Carrier 17EX Operation, Potential FREEZE-UP, Failure to Stop, Loss, Communication, Fault

Page 88

Table 12 Ð LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

G. START-UP FAILURES: This is an alarm condition. A manual reset is required to clear.

PRIMARY MESSAGE

SECONDARY MESSAGE

 

 

 

 

 

 

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

FAILURE TO START

LOW OIL PRESSURE

OILPD [VALUE] exceeded limit of [LIMIT]*. Check

Check for closed oil supply valves. Check oil ®lter.

 

 

oil pump system.

Check for low oil temperature. Check transducer

 

 

 

 

 

 

 

 

 

 

 

 

accuracy.

FAILURE TO START

OIL PRESS SENSOR FAULT

OILPD [VALUE] exceeded limit of [LIMIT]*. Check

Check for excessive refrigerant in oil sump. Run oil

 

 

oil pressure sensor.

pump manually for 5 minutes. Check calibration of

 

 

 

 

 

 

 

 

 

 

 

 

oil pressure differential ampli®er modules. Check wir-

 

 

 

 

 

 

 

 

 

 

 

 

ing. Replace transducers if necessary.

FAILURE TO START

LOW CHILLED WATER FLOW

EVFL Evap Flow Fault: Check water pump/¯ow

Check wiring to ¯ow switch. Check through CON-

 

 

switch.

TROL TEST for proper switch operation.

FAILURE TO START

LOW CONDENSER

CDFL Cond. Flow Fault: Check water pump/¯ow

Check wiring to ¯ow switch. Check through CON-

 

WATER FLOW

switch.

TROL TEST for proper switch operation.

FAILURE TO START

STARTER FAULT

STR

 

 

 

 

FLT Starter Fault: Check Starter for Fault

A starter protective device has faulted. Check starter

 

 

Source.

for ground fault, voltage trip, temperature trip, etc.

FAILURE TO START

STARTER OVERLOAD TRIP

STR

 

 

 

 

FLT Starter Overload Trip: Check amps

Reset overloads, check ICR relay before restarting

 

 

calibration/reset overload.

chiller.

FAILURE TO START

LINE VOLTAGE DROPOUT

V

 

 

 

P Single-Cycle Dropout Detected: Check volt-

Check voltage supply. Check transformers for sup-

 

 

age supply.

ply. Check with utility if voltage supply is erratic. Moni-

 

 

 

 

 

 

 

 

 

 

 

 

tor must be installed to con®rm consistent, single-

 

 

 

 

 

 

 

 

 

 

 

 

cycle dropouts. Check low oil pressure switch.

FAILURE TO START

HIGH CONDENSER

High Condenser Pressure [LIMIT]:* Check switch

Check for proper design condenser ¯ow and tem-

 

PRESSURE

2C aux, and water temperature/¯ow.

perature. Check condenser approach. Check 2C aux-

 

 

 

 

 

 

 

 

 

 

 

 

iliary contacts on oil sump starter. Check high pres-

 

 

 

 

 

 

 

 

 

 

 

 

sure switch.

FAILURE TO START

EXCESS ACCELERATION

CA

 

 

 

 

P Excess Acceleration: Check guide vane clo-

Check that guide vanes are closed at start-up. Check

 

TIME

sure at start-up.

starter for proper operation. Reduce unit pressure

 

 

 

 

 

 

 

 

 

 

 

 

if possible.

FAILURE TO START

STARTER TRANSITION

RUN

 

 

 

AUX Starter Transition Fault: Check 1CR/

Check starter for proper operation.

 

FAULT

1M/Interlock mechanism.

Run contact failed to close.

FAILURE TO START

1CR AUX CONTACT FAULT

1CR

 

 

 

 

AUX Starter Contact Fault: Check 1CR/1M

Check starter for proper operation.

 

 

aux. contacts.

Start contact failed to close.

FAILURE TO START

MOTOR AMPS NOT SENSED

CA

 

 

P Motor Amps Not Sensed: Check motor load

Check for proper motor amps signal to SMM. Check

 

 

signal.

wiring from SMM to current transformer. Check main

 

 

 

 

 

 

 

 

 

 

 

 

motor circuit breaker for trip.

FAILURE TO START

CHECK REFRIGERANT TYPE

Current Refrigerant Properties Abnormal Ð Check

Pressures at transducers indicate another refriger-

 

 

Selection of refrigerant type.

ant type in control test. Make sure to access the AT-

 

 

 

 

 

 

 

 

 

 

 

 

TACH TO NETWORK DEVICE screen after speci-

 

 

 

 

 

 

 

 

 

 

 

 

fying HFC-134a refrigerant type.

FAILURE TO START

LOW OIL PRESSURE

Low Oil Pressure [LIMIT]:* Check oil pressure switch/

The oil pressure differential switch is open when the

 

 

pump and 2C aux.

compressor tried to start. Check the switch for proper

 

 

 

 

 

 

 

 

 

 

 

 

operation. Also, check the oil pump interlock (2C aux)

 

 

 

 

 

 

 

 

 

 

 

 

in the power panel and the high condenser pres-

 

 

 

 

 

 

 

 

 

 

 

 

sure switch.

FAILURE TO START

LOW GEAR OIL PRESSURE

GEAROILP [VALUE] exceeded limit of [LIMIT].*

Check for closed oil supply valves. Check oil ®lter.

 

 

Check gear oil pump/®lter.

Check transducer accuracy.

FAILURE TO START

GEAR OIL PRESSURE SENSOR

Gear Oil Pressure Transducer Out of Range [VALUE].

Check calibration of transducer. Replace if

 

 

 

 

 

 

 

 

 

 

 

 

necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point prede®ned or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

H. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

UNAUTHORIZED

UNIT SHOULD BE

CA

 

 

 

P Emergency: Compressor

Compressor is running with more than 10% RLA

OPERATION

STOPPED

running without control authorization.

and control is trying to shut it down. Turn power

 

 

 

 

 

 

 

 

 

off to compressor if unable to stop. Determine cause

 

 

 

 

 

 

 

 

 

before re-powering.

POTENTIAL FREEZE-UP

EVAP PRESS/TEMP

ERT Emergency: Freeze-up

Determine cause. If pumping refrigerant out of

 

TOO LOW

prevention.

chiller, stop operation and go over pumpout

 

 

 

 

 

 

 

 

 

procedures.

FAILURE TO STOP

DISCONNECT POWER

RUN

 

 

 

AUX Emergency: DISCONNECT

Starter run and start contacts are energized while

 

 

POWER.

control tried to shut down. Disconnect power to

 

 

 

 

 

 

 

 

 

starter.

LOSS OF

WITH STARTER

Loss of Communication with Starter: Check

Check wiring from PSIO to SMM. Check SMM mod-

COMMUNICATION

 

chiller.

ule troubleshooting procedures.

STARTER CONTACT

ABNORMAL 1CR OR

1CR

 

 

AUX Starter Contact Fault: Check

Starter run and start contacts energized while chiller

FAULT

RUN AUX

1CR/1M aux. contacts.

was off. Disconnect power.

POTENTIAL FREEZE UP

COND PRESS/TEMP

CRT [VALUE] exceeded limit of [LIMIT]*

The condenser pressure transducer is reading a

 

TOO LOW

Emergency: Freeze-up prevention.

pressure that could freeze the water in the con-

 

 

 

 

 

 

 

 

 

denser tubes. Check for condenser refrigerant leaks,

 

 

 

 

 

 

 

 

 

bad transducers, or transferred refrigerant. Place

 

 

 

 

 

 

 

 

 

the unit in PUMPDOWN mode to eliminate the

 

 

 

 

 

 

 

 

 

alarm if vessel is evacuated.

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point prede®ned or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

88

Image 88
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Piping Check Relief Devices Inspect Wiring OCCPC01S Input Service CongurationsCoupling Maintenance Motor Maintenance Inspect Water PipingContents Abbreviations Introduction17EX Chiller Familiarization Performance CertifiedTypical 17EX Chiller Components OIL Cooling Cycle Lubrication CycleStarters Refrigeration, Cycle17EX Compressor Lubrication Cycle Controls DenitionsTemperature Sensors See Fig Pressure Transducers Major PIC Components Panel LocationsPIC Component Panel Location Processor Sensor Input/Output Module Control Center17EX Controls and Sensor Locations PIC LIDPsio GRD Equip GND ÐTewac PROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Operation and Menus FigGeneral LID Service Screen YES or no , on or OFF , etc. to select the desired state Override OperationsDefault Screen 17EX LID Menu StructureService Table Alarm HistoryEquipment Configuration Control TestCCN Carrier Comfort NetworkHgbp Ð Hot Gas Bypass LIDSetpoint ChwrChws HgbpDescription Range Units Reference Point Name Alarm History LID Display DataExample 1 Ð STATUS01 Display Screen Menu Status SelectExample 3 Ð STATUS03 Display Screen Example 2 Ð STATUS02 Display ScreenMenu Status Example 5 Ð Setpoint Display Screen Example 4 Ð STATUS04 Display ScreenMenu ECW Control Option Example 6 Ð Configuration Config Display ScreenICE Build Termination Example 7 Ð LEAD/LAG Configuration Display Screen LAG =2, Standby =3Example 8 Ð SERVICE1 Display Screen Example 9 Ð SERVICE2 Display Screen Spare Alert EnableExample 10 Ð SERVICE3 Display Screen Menu ServiceExample 11 Ð Maintenance MAINT01 Display Screen Example 12 Ð Maintenance MAINT02 Display ScreenDischarge Temperature Bearing TemperatureExample 14 Ð Maintenance MAINT04 Display Screen Example 13 Ð Maintenance MAINT03 Display ScreenDescription RANGE/STATUS Units Reference Point Name PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen To Access the Service Screens Example of Holiday Period ScreenSTART-UP/SHUTDOWN Recycle Sequence FigPage Before Initial START-UP Job Data RequiredEquipment Required MotorPage 17EX Leak Test Procedures Ð HFC-134a Pressure Ð Temperature F Ð HFC-134a Pressure Ð Temperature CTemperature F Temperature CDehydration Cold Trap Check Optional Pumpout Compressor Water Pip Inspect Wiring900 500 901 7000 1000 7001-14500 2500 External Gear Pre-Start Checks Recommended Motor Fastener Tightening TorquesExternal Gear Lubrication System Mechanical Starters Check StarterSOLID-STATE Starters Input the Design Set Points Ð To modify the set Set Up Chiller Control CongurationInput the Local Occupied Schedule OCCPC01S Surge Limiting or Change the LID Configuration if NecessaryT1/P1 Full Load Points T2/P2 Increase P1 by Decrease P1 by Load Surge Prevention Occurs TOO Soon Occurs TOO Late50% Charge Refrigerant into Chiller Initial START-UPControl Test Menu Functions Tests to be Devices Tested PerformedCheck Motor Rotation Dry Run to Test Start-Up SequenceInitial Motor START-UP Page Flange Nut Tightening Torques Low Speed Couplings Only Calibrate Motor Current Demand Setting Check Oil Pressure and Compressor StopTo Prevent Accidental Start-Up Ð The PIC can be General RecommendationsOperating Instructions Operator DutiesStarting the Chiller Stopping the ChillerPumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout CompressorPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View RLA Valve ConditionGeneral Maintenance Return Chiller to Normal Operating ConditionsContact Seal Maintenance Refer to Ð Checking Guide Vane Linkage Ð Refer to FigContact Seal Page Chiller Alignment Checking Preliminary AlignmentMeasuring Angular Misalignment Elevation Alignment Formula Adjusting Angular Misalignment in Plan HOT Alignment CheckCorrecting Parallel Misalignment DowelingWeekly Maintenance Scheduled MaintenanceCheck Safety and Operating Controls Monthly Changing the Oil Filters17EX Chiller Oil Specications Compressor OILPumpout Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Troubleshooting Guide Controls for Optional Pumpout CompressorPage MAINT01 MAINT02MAINT03 MAINT041CR AUX OilpdOilt PICStarts Limit Exceeded Autorestart in ProgressFault OperationPotential FREEZE-UP Failure to StopRunning Ð Temp Control Running Ð Demand LimitedChiller Protect Limit Faults Sensor Fault Alert LOW OIL PressureAlert Autorestart PendingDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY External Gear Troubleshooting Guide ProblemPossible Cause Ð Item NO.s Possible Cause ActionÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Temperature Voltage Resistance DropModule Switch Control ModulesModule Address Input Options ModuleStarter Management Module SMM Fig Processor/Sensor Input/Output Module Psio FigGRD Installation of NEW Psio Module Switch Setting Options ModuleFour-In/Two-Out Module Fig Options ModulePhysical Data and Wiring Schematics 4-In/2-Out ModuleAdditional Cooler Weights Weight Vessel SIZE²Condenser Total Weight Condenser Charge 100Additional Condenser Weights Compressor Weight and Elbow WeightDrive Component Weights 101Ð Total Motor Weight, SI kg Ð Total Motor Weight, English lb102 Marine Waterbox Cover Weights NIH Waterbox Cover WeightsApproximate Refrigerant HCFC-134a Charge 103Relief Valve Locations and Data Auxiliary Systems, Electrical Data104 Compressor Fits and Clearances 105Clearance Type Description 106Measure 107 Tabulation Ð Impeller Clearances Open-Drive Compressors17FX 108 109 TempPress Tewac110 111 112 113 General114 GND Ð GroundT1-T4 Terminal StripIndex Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.