action as long as an offset from the set point exists. Reset action is cumulative. The longer the offset exists, the more the output signal is increased.

The controller configured with reset continues to change until there is no offset. If the offset persists, the reset action eventually drives the controller output to its 100% limit - a condition known as "reset windup". To prevent reset windup, a controller with reset mode should never be used to control a measured variable influenced by uncorrectable conditions. Once the con- troller is "wound up", the deviation must be eliminated or redirected before the controller can unwind and resume control of the measured variable. The integral time can be cleared and the "windup" condition quick- ly eliminated by manually overriding the analog out- put using the simulate tests feature (detailed in Section 5.4).

Control Loop Adjustment and Tuning

There are several methods for tuning PID loops includ- ing: Ziegler-Nichols frequency response, open loop step response, closed loop step response, and trial and error. Described in this section is a form of the open loop response method called the process reaction curve method. The reaction times and control charac- teristics of installed equipment and real processes are difficult to predict. The process reaction curve method of tuning works well because it is based on the response of the installed system. This procedure, out- lined in the following paragraphs, can be used as a starting point for the P and I settings. Experience has shown that PID controllers will do a fair job of control- ling most processes with many combinations of rea- sonable control mode settings.

Process Reaction Curve Method

A PID loop can be tuned using the process reaction curve method. This method involves making a step change in the chemical feedrate (usually about 50% of the pump or valve range) and graphing the response of the Model 54eA controller reading versus time.

The process reaction curve graphically shows the reac- tion of the process to step change in the input signal. Figure 14-1 shows an example of a tuning process for a pH controller. Similar results can be obtained for the oxygen, ozone, or chlorine controller.

To use this procedure with a Model 54eA controller and a control valve or metering pump, follow the steps out- lined below.

Wire the controller to the control valve or metering pump. Introduce a step change to the process by using the simulate test function to make the step change in the output signal.

Graph the change in the measured variable (concen- tration or pH) as shown in Figure 15-1. Observe the reading on the Model 54eA controller and note values at intervals timed with a stop watch. A strip chart recorder can be used for slower reacting processes. To collect the data, perform the following steps:

1.Let the system come to a steady state where the measured variable (pH, concentration or tempera- ture) is relatively stable.

2.Observe the output current on the main display of the controller.

3.Using the simulate test, manually set the controller output signal at the value which represented the stable process measurement observed in step 1, then observe the process reading to ensure steady state conditions (a stable process measurement).

4.Using the simulate test, cause a step change in the output signal. This change should be large enough to produce a significant change in the measured variable in a reasonable amount of time, but not too large to drive the process out of desired limits.

5.The reaction of the system, when graphed, will resemble Figure 15-1, showing a change in the measured variable over the change in time. After a period of time (the process delay time), the meas- ured variable will start to increase (or decrease) rapidly. At some further time the process will begin to change less rapidly as the process begins to sta- bilize from the imposed step change. It is important to collect data for a long enough period of time to see the process begin to level off to establish a tan- gent to the process reaction curve.

82

Image 88
Contents Model 54eA Amperometric Hart Analyzer/ControllerEssential Instructions Page Model 54eA ANALYZER/CONTROLLER 10.0 11.012.0 13.0Section Title List of FiguresIii Section Specifications Features and ApplicationsSpecifications General PowerOutput Accuracy ± 0.05 mA Alarms Weight/Shipping Weight 5 lb/6 lb 2 kg/2.5 kgSpecifications Oxygen Specifications Free ChlorineSpecifications Total Chlorine Specifications OzoneOrdering Information 115/230 VAC, 50/60 Hz Power24 VDC Installation Section InstallationUnpacking and Inspection Pipe and Wall Mounting Dimensions Pipe mountingPanel Mounting Dimensions Panel mountingPOWER, ALARM, and Output Wiring Section WiringGeneral 454EPH02 Wiring Model 499A oxygen, chlorine, and ozone sensors Sensor WiringGeneral 4054eA01 4054eA03 4054eA02 4054eA04 4054eA07 Alarm Status Section Display and OperationGeneral Description DisplaySection Software Configuration Program Settings ListChoices Factory Settings Configure Choices Factory Settings Temperature compensation Section Menu Tree for the 54eA Controller Main Menu Main Alarm setpoints Alarm 2 setpointMA 0.00 ppm 20 mA 20.00 ppm Output 1 12.00 mA Ranging the OutputsAlarm setpoints Output setpointsSimulated test Setpoint 1.000 ppm 4mA 0.000 ppm 20mA 10.00 ppmSimulated tests Test alarm 1 OpenTest output Configure DisplayTemp units C Output 1 mA Output 2 mA Display contrast Timeout OnLanguage English Display left Display right Out Output 1 control OutputsOutput Measurement Ctrl mode Normal Output 1 SetupOutput 1 Control Range 4-20 mA Dampen 0 sec Hold Last ValueHold setup Using holdChanging Alarm Parameters Always configure the control parameters Before makingChanges in the alarm setup Alarm Control SettingsAlarm 1 control Alarm 1 setupAlarm 2 control Alarm Low Setpoint 0.000 ppmLow Alarm High AlarmAlarm Fault Feed limit DisableTimeout 3600 sec Feed limit timer setupAlarm 4 setup Feed limit timer Interval timerTimer Disable Timer Time activated Interval 24.0 hr Interval timer setupPH sensor Enable PH sensor DisableUsing the 499ACL-01 sensor PH comp Manual PH value 7.00 pHGlass imp lo 20 MΩ Diagnostics OffAutocal Standard Temp coeff Operate iso 7.00 pH Sensor iso 7.00 pHTemperature Compensation and Temperature Units Temp comp AutoTemp units C Temp comp Manual Temp units C60 Hz Noise ReductionMain sensor cal Bar units mm Hg Bar meas AutoBarometric Pressure Lock program Lock config Noise rejection Main sensor calSecurity Lock allCondition Definitions Controller Mode PriorityAction Definitions Section Calibration Temperature IntroductionAdjust temp + 025.1 C Temperature CalibrationSection Calibration Dissolved Oxygen Dissolved Oxygen ConcentrationSensor must be in zero solution Zeroing the SensorStabilizing . . . Wait Calibrating the Sensor in AIRSection Calibrate 8.32 ppm Calibrating the Sensor Against a Standard InstrumentZero main sensor Adjust temperature Calibrate main sensorStandardize Calibrating Barometric PressureSection Calibration Free Chlorine 499ACL-01 Sensor Current as a Function of Free Chlorine ConcentrationCalibrate main sensor Calibrate 1.100 ppm Full Scale CalibrationDual range cal Output trimCalibrate low point Dual Slope CalibrationLow point 2.000 ppm Calibrate high pointSection Calibration Free Chlorine 498CL-01 IntroductionPpm 100ppm 000 ppm Section Calibration Free Chlorine 498CL-01 Section Calibration Total Chlorine This page intentionally left blank Section Calibration Monochloramine Sensor Current as a Function of Monochloramine ConcentrationPpm 100ppm Section Calibration Ozone Sensor Current as a Function of Ozone ConcentrationPpm 100ppm Section PH at 25C Standards Nominal pHAutocal buffer Automatic TWO-POINT Calibration10.02 pH Pt 04.00pH 25C Calibrate pointManual TWO-POINT Calibration 10.01 pH Pt 4.00pH 25.0CStandardization ONE-POINT Calibration Pt calibration Standardize pH pH slope PH slope 60.00 mV/pH Section Calibration Current Outputs Trimming the OutputsSection PID and TPC Control PID Control CodeControl Loop Adjustment and Tuning Proportional Gain Plus Integral ResetProcess Reaction Curve Method Process Reaction Curve Section Time Proportional Control TPC Mode Code Section Troubleshooting Troubleshooting When a Fault Message is ShowingFault message Explanation See Section OverviewTemperature error low or high High input currentCheck sensor zero PH low or high input voltageTroubleshooting When no Fault Message is Showing Oxygen Problem See SectionSense line open Failure factory and Failure eepromZero current is too high Possible error warning during in-process calibrationZero reading Is unstable Barometric pressure reading is too high or too low Process readings are erraticReadings drift Sensor does not respond to changes in oxygen levelProblem Zero current is unstableSensor can be calibrated, but the current is too low Sensor does not respond to changes in chlorine level Chlorine readings are too lowProblem See Section Sensor does not respond to changes in monochloramine level Readings are too low Troubleshooting When no Fault Message is Showing Ozone Sensor does not respond to changes in ozone level Ozone readings are too lowTroubleshooting When no Fault Message is Showing pH Sensor does not respond to known pH changes Controller will not accept manual slope100 Process pH readings are noisy 101Troubleshooting not Related to Measurement Problems Problem ActionSimulating Inputs Dissolved Oxygen Sensor Polarizing Voltage Resistance Expected currentSimulating Inputs Other Amperometric Measurements Simulate Chlorine and Ozone 103Voltage mV PH at 25C Simulating pH input when the preamplifier is in the sensor104 Simulating temperature Simulating Temperature105 Measuring Reference Voltage 106Section Maintenance Replacement Parts Part Number DescriptionSection Return of Material GeneralWarranty Specifications subject to change without notice