Carrier 17EX Operating Instructions, Operator Duties, Starting the Chiller, Stopping the Chiller

Page 62

Instruct the Operator Ð Check to be sure that the op- erator(s) understands all operating and maintenance proce- dures. Point out the various chiller parts and explain their function as part of the complete system.

COOLER-CONDENSER Ð Relief devices, temperature sen- sor locations, pressure transducer locations, Schrader ®t- tings, waterboxes and tubes, and vents and drains.

ECONOMIZER/STORAGE VESSEL Ð Float chambers, re- lief valves, charging valve.

PUMPOUT SYSTEM Ð Transfer valves and pumpout sys- tem, refrigerant charging and pumpdown procedure, lubri- cation, and relief devices.

COMPRESSOR ASSEMBLY Ð Guide vane actuator, trans- mission, oil cooling system, temperature and pressure sen- sors, oil sight glasses, integral oil pump, isolatable oil ®lter, extra oil and motor temperature sensors, synthetic oil, and compressor serviceability.

COMPRESSOR LUBRICATION SYSTEM Ð Oil pump, cooler ®lter, oil heater, oil charge and speci®cation, operat- ing and shutdown oil level, temperature and pressure, oil charg- ing connections, and seal oil chambers.

EXTERNAL GEAR LUBRICATION SYSTEM Ð Oil pump, cooler/®lter, oil charge and speci®cation, operating and shut- down oil level, temperature and pressure, and oil charging procedures.

CONTROL SYSTEM Ð CCN and local start, reset, menu, softkey functions, LID operation, occupancy schedule, set points, safety controls, and auxiliary and optional controls.

AUXILIARY EQUIPMENT Ð Starters and disconnects, sepa- rate electrical sources, pumps, and cooling tower.

CHILLER CYCLES Ð Refrigerant, motor cooling, lubri- cation, and oil reclaim cycles.

MAINTENANCE Ð Scheduled, routine, and extended shut- downs; importance of a log sheet, water treatment, tube clean- ing, and maintaining a leak-free chiller.

SAFETY DEVICES AND PROCEDURES Ð Electrical dis- connects, relief device inspection, and handling refrigerant.

CHECK OPERATOR KNOWLEDGE Ð Start, stop, and shut- down procedures, safety and operating controls, refrigerant and oil charging, and job safety.

THIS MANUAL Ð Be sure that the operator is familiar with the contents of this manual.

OPERATING INSTRUCTIONS

Operator Duties

1.Become familiar with chiller refrigeration and related equip- ment before operating the chiller.

2.Prepare the system for start-up, start and stop the chiller, and place the system in a shutdown condition.

3.Maintain a log of operating conditions and document any abnormal readings.

4.Inspect the equipment, make routine adjustments, and per- form a controls test. Maintain the proper oil and refrig- erant levels.

5.Protect the system from damage during shutdown periods.

6.Maintain the set point, time schedules, and other PIC functions.

Prepare the Chiller for Start-Up Ð Follow the steps described in the Initial Start-Up section, page 57.

Starting the Chiller

1. Start the water pumps if they are not automatic.

2. On the LID default screen, press the LOCAL or

CCN softkey to start the system. If the schedule indi- cates that the current time and date have been established as a run time and date (a condition referred to as ``oc- cupied'') and the 3- and 15-minute start timers have ex- pired, the start sequence will start. Follow the procedure described in the Start-Up/Shutdown/Recycle Sequence section, page 43.

Check the Running System Ð After the compres- sor starts, monitor the LID display and observe the param- eters for normal operating conditions:

1.The oil reservoir temperature should be above 150 F (66 C) or refrigerant temperature plus 70° F (38° C) dur- ing shutdown and above 125 F (52 C) during compressor operation.

2.The bearing oil temperature (BEARING TEMPERA- TURE on the STATUS01 screen) should be 150 to 200 F (65 to 93 C). If the bearing oil temperature reads more than 210 F (99 C) with the oil pump running, stop the chiller and determine the cause of the high temperature. Do not restart the chiller until corrected.

3.The oil level should be visible in the lower sight glass when the compressor is running. At shutdown, oil level should be halfway in the lower sight glass.

4.The oil pressure should be between 18 and 30 psid (124 to 207 kPad) differential, as seen on the LID default screen. Typically the reading will be 18 to 25 psid (124 to 172 kPad) at initial start-up.

5.The condenser pressure and temperature vary with the chiller design conditions. Typically the pressure ranges between 57 and 135 psig (393 and 930 kPa) with a corresponding temperature range of 60 to 105 F (15 to 41 C) for R-134a. The condenser entering water temperature should be con- trolled to remain below the speci®ed design entering wa- ter temperature to save on compressor kilowatt require- ments. The leaving condenser water temperature should be at least 20° F (11° C) above leaving chilled water temperature.

6.Cooler pressure and temperature also vary with the de- sign conditions. Typical cooler pressure ranges between 30 and 40 psig (206 and 275 kPa); temperature ranges between 34 and 45 F (1 and 8 C) for R-134a).

7.The compressor may operate at full capacity for a short time after the pulldown ramping has ended, even though the building load is small. The active electrical demand setting can be overridden to limit the compressor IkW, or the pulldown rate can be decreased to avoid a high de- mand charge for the short period of high demand operation. Pulldown rate can be based on kW rate (LOAD PULLDOWN %/MIN) or temperature rate (TEMP PULL- DOWN DEG/MIN) These parameters may be accessed on the CONFIG screen (see Table 2, Example 6).

8.The oil pump is energized once every 12 hours during shutdown periods to ensure that the shaft seal is ®lled with oil.

Stopping the Chiller

1.The occupancy schedule starts and stops the chiller au- tomatically once the time schedule is set up.

2.Pressing the Stop button on the control panel for one sec- ond causes the alarm light to blink once to con®rm that the button has been pressed. Then, the compressor fol- lows the normal shutdown sequence as described in the Controls section. The chiller is now in the OFF mode.

The chiller will not restart until the CCN or LOCAL softkey is pressed.

62

Image 62
Contents Start-Up, Operation, and Maintenance Instructions Safety ConsiderationsContents Coupling Maintenance Motor Maintenance Piping Check Relief Devices Inspect WiringOCCPC01S Input Service Congurations Inspect Water PipingContents 17EX Chiller Familiarization IntroductionAbbreviations Performance CertifiedTypical 17EX Chiller Components OIL Cooling Cycle Lubrication CycleStarters Refrigeration, Cycle17EX Compressor Lubrication Cycle Controls DenitionsPIC Component Panel Location Temperature Sensors See Fig Pressure TransducersMajor PIC Components Panel Locations Processor Sensor Input/Output Module Control Center17EX Controls and Sensor Locations Psio LIDPIC Tewac Equip GND ÐGRD General LID Operation and Menus FigPROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Service Screen YES or no , on or OFF , etc. to select the desired state Override OperationsDefault Screen 17EX LID Menu StructureEquipment Configuration Service TableAlarm History Control TestHgbp Ð Hot Gas Bypass CCNCarrier Comfort Network LIDChws SetpointChwr HgbpExample 1 Ð STATUS01 Display Screen Description Range Units Reference Point Name Alarm HistoryLID Display Data Menu Status SelectMenu Status Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen Menu Example 4 Ð STATUS04 Display ScreenExample 5 Ð Setpoint Display Screen ICE Build Termination Example 6 Ð Configuration Config Display ScreenECW Control Option Example 7 Ð LEAD/LAG Configuration Display Screen LAG =2, Standby =3Example 8 Ð SERVICE1 Display Screen Example 10 Ð SERVICE3 Display Screen Example 9 Ð SERVICE2 Display ScreenSpare Alert Enable Menu ServiceDischarge Temperature Example 11 Ð Maintenance MAINT01 Display ScreenExample 12 Ð Maintenance MAINT02 Display Screen Bearing TemperatureDescription RANGE/STATUS Units Reference Point Name Example 13 Ð Maintenance MAINT03 Display ScreenExample 14 Ð Maintenance MAINT04 Display Screen PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen To Access the Service Screens Example of Holiday Period ScreenSTART-UP/SHUTDOWN Recycle Sequence FigPage Equipment Required Before Initial START-UPJob Data Required MotorPage 17EX Leak Test Procedures Temperature F Ð HFC-134a Pressure Ð Temperature FÐ HFC-134a Pressure Ð Temperature C Temperature CDehydration Cold Trap 900 500 901 7000 1000 7001-14500 2500 Inspect WiringCheck Optional Pumpout Compressor Water Pip External Gear Pre-Start Checks Recommended Motor Fastener Tightening TorquesExternal Gear Lubrication System SOLID-STATE Starters Check StarterMechanical Starters Input the Local Occupied Schedule OCCPC01S Set Up Chiller Control CongurationInput the Design Set Points Ð To modify the set T1/P1 Full Load Points T2/P2 Change the LID Configuration if NecessarySurge Limiting or 50% Load Surge Prevention Occurs TOO Soon Occurs TOO LateIncrease P1 by Decrease P1 by Control Test Menu Functions Charge Refrigerant into ChillerInitial START-UP Tests to be Devices Tested PerformedInitial Motor START-UP Dry Run to Test Start-Up SequenceCheck Motor Rotation Page Flange Nut Tightening Torques Low Speed Couplings Only To Prevent Accidental Start-Up Ð The PIC can be Calibrate Motor Current Demand SettingCheck Oil Pressure and Compressor Stop General RecommendationsStarting the Chiller Operating InstructionsOperator Duties Stopping the ChillerPumpout and Refrigerant Transfer Procedures Operating the Optional Pumpout CompressorPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View RLA Valve ConditionGeneral Maintenance Return Chiller to Normal Operating ConditionsContact Seal Maintenance Refer to Ð Checking Guide Vane Linkage Ð Refer to FigContact Seal Page Chiller Alignment Checking Preliminary AlignmentMeasuring Angular Misalignment Elevation Alignment Formula Adjusting Angular Misalignment in Plan HOT Alignment CheckCorrecting Parallel Misalignment DowelingCheck Safety and Operating Controls Monthly Weekly MaintenanceScheduled Maintenance Changing the Oil FiltersPumpout Compressor OIL17EX Chiller Oil Specications Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Troubleshooting Guide Controls for Optional Pumpout CompressorPage MAINT03 MAINT01MAINT02 MAINT04Oilt 1CR AUXOilpd PICStarts Limit Exceeded Autorestart in ProgressPotential FREEZE-UP FaultOperation Failure to StopRunning Ð Temp Control Running Ð Demand LimitedChiller Protect Limit Faults Alert Sensor Fault AlertLOW OIL Pressure Autorestart PendingDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Possible Cause Ð Item NO.s External Gear Troubleshooting GuideProblem Possible Cause ActionÐ Thermistor Temperature F vs Resistance/Voltage Drop Temperature Voltage Resistance DropÐ Thermistor Temperature C vs Resistance/Voltage Drop Temperature Voltage Resistance DropModule Address Module SwitchControl Modules Input Options ModuleGRD Processor/Sensor Input/Output Module Psio FigStarter Management Module SMM Fig Four-In/Two-Out Module Fig Installation of NEW Psio ModuleSwitch Setting Options Module Options ModulePhysical Data and Wiring Schematics 4-In/2-Out ModuleCondenser Total Weight Condenser Charge Additional Cooler WeightsWeight Vessel SIZE² 100Drive Component Weights Additional Condenser WeightsCompressor Weight and Elbow Weight 101102 Ð Total Motor Weight, English lbÐ Total Motor Weight, SI kg Approximate Refrigerant HCFC-134a Charge Marine Waterbox Cover WeightsNIH Waterbox Cover Weights 103104 Auxiliary Systems, Electrical DataRelief Valve Locations and Data Compressor Fits and Clearances 105Measure 106Clearance Type Description 17FX Tabulation Ð Impeller Clearances Open-Drive Compressors107 108 Press 109Temp Tewac110 111 112 113 GeneralT1-T4 114GND Ð Ground Terminal StripIndex Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.