Carrier 17EX specifications Start-Up, Operation, and Maintenance Instructions

Page 1

17EX Externally Geared Centrifugal Liquid Chillers 50/60 Hz 1500 to 2250 Nominal Tons (5280 to 7910 kW)

Start-Up, Operation, and Maintenance Instructions

SAFETY CONSIDERATIONS

Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design speci- ®cations. When operating this equipment, use good judg- ment and safety precautions to avoid damage to equip- ment and property or injury to personnel.

Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide.

DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in ac- cordance with the latest edition of ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) 15. The accumulation of refrigerant in an enclosed space can displace oxy- gen and cause asphyxiation.

PROVIDE adequate ventilation in accordance with ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregulari- ties, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.

DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.

NEVER EXCEED speci®ed test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.

DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.

DO NOT VALVE OFF any safety device.

BE SURE that all pressure relief devices are properly installed and functioning before operating any machine.

DO NOT WELD OR FLAME CUT any refrigerant line or vessel until all refrigerant (liquid and vapor) has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with an open ¯ame produces toxic gases.

DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the entire assembly.

DO NOT work on high-voltage equipment unless you are a quali- ®ed electrician.

DO NOT WORK ON electrical components, including control pan- els, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid- state components.

LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, con®rm that all circuits are deenergized be- fore resuming work.

AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If any enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.

NEVER APPLY an open ¯ame or live steam to a refrigerant cyl- inder. Dangerous overpressure can result. When necessary to heat refrigerant, use only warm (110 F [43 C]) water.

DO NOT REUSE disposable (nonreturnable) cylinders or attempt to re®ll them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.

CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller. The introduction of the wrong refrigerant can cause dam- age or malfunction to this chiller.

Operation of this equipment with refrigerants other than those cited herein should comply with ASHRAE-15 (latest edition). Con- tact Carrier for further information on use of this chiller with other refrigerants.

DO NOT ATTEMPT TO REMOVE ®ttings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.

CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at more frequent intervals.

DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.

DO NOT install relief devices in series or backwards.

USE CARE when working near or in line with a compressed spring. Sudden release of the spring can cause it and objects in its path to act as projectiles.

RUN WATER PUMPS when removing, transferring, or charg- ing refrigerant.

DO NOT STEP on refrigerant lines. Broken lines can whip about and cause personal injury.

DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.

USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if com- ponents are light, use such equipment when there is a risk of slip- ping or losing your balance.

BE AWARE that certain automatic start arrangements CAN EN- GAGE THE STARTER. Open the disconnect ahead of the starter in addition to shutting off the machine or pump.

USE only repair or replacement parts that meet the code require- ments of the original equipment.

DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases, or semisolids without permission of your process con- trol group.

DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained.

DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items have been removed before rotating any shafts.

DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.

PERIODICALLY INSPECT all valves, ®ttings, and piping for cor- rosion, rust, leaks, or damage.

PROVIDE A DRAIN connection in the vent line near each pres- sure relief device to prevent a build-up of condensate or rain water.

Manufacturer reserves the right to discontinue, or change at any time, speci®cations or designs without notice and without incurring obligations.

Book

2

 

PC 211

Catalog No. 531-721

Printed in U.S.A.

Form 17EX-1SS

Pg 1

7-97

Replaces: New

Tab

5d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 1
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents OCCPC01S Input Service Congurations Piping Check Relief Devices Inspect WiringCoupling Maintenance Motor Maintenance Inspect Water PipingContents Abbreviations Introduction17EX Chiller Familiarization Certified PerformanceTypical 17EX Chiller Components Lubrication Cycle OIL Cooling CycleRefrigeration, Cycle Starters17EX Compressor Lubrication Cycle Denitions ControlsMajor PIC Components Panel Locations Temperature Sensors See Fig Pressure TransducersPIC Component Panel Location Processor Sensor Input/Output Module Control Center17EX Controls and Sensor Locations PIC LIDPsio GRD Equip GND ÐTewac PROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Operation and Menus FigGeneral LID Service Screen Override Operations YES or no , on or OFF , etc. to select the desired state17EX LID Menu Structure Default ScreenAlarm History Service TableEquipment Configuration Control TestCarrier Comfort Network CCNHgbp Ð Hot Gas Bypass LIDChwr SetpointChws HgbpLID Display Data Description Range Units Reference Point Name Alarm HistoryExample 1 Ð STATUS01 Display Screen Menu Status SelectExample 3 Ð STATUS03 Display Screen Example 2 Ð STATUS02 Display ScreenMenu Status Example 5 Ð Setpoint Display Screen Example 4 Ð STATUS04 Display ScreenMenu ECW Control Option Example 6 Ð Configuration Config Display ScreenICE Build Termination LAG =2, Standby =3 Example 7 Ð LEAD/LAG Configuration Display ScreenExample 8 Ð SERVICE1 Display Screen Spare Alert Enable Example 9 Ð SERVICE2 Display ScreenExample 10 Ð SERVICE3 Display Screen Menu ServiceExample 12 Ð Maintenance MAINT02 Display Screen Example 11 Ð Maintenance MAINT01 Display ScreenDischarge Temperature Bearing TemperatureExample 14 Ð Maintenance MAINT04 Display Screen Example 13 Ð Maintenance MAINT03 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen Example of Holiday Period Screen To Access the Service ScreensRecycle Sequence Fig START-UP/SHUTDOWNPage Job Data Required Before Initial START-UPEquipment Required MotorPage 17EX Leak Test Procedures Ð HFC-134a Pressure Ð Temperature C Ð HFC-134a Pressure Ð Temperature FTemperature F Temperature CDehydration Cold Trap Check Optional Pumpout Compressor Water Pip Inspect Wiring900 500 901 7000 1000 7001-14500 2500 Recommended Motor Fastener Tightening Torques External Gear Pre-Start ChecksExternal Gear Lubrication System Mechanical Starters Check StarterSOLID-STATE Starters Input the Design Set Points Ð To modify the set Set Up Chiller Control CongurationInput the Local Occupied Schedule OCCPC01S Surge Limiting or Change the LID Configuration if NecessaryT1/P1 Full Load Points T2/P2 Increase P1 by Decrease P1 by Load Surge Prevention Occurs TOO Soon Occurs TOO Late50% Initial START-UP Charge Refrigerant into ChillerControl Test Menu Functions Tests to be Devices Tested PerformedCheck Motor Rotation Dry Run to Test Start-Up SequenceInitial Motor START-UP Page Flange Nut Tightening Torques Low Speed Couplings Only Check Oil Pressure and Compressor Stop Calibrate Motor Current Demand SettingTo Prevent Accidental Start-Up Ð The PIC can be General RecommendationsOperator Duties Operating InstructionsStarting the Chiller Stopping the ChillerOperating the Optional Pumpout Compressor Pumpout and Refrigerant Transfer ProceduresPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View Valve Condition RLAReturn Chiller to Normal Operating Conditions General MaintenanceChecking Guide Vane Linkage Ð Refer to Fig Contact Seal Maintenance Refer to ÐContact Seal Page Checking Preliminary Alignment Chiller AlignmentMeasuring Angular Misalignment Elevation Alignment Formula HOT Alignment Check Adjusting Angular Misalignment in PlanDoweling Correcting Parallel MisalignmentScheduled Maintenance Weekly MaintenanceCheck Safety and Operating Controls Monthly Changing the Oil Filters17EX Chiller Oil Specications Compressor OILPumpout Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Controls for Optional Pumpout Compressor Troubleshooting GuidePage MAINT02 MAINT01MAINT03 MAINT04Oilpd 1CR AUXOilt PICAutorestart in Progress Starts Limit ExceededOperation FaultPotential FREEZE-UP Failure to StopRunning Ð Demand Limited Running Ð Temp ControlChiller Protect Limit Faults LOW OIL Pressure Sensor Fault AlertAlert Autorestart PendingDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Problem External Gear Troubleshooting GuidePossible Cause Ð Item NO.s Possible Cause ActionTemperature Voltage Resistance Drop Ð Thermistor Temperature F vs Resistance/Voltage DropTemperature Voltage Resistance Drop Ð Thermistor Temperature C vs Resistance/Voltage DropControl Modules Module SwitchModule Address Input Options ModuleStarter Management Module SMM Fig Processor/Sensor Input/Output Module Psio FigGRD Switch Setting Options Module Installation of NEW Psio ModuleFour-In/Two-Out Module Fig Options Module4-In/2-Out Module Physical Data and Wiring SchematicsWeight Vessel SIZE² Additional Cooler WeightsCondenser Total Weight Condenser Charge 100Compressor Weight and Elbow Weight Additional Condenser WeightsDrive Component Weights 101Ð Total Motor Weight, SI kg Ð Total Motor Weight, English lb102 NIH Waterbox Cover Weights Marine Waterbox Cover WeightsApproximate Refrigerant HCFC-134a Charge 103Relief Valve Locations and Data Auxiliary Systems, Electrical Data104 105 Compressor Fits and ClearancesClearance Type Description 106Measure 107 Tabulation Ð Impeller Clearances Open-Drive Compressors17FX 108 Temp 109Press Tewac110 111 112 General 113GND Ð Ground 114T1-T4 Terminal StripIndex Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.