Carrier 17EX specifications Inspect the Heat Exchanger Tubes

Page 82

Fill the gear drive to the recommended oil level with heated Shell VSI grade 68 oil or its equivalent, heated between 110 and 120 F (43 and 49 C). Do not over®ll. Immediately close the openings to keep the vapors in the housing.

Inspect the unit every 30 days and spray or add rust in- hibitor suitable for anticipated storage conditions, as required.

Drain and replace the oil with the recommended oil type prior to start-up.

·Remove the breather and replace it with a pipe plug. Pack the entire seal area with grease to form a vapor barrier and seal it with tape.

A vapor-phase rust inhibitor, such as Daubert Chemical, Non-Rust Motorstor VCi-10 or its equivalent, may be added to the recommended oil type in the amount of 2% of the total sump capacity. Fill the unit to the recommended level. Do not over®ll.

Inspect the unit every 30 days and spray or add rust in- hibitor suitable for anticipated storage conditions, as required.

The unit may run without changing this oil mixture.

EXTENDED DOWNTIME Ð Consider the length of down- time the unit will undergo. The lubricating oil used in the unit should protect the interior parts for up to 30 days of shutdown. If the unit will be shut down longer than 30 days, it must be operated a minimum of 30 minutes every 30 days to distribute the lubricant to all interior parts.

If it is impractical to operate the unit every 30 days, the long-term storage instructions described above must be fol- lowed. All seals applied for this storage condition must be removed before operating the unit.

Compressor Bearing Maintenance Ð The key to good bearing maintenance is proper lubrication. Use the proper grade of oil, maintained at recommended level, temperature, and pressure. Inspect the lubrication system regularly and thoroughly.

Only a trained service technician should remove and examine the bearings. The bearings should be examined on a scheduled basis for signs of wear. The frequency of ex- amination is determined by the hours of chiller operation, load conditions during operation, and the condition of the oil and the lubrication system. Excessive bearing wear can sometimes be detected through increased vibration or in- creased bearing temperature. If either symptom appears, con- tact an experienced and responsible service organization for assistance.

External Gear Maintenance Ð Perform the re- quired maintenance and recommended intervals. Good pre- ventive maintenance prolongs the life of the unit.

Daily

·Inspect for leaks and loose connections.

·Check the oil level.

·Check the oil temperature and pressure.

·Check for unusual noise and/or vibration.

Weekly Ð Check the oil ®lter.

Monthly

·Obtain oil sample analysis.

·Clean or replace oil ®lters.

·Check the foundation mounting bolts for tightness.

·Clean the air ®lter.

·Check the operation of all auxiliary equipment.

Semi-Annually

·Check gear tooth wear.

·Check the oil and replace it if necessary.

·Check the coupling alignment.

Annually

·Check the heat exchanger for corrosion and clogged tubes.

·Check the bearing clearance and end play.

Disassembly and Assembly Instructions Ð The following in- structions apply to standard high speed gear units.

·Required Equipment: In addition to standard mechanic's

tools, have the following equipment on hand: hoist, sling, torque wrench, feeler gages, and dial indicator.

·General Instructions: Clean external surfaces of the gear unit before removing the cover to prevent contaminants from falling into it. Record the mounting dimensions and the location of accessories for reference when reassem- bling. To remove the gear from its operating area, discon- nect all connected equipment and lift the gear from its foundation using 4 lifting lugs.

Inspect the Heat Exchanger Tubes

COOLER Ð Inspect and clean the cooler tubes at the end of the ®rst operating season. Because these tubes have internal ridges, a rotary-type tube cleaning system is necessary to fully clean the tubes. Upon inspection, the tube condition deter- mines the scheduled frequency for cleaning and indicates whether water treatment is adequate in the chilled water/ brine circuit. Inspect the entering and leaving chilled water temperature sensors for signs of slime, corrosion, or scale. Replace the sensor if corroded or remove any scale if found.

CONDENSER Ð Since this water circuit is usually an open- type system, the tubes may be subject to contamination and scale. Clean the condenser tubes with a rotary tube cleaning system at least once per year and more often if the water is contaminated. Inspect the entering and leaving condenser wa- ter sensors for signs of slime, corrosion, or scale. Replace the sensor if corroded or remove any scale if found.

Higher than normal condenser pressures, together with the inability to reach full refrigeration load, usually indicate dirty tubes or air in the chiller. If the refrigeration log indicates a rise above normal condenser pressures, check the condenser refrigerant temperature against the leaving condenser water temperature. If this reading is more than what the design dif- ference is supposed to be, then the condenser tubes may be dirty, or water ¯ow may be incorrect. Because HFC 134a is a high-pressure refrigerant, air usually does not enter the chiller; rather, the refrigerant leaks out.

During the tube cleaning process, use brushes especially designed to avoid scraping and scratching the tube wall. Con- tact your Carrier representative to obtain these brushes. Do not use wire brushes.

Hard scale may require chemical treatment for its pre- vention or removal. Consult a water treatment specialist for proper treatment.

Water Leaks Ð Water in the refrigerant is indicated dur- ing chiller operation by the refrigerant moisture indicator on the refrigerant motor cooling line. Water leaks should be re- paired immediately.

The chiller must be dehydrated after repair of water leaks. See Chiller Dehydration section, page 49.

Water Treatment Ð Untreated or improperly treated wa- ter may result in corrosion, scaling, erosion, or algae. The services of a quali®ed water treatment specialist should be obtained to develop and monitor a treatment program.

82

Image 82
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Coupling Maintenance Motor Maintenance Piping Check Relief Devices Inspect WiringOCCPC01S Input Service Congurations Inspect Water PipingContents Abbreviations Introduction17EX Chiller Familiarization Performance CertifiedTypical 17EX Chiller Components OIL Cooling Cycle Lubrication CycleStarters Refrigeration, Cycle17EX Compressor Lubrication Cycle Controls DenitionsPIC Component Panel Location Temperature Sensors See Fig Pressure TransducersMajor PIC Components Panel Locations Processor Sensor Input/Output Module Control Center17EX Controls and Sensor Locations PIC LIDPsio GRD Equip GND ÐTewac PROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Operation and Menus FigGeneral LID Service Screen YES or no , on or OFF , etc. to select the desired state Override OperationsDefault Screen 17EX LID Menu StructureEquipment Configuration Service TableAlarm History Control TestHgbp Ð Hot Gas Bypass CCNCarrier Comfort Network LIDChws SetpointChwr HgbpExample 1 Ð STATUS01 Display Screen Description Range Units Reference Point Name Alarm HistoryLID Display Data Menu Status SelectExample 3 Ð STATUS03 Display Screen Example 2 Ð STATUS02 Display ScreenMenu Status Example 5 Ð Setpoint Display Screen Example 4 Ð STATUS04 Display ScreenMenu ECW Control Option Example 6 Ð Configuration Config Display ScreenICE Build Termination Example 7 Ð LEAD/LAG Configuration Display Screen LAG =2, Standby =3Example 8 Ð SERVICE1 Display Screen Example 10 Ð SERVICE3 Display Screen Example 9 Ð SERVICE2 Display ScreenSpare Alert Enable Menu ServiceDischarge Temperature Example 11 Ð Maintenance MAINT01 Display ScreenExample 12 Ð Maintenance MAINT02 Display Screen Bearing TemperatureExample 14 Ð Maintenance MAINT04 Display Screen Example 13 Ð Maintenance MAINT03 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen To Access the Service Screens Example of Holiday Period ScreenSTART-UP/SHUTDOWN Recycle Sequence FigPage Equipment Required Before Initial START-UPJob Data Required MotorPage 17EX Leak Test Procedures Temperature F Ð HFC-134a Pressure Ð Temperature FÐ HFC-134a Pressure Ð Temperature C Temperature CDehydration Cold Trap Check Optional Pumpout Compressor Water Pip Inspect Wiring900 500 901 7000 1000 7001-14500 2500 External Gear Pre-Start Checks Recommended Motor Fastener Tightening TorquesExternal Gear Lubrication System Mechanical Starters Check StarterSOLID-STATE Starters Input the Design Set Points Ð To modify the set Set Up Chiller Control CongurationInput the Local Occupied Schedule OCCPC01S Surge Limiting or Change the LID Configuration if NecessaryT1/P1 Full Load Points T2/P2 Increase P1 by Decrease P1 by Load Surge Prevention Occurs TOO Soon Occurs TOO Late50% Control Test Menu Functions Charge Refrigerant into ChillerInitial START-UP Tests to be Devices Tested PerformedCheck Motor Rotation Dry Run to Test Start-Up SequenceInitial Motor START-UP Page Flange Nut Tightening Torques Low Speed Couplings Only To Prevent Accidental Start-Up Ð The PIC can be Calibrate Motor Current Demand SettingCheck Oil Pressure and Compressor Stop General RecommendationsStarting the Chiller Operating InstructionsOperator Duties Stopping the ChillerPumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout CompressorPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View RLA Valve ConditionGeneral Maintenance Return Chiller to Normal Operating ConditionsContact Seal Maintenance Refer to Ð Checking Guide Vane Linkage Ð Refer to FigContact Seal Page Chiller Alignment Checking Preliminary AlignmentMeasuring Angular Misalignment Elevation Alignment Formula Adjusting Angular Misalignment in Plan HOT Alignment CheckCorrecting Parallel Misalignment DowelingCheck Safety and Operating Controls Monthly Weekly MaintenanceScheduled Maintenance Changing the Oil Filters17EX Chiller Oil Specications Compressor OILPumpout Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Troubleshooting Guide Controls for Optional Pumpout CompressorPage MAINT03 MAINT01MAINT02 MAINT04Oilt 1CR AUXOilpd PICStarts Limit Exceeded Autorestart in ProgressPotential FREEZE-UP FaultOperation Failure to StopRunning Ð Temp Control Running Ð Demand LimitedChiller Protect Limit Faults Alert Sensor Fault AlertLOW OIL Pressure Autorestart PendingDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Possible Cause Ð Item NO.s External Gear Troubleshooting GuideProblem Possible Cause ActionÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Temperature Voltage Resistance DropModule Address Module SwitchControl Modules Input Options ModuleStarter Management Module SMM Fig Processor/Sensor Input/Output Module Psio FigGRD Four-In/Two-Out Module Fig Installation of NEW Psio ModuleSwitch Setting Options Module Options ModulePhysical Data and Wiring Schematics 4-In/2-Out ModuleCondenser Total Weight Condenser Charge Additional Cooler WeightsWeight Vessel SIZE² 100Drive Component Weights Additional Condenser WeightsCompressor Weight and Elbow Weight 101Ð Total Motor Weight, SI kg Ð Total Motor Weight, English lb102 Approximate Refrigerant HCFC-134a Charge Marine Waterbox Cover WeightsNIH Waterbox Cover Weights 103Relief Valve Locations and Data Auxiliary Systems, Electrical Data104 Compressor Fits and Clearances 105Clearance Type Description 106Measure 107 Tabulation Ð Impeller Clearances Open-Drive Compressors17FX 108 Press 109Temp Tewac110 111 112 113 GeneralT1-T4 114GND Ð Ground Terminal StripIndex Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.