Carrier 17EX specifications Physical Data and Wiring Schematics, 4-In/2-Out Module

Page 99

6.Restore control system power (the LID displays, COM- MUNICATION FAILURE at the bottom of the screen).

7.Access the SERVICE menu. Highlight and select the ATTACH TO NETWORK DEVICE screen. Press

the ATTACH softkey. (The LID displays, UPLOAD- ING TABLES. PLEASE WAIT; then, COMMUNICA- TION FAILURE.) Press the EXIT softkey.

8.Turn off control power.

9.Mount the new module in the unit control box using a long-shaft Phillips screwdriver and the screw saved in Step 4 on page 98. Make sure that the green grounding wire is reinstalled along with the mounting screw.

10.Connect the LID communication wires (CCN bus) and the power wires. If CCN wiring has been attached to the CCN bus, disconnect the wires. Attach the sensor bus plug and the input and output plugs.

11.Carefully check all wiring connections before restoring power.

12.Restore control power and verify that the red and green LEDs on the PSIO are functioning properly.

13.The LID should indicate AVAILABLE MEMORY and a value. This value should start to decrease. (If it does not, check the LID wiring to the PSIO; ensure connec- tion to the proper plug.) The bottom of the screen dis- plays, UPLOADING TABLES, PLEASE WAIT.

14.After the PSIO tables have been uploaded into the LID, access the STATUS01 screen. Move the highlight bar to the TOTAL COMPRESSOR STARTS line. Press the

SELECT softkey and then, using the INCREASE or

DECREASE softkeys, change the value until it is the

same as the value from the old module. Press the ENTER softkey to save this value.

15.Move the highlight bar to the COMPRESSOR ONTIME line. Press the SELECT softkey and the, us-

ing the INCREASE or DECREASE softkeys, change this value until it matches the old module run hours. Press the SELECT softkey to save this value.

16.Change the address of the PSIO In the CONTROLLER IDENTIFICATION table back to its previous value. Write the address on the PSIO.

17.Use the con®guration sheets (pages CL-3 to CL-11) to input set point, con®guration, and schedule information into the PSIO. The TIME AND DATE table from the SERVICE menu must also be set. A Building Supervi- sor terminal can be used to download the old con®gu- ration into the PSIO.

18.Access the CONTROL TEST table and perform the con- trol tests to verify all that all tested functions are work- ing properly.

If the software version has been updated, a CCN down- load of the con®guration will not be allowed. Con®gure the PSIO by hand, and upload the PSIO into the net- work using the ATTACH TO NETWORK DEVICE screen.

19.Restore the chiller to normal operation; calibrate the mo- tor amps.

PHYSICAL DATA AND WIRING

SCHEMATICS

Tables 15-26 and Fig. 56-61 provide additional informa- tion regarding compressor ®ts and clearances, physical and electrical data, and wiring schematics for operator conve- nience during troubleshooting.

Fig. 55 Ð 4-In/2-Out Module

99

Image 99
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents Inspect Water Piping Piping Check Relief Devices Inspect WiringOCCPC01S Input Service Congurations Coupling Maintenance Motor MaintenanceContents Introduction Abbreviations17EX Chiller Familiarization Certified PerformanceTypical 17EX Chiller Components Lubrication Cycle OIL Cooling CycleRefrigeration, Cycle Starters17EX Compressor Lubrication Cycle Denitions ControlsProcessor Sensor Input/Output Module Control Center Temperature Sensors See Fig Pressure TransducersMajor PIC Components Panel Locations PIC Component Panel Location17EX Controls and Sensor Locations LID PICPsio Equip GND Ð GRDTewac LID Operation and Menus Fig PROCESSOR/SENSOR INPUT/OUTPUT Module PsioGeneral LID Service Screen Override Operations YES or no , on or OFF , etc. to select the desired state17EX LID Menu Structure Default ScreenControl Test Service TableAlarm History Equipment ConfigurationLID CCNCarrier Comfort Network Hgbp Ð Hot Gas BypassHgbp SetpointChwr ChwsMenu Status Select Description Range Units Reference Point Name Alarm HistoryLID Display Data Example 1 Ð STATUS01 Display ScreenExample 2 Ð STATUS02 Display Screen Example 3 Ð STATUS03 Display ScreenMenu Status Example 4 Ð STATUS04 Display Screen Example 5 Ð Setpoint Display ScreenMenu Example 6 Ð Configuration Config Display Screen ECW Control OptionICE Build Termination LAG =2, Standby =3 Example 7 Ð LEAD/LAG Configuration Display ScreenExample 8 Ð SERVICE1 Display Screen Menu Service Example 9 Ð SERVICE2 Display ScreenSpare Alert Enable Example 10 Ð SERVICE3 Display ScreenBearing Temperature Example 11 Ð Maintenance MAINT01 Display ScreenExample 12 Ð Maintenance MAINT02 Display Screen Discharge TemperatureExample 13 Ð Maintenance MAINT03 Display Screen Example 14 Ð Maintenance MAINT04 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen Example of Holiday Period Screen To Access the Service ScreensRecycle Sequence Fig START-UP/SHUTDOWNPage Motor Before Initial START-UPJob Data Required Equipment RequiredPage 17EX Leak Test Procedures Temperature C Ð HFC-134a Pressure Ð Temperature FÐ HFC-134a Pressure Ð Temperature C Temperature FDehydration Cold Trap Inspect Wiring Check Optional Pumpout Compressor Water Pip900 500 901 7000 1000 7001-14500 2500 Recommended Motor Fastener Tightening Torques External Gear Pre-Start ChecksExternal Gear Lubrication System Check Starter Mechanical StartersSOLID-STATE Starters Set Up Chiller Control Conguration Input the Design Set Points Ð To modify the setInput the Local Occupied Schedule OCCPC01S Change the LID Configuration if Necessary Surge Limiting orT1/P1 Full Load Points T2/P2 Load Surge Prevention Occurs TOO Soon Occurs TOO Late Increase P1 by Decrease P1 by50% Tests to be Devices Tested Performed Charge Refrigerant into ChillerInitial START-UP Control Test Menu FunctionsDry Run to Test Start-Up Sequence Check Motor RotationInitial Motor START-UP Page Flange Nut Tightening Torques Low Speed Couplings Only General Recommendations Calibrate Motor Current Demand SettingCheck Oil Pressure and Compressor Stop To Prevent Accidental Start-Up Ð The PIC can beStopping the Chiller Operating InstructionsOperator Duties Starting the ChillerOperating the Optional Pumpout Compressor Pumpout and Refrigerant Transfer ProceduresPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View Valve Condition RLAReturn Chiller to Normal Operating Conditions General MaintenanceChecking Guide Vane Linkage Ð Refer to Fig Contact Seal Maintenance Refer to ÐContact Seal Page Checking Preliminary Alignment Chiller AlignmentMeasuring Angular Misalignment Elevation Alignment Formula HOT Alignment Check Adjusting Angular Misalignment in PlanDoweling Correcting Parallel MisalignmentChanging the Oil Filters Weekly MaintenanceScheduled Maintenance Check Safety and Operating Controls MonthlyCompressor OIL 17EX Chiller Oil SpecicationsPumpout Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Controls for Optional Pumpout Compressor Troubleshooting GuidePage MAINT04 MAINT01MAINT02 MAINT03PIC 1CR AUXOilpd OiltAutorestart in Progress Starts Limit ExceededFailure to Stop FaultOperation Potential FREEZE-UPRunning Ð Demand Limited Running Ð Temp ControlChiller Protect Limit Faults Autorestart Pending Sensor Fault AlertLOW OIL Pressure AlertDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Possible Cause Action External Gear Troubleshooting GuideProblem Possible Cause Ð Item NO.sTemperature Voltage Resistance Drop Ð Thermistor Temperature F vs Resistance/Voltage DropTemperature Voltage Resistance Drop Ð Thermistor Temperature C vs Resistance/Voltage DropInput Options Module Module SwitchControl Modules Module AddressProcessor/Sensor Input/Output Module Psio Fig Starter Management Module SMM FigGRD Options Module Installation of NEW Psio ModuleSwitch Setting Options Module Four-In/Two-Out Module Fig4-In/2-Out Module Physical Data and Wiring Schematics100 Additional Cooler WeightsWeight Vessel SIZE² Condenser Total Weight Condenser Charge101 Additional Condenser WeightsCompressor Weight and Elbow Weight Drive Component WeightsÐ Total Motor Weight, English lb Ð Total Motor Weight, SI kg102 103 Marine Waterbox Cover WeightsNIH Waterbox Cover Weights Approximate Refrigerant HCFC-134a ChargeAuxiliary Systems, Electrical Data Relief Valve Locations and Data104 105 Compressor Fits and Clearances106 Clearance Type DescriptionMeasure Tabulation Ð Impeller Clearances Open-Drive Compressors 10717FX 108 Tewac 109Temp Press110 111 112 General 113Terminal Strip 114GND Ð Ground T1-T4Index Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.