Carrier 17EX specifications OIL Cooling Cycle, Lubrication Cycle

Page 8

The chiller compressor continuously draws large quanti- ties of refrigerant vapor from the cooler at a rate determined by the amount of guide vane opening. This compressor suc- tion reduces the pressure within the cooler, allowing the liq- uid refrigerant to boil vigorously at a fairly low temperature (typically 38 to 42 F [3 to 6 C]).

The liquid refrigerant obtains the energy needed to va- porize by removing heat from the water or brine in the cooler tubes. The cold water or brine can then be used in air con- ditioning and/or other processes.

After removing heat from the water or brine, the refrig- erant vapor enters the ®rst stage of the compressor, is compressed, and ¯ows into the compressor second stage. Here it is mixed with ¯ash-economizer gas and is further compressed.

Compression raises the refrigerant temperature above that of the water ¯owing through the condenser tubes. When the warm (typically 98 to 102 F [37 to 40 C]) refrig- erant vapor comes into contact with the condenser tubes, the relatively cool condensing water (typically 85 to 95 F [29 to 35 C]) removes some of the heat, and the vapor con- denses into a liquid.

The liquid refrigerant passes through an ori®ce into the FLASC chamber. The coolest condenser water ¯ows through the FLASC and allows a lower saturated temperature and pressure. Part of the entering liquid refrigerant will ¯ash to vapor once it has passed through the FLASC ori®ce, thereby cooling the remaining liquid. The vapor is then recondensed by the condenser water ¯owing through the FLASC chamber.

The subcooled liquid refrigerant drains into a high-side valve chamber that meters the refrigerant liquid into a ¯ash economizer chamber. Pressure in this chamber is interme- diate between condenser and cooler pressures. At this lower pressure, some of the liquid refrigerant ¯ashes to gas, fur- ther cooling the remaining liquid. The ¯ash gas, having ab- sorbed heat, is returned directly to the compressor second stage. Here it is mixed with discharge gas that is already com- pressed by the ®rst-stage impeller. Since the ¯ash gas has to pass through only half the compression cycle to reach con- denser pressure, there is a savings in power.

The cooled liquid refrigerant in the economizer is me- tered through the low-side valve chamber, reducing the re- frigerant pressure. Pressure in the cooler is lower than in the economizer. Some of the liquid ¯ashes as it passes through the low side ¯oat valve. The cycle is now complete.

OIL COOLING CYCLE

Compressor Oil Cooling Ð The compressor oil is water cooled. Water ¯ow through the oil cooler is manually adjusted by a plug valve to maintain an operating tempera- ture at the reservoir of approximately 145 F (63 C). An oil heater in the reservoir helps to prevent oil from being di- luted by the refrigerant. The heater is controlled by the PIC (Product Integrated Control) and is energized when the oil temperature is outside the operating temperature range of 150 to 160 F (66 to 71 C).

External Gear Oil Cooling Ð The external gear oil is also water cooled. Water ¯ow through the gear oil cooler is manually adjusted by a plug valve to maintain an oper- ating temperature of approximately 130 F (54 C). If so equipped, an oil heater in the reservoir helps to maintain the oil tem- perature under cold ambient operating conditions. The heater is controlled by an internal thermostat.

LUBRICATION CYCLE

Compressor Lubrication Cycle (Refer to item numbers shown in Fig. 4) Ð The compressor oil pump and oil reservoir are contained in the compressor base. Oil is pumped through an oil cooler and ®lter to remove heat and any foreign particles. A portion of the oil is then di- rected to the shaft-end bearing and the shaft seal. The bal- ance of the oil lubricates the thrust and journal bearings and the thrust end seal. The bearing and transmission oil returns directly to the reservoir to complete the cycle. Contact-seal oil leakage, however, is collected in an atmospheric ¯oat cham- ber to be pumped back to the main reservoir as the oil accumulates.

Oil may be charged into the compressor oil reservoir (Item 8) through a charging valve (Item 6) which also func- tions as an oil drain. If there is refrigerant in the chiller, how- ever, a hand pump will be required for charging at this connection.

An oil-charging elbow (Item 3) on the seal-oil return cham- ber allows oil to be added without pumping. The seal-oil re- turn pump (Item 4) automatically transfers the oil to the main reservoir. Sight glasses (11) on the reservoir wall permit ob- servation of the oil level.

A motor-driven oil pump (Item 10) discharges oil to an oil cooler/®lter (Item 16) at a rate and pressure controlled by an oil regulator (Item 10). The differential oil pressure (bearing supply versus oil reservoir) is registered on the control panel.

Water ¯ow through the oil cooler is manually adjusted by a plug valve (Item 17) to maintain the oil at an operating temperature of approximately 145 F (63 C). During shut- down, the oil temperature is also maintained at 150 to 160 F (65 to 71 C) by an immersion heater (Item 7) in order to minimize absorption of refrigerant by the oil.

Upon leaving the cooler section of the oil cooler/®lter, the oil is ®ltered (Item 15) and a portion is directed to the seal- end bearing (Item 1) and the shaft seal (Item 2). The remain- der lubricates thrust (Item 14) and journal bearings (Item 12). Thrust bearing temperature is indicated on the PIC controls. Oil from both circuits returns by gravity to the reservoir.

The shaft seal of the open compressor drive must be kept full of lubrication oil, even when the chiller is not operating, to prevent loss of refrigerant.

If the chiller is not operating and the oil pump has not operated during the last 12 hours, the control system auto- matically runs the oil pump for one minute in order to keep the contact seal ®lled with oil.

IMPORTANT: If the control power is to be deener- gized for more than one day, the chiller refrigerant should be pumped over to the economizer/storage vessel.

8

Image 8
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Piping Check Relief Devices Inspect Wiring OCCPC01S Input Service CongurationsCoupling Maintenance Motor Maintenance Inspect Water PipingContents 17EX Chiller Familiarization IntroductionAbbreviations Performance CertifiedTypical 17EX Chiller Components OIL Cooling Cycle Lubrication CycleStarters Refrigeration, Cycle17EX Compressor Lubrication Cycle Controls DenitionsTemperature Sensors See Fig Pressure Transducers Major PIC Components Panel LocationsPIC Component Panel Location Processor Sensor Input/Output Module Control Center17EX Controls and Sensor Locations Psio LIDPIC Tewac Equip GND ÐGRD General LID Operation and Menus FigPROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Service Screen YES or no , on or OFF , etc. to select the desired state Override OperationsDefault Screen 17EX LID Menu StructureService Table Alarm HistoryEquipment Configuration Control TestCCN Carrier Comfort NetworkHgbp Ð Hot Gas Bypass LIDSetpoint ChwrChws HgbpDescription Range Units Reference Point Name Alarm History LID Display DataExample 1 Ð STATUS01 Display Screen Menu Status SelectMenu Status Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen Menu Example 4 Ð STATUS04 Display ScreenExample 5 Ð Setpoint Display Screen ICE Build Termination Example 6 Ð Configuration Config Display ScreenECW Control Option Example 7 Ð LEAD/LAG Configuration Display Screen LAG =2, Standby =3Example 8 Ð SERVICE1 Display Screen Example 9 Ð SERVICE2 Display Screen Spare Alert EnableExample 10 Ð SERVICE3 Display Screen Menu ServiceExample 11 Ð Maintenance MAINT01 Display Screen Example 12 Ð Maintenance MAINT02 Display ScreenDischarge Temperature Bearing TemperatureDescription RANGE/STATUS Units Reference Point Name Example 13 Ð Maintenance MAINT03 Display ScreenExample 14 Ð Maintenance MAINT04 Display Screen PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen To Access the Service Screens Example of Holiday Period ScreenSTART-UP/SHUTDOWN Recycle Sequence FigPage Before Initial START-UP Job Data RequiredEquipment Required MotorPage 17EX Leak Test Procedures Ð HFC-134a Pressure Ð Temperature F Ð HFC-134a Pressure Ð Temperature CTemperature F Temperature CDehydration Cold Trap 900 500 901 7000 1000 7001-14500 2500 Inspect WiringCheck Optional Pumpout Compressor Water Pip External Gear Pre-Start Checks Recommended Motor Fastener Tightening TorquesExternal Gear Lubrication System SOLID-STATE Starters Check StarterMechanical Starters Input the Local Occupied Schedule OCCPC01S Set Up Chiller Control CongurationInput the Design Set Points Ð To modify the set T1/P1 Full Load Points T2/P2 Change the LID Configuration if NecessarySurge Limiting or 50% Load Surge Prevention Occurs TOO Soon Occurs TOO LateIncrease P1 by Decrease P1 by Charge Refrigerant into Chiller Initial START-UPControl Test Menu Functions Tests to be Devices Tested PerformedInitial Motor START-UP Dry Run to Test Start-Up SequenceCheck Motor Rotation Page Flange Nut Tightening Torques Low Speed Couplings Only Calibrate Motor Current Demand Setting Check Oil Pressure and Compressor StopTo Prevent Accidental Start-Up Ð The PIC can be General RecommendationsOperating Instructions Operator DutiesStarting the Chiller Stopping the ChillerPumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout CompressorPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View RLA Valve ConditionGeneral Maintenance Return Chiller to Normal Operating ConditionsContact Seal Maintenance Refer to Ð Checking Guide Vane Linkage Ð Refer to FigContact Seal Page Chiller Alignment Checking Preliminary AlignmentMeasuring Angular Misalignment Elevation Alignment Formula Adjusting Angular Misalignment in Plan HOT Alignment CheckCorrecting Parallel Misalignment DowelingWeekly Maintenance Scheduled MaintenanceCheck Safety and Operating Controls Monthly Changing the Oil FiltersPumpout Compressor OIL17EX Chiller Oil Specications Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Troubleshooting Guide Controls for Optional Pumpout CompressorPage MAINT01 MAINT02MAINT03 MAINT041CR AUX OilpdOilt PICStarts Limit Exceeded Autorestart in ProgressFault OperationPotential FREEZE-UP Failure to StopRunning Ð Temp Control Running Ð Demand LimitedChiller Protect Limit Faults Sensor Fault Alert LOW OIL PressureAlert Autorestart PendingDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY External Gear Troubleshooting Guide ProblemPossible Cause Ð Item NO.s Possible Cause ActionÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Temperature Voltage Resistance DropModule Switch Control ModulesModule Address Input Options ModuleGRD Processor/Sensor Input/Output Module Psio FigStarter Management Module SMM Fig Installation of NEW Psio Module Switch Setting Options ModuleFour-In/Two-Out Module Fig Options ModulePhysical Data and Wiring Schematics 4-In/2-Out ModuleAdditional Cooler Weights Weight Vessel SIZE²Condenser Total Weight Condenser Charge 100Additional Condenser Weights Compressor Weight and Elbow WeightDrive Component Weights 101102 Ð Total Motor Weight, English lbÐ Total Motor Weight, SI kg Marine Waterbox Cover Weights NIH Waterbox Cover WeightsApproximate Refrigerant HCFC-134a Charge 103104 Auxiliary Systems, Electrical DataRelief Valve Locations and Data Compressor Fits and Clearances 105Measure 106Clearance Type Description 17FX Tabulation Ð Impeller Clearances Open-Drive Compressors107 108 109 TempPress Tewac110 111 112 113 General114 GND Ð GroundT1-T4 Terminal StripIndex Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.