Carrier 17EX specifications

Page 59

Under normal conditions, for the self-lubricating bear- ing, the rate of temperature rise should be from 20° to 25° F (11° to 14° C) during the ®rst 10 minutes after starting up and approximately 40° F (22° C) over 30 minutes. The rate of bearing temperature rise is a function of the natural ventilation and operating conditions.

When the rate of bearing temperature rise is less than 2° F (1.1° C) per half-hour, the bearing temperature is considered to be stabilized.

If the total bearing temperature exceeds 195 F (91 C), the motor should be shut down immediately.

3.Any abnormal noise or vibration should be immediately investigated and corrected. Increased vibration (with the motor uncoupled from its load) can indicate a change in balance due to a mechanical failure or loose rotor part, a stator winding problem, a foundation problem, or a change in motor alignment.

4.Verify that the magnetic center indicator aligns with the shaft.

Initial Coupled Start-Up Ð After initial uncoupled start-up, take the following steps to ensure safe coupled operation:

1.Follow the procedure stated in the General Maintenance, Chiller Alignment section to align the motor to the driven chiller.

2.Prepare the coupling for operation according to the Disc Coupling Installation and Alignment instructions, this page. Note any match marks on the couplings and assemble ac- cordingly. For sleeve bearing motors, verify that the cor- rect limited end ¯oat coupling has been installed. The end ¯oat limits can be found on the certi®ed drawing.

3.Ensure that all personnel are at a safe distance from ro- tating parts. Start the motor in accordance with instruc- tions supplied with the motor control.

4.If the motor rotor fails to start turning in a second or two, shut off the power supply immediately. This can result from:

a.too low a voltage at the motor terminals

b.the load is too much for the rotor to accelerate

c.the load is frozen up mechanically

d.all required electrical connections are not made

e.single-phase power has been applied

f.any combination of the above.

Investigate thoroughly and take corrective action before attempting a restart.

5.Carefully observe the vibration of the bearing housing and any abnormal noise generator. Note that coupled motor vibration may not be the same as uncoupled vibration amounts. If coupled vibration is excessive, recheck the mounting and alignment.

6.Carefully observe the bearing temperature rise and the movement of the oil ring.

If the bearing temperatures rise and motor operation ap- pears normal, operation should continue until the bearing temperatures stabilize.

7.If possible, check the motor line currents for balance.

Note that each start time an induction motor starts, it is subjected to the full inrush of current along with heating of the stator and rotor windings. Each acceleration and re- peated start can produce more heat than is produced and dis- sipated by the motor under full load. The starting duty for which the motor is designed is shown on a nameplate mounted on the motor. Do not exceed this amount if long motor life is expected.

Abnormally low terminal voltage, excessive load torque, and/or excessive load inertia during motor start-up can cause lengthened acceleration times during which rotor ventilation is reduced. This can cause rotor damage or can lead to short- ened rotor life.

The temperature rating of the motor is shown on the main nameplate as a temperature rise above an ambient tempera- ture. If there is a service factor, it is also shown. If the motor temperature switch opens, investigate the situation before at- tempting to continue operation.

If the motor is a TEWAC (Totally Enclosed Water-to-Air Cooled) design, the maximum inlet water temperature and the water ¯ow rate or gpm (gallons per minute) at the air cooler must be as shown on the certi®ed drawing. Other- wise, the discharge air temperature from the cooler (actually the ambient air for the motor as shown by the main name- plate) could be too high for the motor to properly cool.

Disc Coupling Installation and Alignment Ð Be- fore installing the disc coupling, inspect it for any signs of damage during shipment. Check that all parts are available, as ordered. Cradle or support the coupling components dur- ing handling to avoid damage. Wrap the components for pro- tection. Keep ¯anges free of nicks and burrs. Read all the instructions and review this procedure before beginning the actual installation. Some steps apply only to certain types of couplings (e.g., high speed coupling).

Use only the bolts and nuts supplied by the coupling manufacturer.

1.Installing the Coupling Hubs (Keyed Mounting).

a.Check the hub bore and shaft for nicks and burrs; dress if necessary.

b.For taper bores, check the ®t of the bore to the shaft.

c.Fit keys precisely to the keyways in the shaft and hub. Each key should have a tight ®t on the sides with a slight clearance on top. To maintain dynamic balance, the keys should ®ll the keyways exactly and not be too short or too long.

d.Clean the hub bore and shaft.

e.Heat the hub to expand the bore. DO NOT allow the hub temperature to exceed 600 F (300 C). DO NOT apply an open ¯ame to any part of the coupling. Car- rier recommends using an oven to heat the hub.

To avoid the risk of explosion, ®re, or damage to the coupling and equipment and/or injury to per- sonnel, do not use an open ¯ame or oil bath to ex- pand the hub. If heat is used at anytime for instal- lation, DO NOT ALLOW the hub temperature to exceed 600 F (300 C).

f.Place the hub in the proper position on the shaft. Hold the hub in place as it cools. For tapered bores, verify the hub advance and install the shaft retaining nut.

59

Image 59
Contents Safety Considerations Start-Up, Operation, and Maintenance InstructionsContents Inspect Water Piping Piping Check Relief Devices Inspect WiringOCCPC01S Input Service Congurations Coupling Maintenance Motor MaintenanceContents 17EX Chiller Familiarization IntroductionAbbreviations Certified PerformanceTypical 17EX Chiller Components Lubrication Cycle OIL Cooling CycleRefrigeration, Cycle Starters17EX Compressor Lubrication Cycle Denitions ControlsProcessor Sensor Input/Output Module Control Center Temperature Sensors See Fig Pressure TransducersMajor PIC Components Panel Locations PIC Component Panel Location17EX Controls and Sensor Locations Psio LIDPIC Tewac Equip GND ÐGRD General LID Operation and Menus FigPROCESSOR/SENSOR INPUT/OUTPUT Module Psio LID Service Screen Override Operations YES or no , on or OFF , etc. to select the desired state17EX LID Menu Structure Default ScreenControl Test Service TableAlarm History Equipment ConfigurationLID CCNCarrier Comfort Network Hgbp Ð Hot Gas BypassHgbp SetpointChwr ChwsMenu Status Select Description Range Units Reference Point Name Alarm HistoryLID Display Data Example 1 Ð STATUS01 Display ScreenMenu Status Example 2 Ð STATUS02 Display ScreenExample 3 Ð STATUS03 Display Screen Menu Example 4 Ð STATUS04 Display ScreenExample 5 Ð Setpoint Display Screen ICE Build Termination Example 6 Ð Configuration Config Display ScreenECW Control Option LAG =2, Standby =3 Example 7 Ð LEAD/LAG Configuration Display ScreenExample 8 Ð SERVICE1 Display Screen Menu Service Example 9 Ð SERVICE2 Display ScreenSpare Alert Enable Example 10 Ð SERVICE3 Display ScreenBearing Temperature Example 11 Ð Maintenance MAINT01 Display ScreenExample 12 Ð Maintenance MAINT02 Display Screen Discharge TemperatureDescription RANGE/STATUS Units Reference Point Name Example 13 Ð Maintenance MAINT03 Display ScreenExample 14 Ð Maintenance MAINT04 Display Screen PIC System Functions Page Protective Safety Limits and Control Settings Capacity Overrides Page Page ECW Cent Capacity ICE Build Setpoint Example of Attach to Network Device Screen Example of Holiday Period Screen To Access the Service ScreensRecycle Sequence Fig START-UP/SHUTDOWNPage Motor Before Initial START-UPJob Data Required Equipment RequiredPage 17EX Leak Test Procedures Temperature C Ð HFC-134a Pressure Ð Temperature FÐ HFC-134a Pressure Ð Temperature C Temperature FDehydration Cold Trap 900 500 901 7000 1000 7001-14500 2500 Inspect WiringCheck Optional Pumpout Compressor Water Pip Recommended Motor Fastener Tightening Torques External Gear Pre-Start ChecksExternal Gear Lubrication System SOLID-STATE Starters Check StarterMechanical Starters Input the Local Occupied Schedule OCCPC01S Set Up Chiller Control CongurationInput the Design Set Points Ð To modify the set T1/P1 Full Load Points T2/P2 Change the LID Configuration if NecessarySurge Limiting or 50% Load Surge Prevention Occurs TOO Soon Occurs TOO LateIncrease P1 by Decrease P1 by Tests to be Devices Tested Performed Charge Refrigerant into ChillerInitial START-UP Control Test Menu FunctionsInitial Motor START-UP Dry Run to Test Start-Up SequenceCheck Motor Rotation Page Flange Nut Tightening Torques Low Speed Couplings Only General Recommendations Calibrate Motor Current Demand SettingCheck Oil Pressure and Compressor Stop To Prevent Accidental Start-Up Ð The PIC can beStopping the Chiller Operating InstructionsOperator Duties Starting the ChillerOperating the Optional Pumpout Compressor Pumpout and Refrigerant Transfer ProceduresPlant Chiller Serial No Chiller Model No Refrigerant Type Rear View Valve Condition RLAReturn Chiller to Normal Operating Conditions General MaintenanceChecking Guide Vane Linkage Ð Refer to Fig Contact Seal Maintenance Refer to ÐContact Seal Page Checking Preliminary Alignment Chiller AlignmentMeasuring Angular Misalignment Elevation Alignment Formula HOT Alignment Check Adjusting Angular Misalignment in PlanDoweling Correcting Parallel MisalignmentChanging the Oil Filters Weekly MaintenanceScheduled Maintenance Check Safety and Operating Controls MonthlyPumpout Compressor OIL17EX Chiller Oil Specications Typical Float Valve Arrangement Sleeve Bearings Page Motor Riggings Inspect the Heat Exchanger Tubes Controls for Optional Pumpout Compressor Troubleshooting GuidePage MAINT04 MAINT01MAINT02 MAINT03PIC 1CR AUXOilpd OiltAutorestart in Progress Starts Limit ExceededFailure to Stop FaultOperation Potential FREEZE-UPRunning Ð Demand Limited Running Ð Temp ControlChiller Protect Limit Faults Autorestart Pending Sensor Fault AlertLOW OIL Pressure AlertDESCRIPTION/MALFUNCTION Probable CAUSE/REMEDY Possible Cause Action External Gear Troubleshooting GuideProblem Possible Cause Ð Item NO.sTemperature Voltage Resistance Drop Ð Thermistor Temperature F vs Resistance/Voltage DropTemperature Voltage Resistance Drop Ð Thermistor Temperature C vs Resistance/Voltage DropInput Options Module Module SwitchControl Modules Module AddressGRD Processor/Sensor Input/Output Module Psio FigStarter Management Module SMM Fig Options Module Installation of NEW Psio ModuleSwitch Setting Options Module Four-In/Two-Out Module Fig4-In/2-Out Module Physical Data and Wiring Schematics100 Additional Cooler WeightsWeight Vessel SIZE² Condenser Total Weight Condenser Charge101 Additional Condenser WeightsCompressor Weight and Elbow Weight Drive Component Weights102 Ð Total Motor Weight, English lbÐ Total Motor Weight, SI kg 103 Marine Waterbox Cover WeightsNIH Waterbox Cover Weights Approximate Refrigerant HCFC-134a Charge104 Auxiliary Systems, Electrical DataRelief Valve Locations and Data 105 Compressor Fits and ClearancesMeasure 106Clearance Type Description 17FX Tabulation Ð Impeller Clearances Open-Drive Compressors107 108 Tewac 109Temp Press110 111 112 General 113Terminal Strip 114GND Ð Ground T1-T4Index Index Index Index Index Copyright 1997 Carrier Corporation

17EX specifications

The Carrier 17EX is recognized as an innovative air conditioning solution that combines efficiency with advanced technology. This model is designed to meet the increasing demands of residential and commercial cooling needs while maintaining environmental consciousness.

One of the standout features of the Carrier 17EX is its impressive Seasonal Energy Efficiency Ratio (SEER) rating. With a SEER rating that often exceeds 17, this unit ensures optimized energy consumption, significantly lowering operational costs for users. The incorporation of advanced compressor technology allows the system to adjust its cooling output based on the specific needs of the environment, thus providing both comfort and energy savings.

The Carrier 17EX utilizes a variable-speed inverter-driven compressor that enhances its performance and adaptability. This technology allows the air conditioning unit to operate at different speeds, intelligently adjusting to changing load conditions. As a result, the system runs more efficiently and quietly, providing a more consistent comfort level without the abrupt temperature swings associated with traditional units.

In addition to efficiency, the Carrier 17EX also prioritizes reliability and durability. The unit comes with a robust cabinet that protects the components from weather elements, ensuring longevity and consistent performance. The innovative design integrates a corrosion-resistant finish and robust insulation, which further enhances the unit's resilience in various environmental conditions.

For users concerned about indoor air quality, the Carrier 17EX includes advanced filtration systems designed to capture allergens and airborne particles. This feature is particularly beneficial for individuals with respiratory issues, ensuring that the air circulated within the space is clean and healthy.

Moreover, the Carrier 17EX is equipped with smart technology capabilities, allowing users to control their systems remotely through smartphones or other smart devices. This connectivity not only provides convenience but also empowers homeowners to optimize their energy use by adjusting settings on the fly, ensuring efficient operation even when they are away from home.

Overall, the Carrier 17EX stands out in the marketplace for its exceptional energy efficiency, advanced technology, and commitment to providing reliable and effective cooling solutions. Its combination of modern features makes it a preferred choice for those looking to enhance comfort while being mindful of energy consumption and environmental impact.